Ohio Admin. Code 4123:1-5-18 - Control of air contaminants
Abrasive wheel and buffing wheel exhaust systems
shall
will be
separate when the dust from the buffing wheel is of flammable material.
When toxic materials are generated in hazardous concentrations
during their application, drying, or handling, they shall
will be
minimized or eliminated by at least one of the methods described in paragraph
(C) of this rule.
Hazardous concentrations of air contaminants produced by
internal combustion engines shall
will be exhausted.
Each exhaust or ventilating fan located less than seven feet
above the floor or normal working level shall
will be
guarded.
Exhaust ductwork shall
will be sized in accordance with good design
practice which shall
will include consideration of fan capacity,
length of duct, number of turns and elbows, variation in size, volume, and
character of materials being exhausted.
The outlet from every separator or (collector)
shall
will
discharge the air contaminants collected by the exhaust system, in such manner
that the discharged materials shall
will not re-enter the working area in hazardous
concentrations.
Air supply openings or inlets through which air enters the
building or room in which the local exhaust system is in operation
shall
will be
isolated from any known source of contamination from outside of the
building.
Notes
Promulgated Under: 119.03
Statutory Authority: 4121.12, 4121.121, 4121.13
Rule Amplifies: 4121.47
Prior Effective Dates: 04/01/1964, 08/01/1977, 01/01/1986, 04/10/2011, 06/01/2016