(A) Features added
during installation.
Optional equipment or features shall not take the home out of
conformance with the requirements of the MHCSS and these standards.
(B) Expanding rooms.
The support and anchoring systems for expanding rooms shall be
installed in accordance with designs provided by the home manufacturer or
prepared by a registered professional engineer or registered architect in
accordance with acceptable engineering practice.
(C) Optional appliances.
(1) Comfort cooling systems. When not
provided and installed by the home manufacturer, comfort cooling systems shall
be installed according to the appliance manufacturer's installation
instructions.
(a) Air conditioners. Air
conditioning equipment shall be listed or certified by a nationally recognized
testing agency for the application for which the unit is intended and installed
in accordance with the terms of its listing or certification.
(i) Energy efficiency.
(a) Site-installed central air conditioning
equipment shall be sized to meet the home's heat gain requirement, in
accordance with chapter twenty-eight of the 2007 ASHRAE "Handbook of Fundamentals" or ACCA
"Manual J, Residential Cooling Load," eighth edition.
(b) The BTU per hour rated capacity of the
site-installed air conditioning equipment shall not exceed the air distribution
system's rated BTU per hour capacity as shown on the home's compliance
certificate.
(ii)
Circuit rating. If a manufactured home is factory provided with an exterior
outlet to energize heating and/or air conditioning equipment, the branch
circuit rating on the tag adjacent to this outlet shall be equal to or greater
than the minimum circuit amperage identified on the equipment rating
plate.
(iii) A-coil units.
(a) A-coil air conditioning units shall be
compatible and listed for use with the furnace in the home and installed in
accordance with the appliance manufacturer's instructions.
(b) The air conditioner manufacturer's
instructions shall be followed.
(c)
All condensation shall be directed beyond the perimeter of the home by means
specified by the equipment manufacturer.
(b) Heat pumps. Heat pumps shall be listed or
certified by a nationally recognized testing agency for the application for
which the unit is intended and installed in accordance with the terms of its
listing or certification.
(2) Fireplace and wood-stove chimneys and air
inlets. Fireplace and wood-stove chimneys and air inlets shall be listed for
use with manufactured homes and shall be installed in accordance with their
listings.
(3) Appliance venting.
(a) All heat -
producing appliances, except ranges and ovens, shall be vented to the exterior of the
home.
(b) When the vent exhausts
through the floor, the vent shall not terminate under the home and shall extend
to the home's exterior and through any skirting or foundation wall that may be
installed.
(4) Flood
hazard areas.
(a) Outside appliances.
Appliances installed on the manufactured home site shall be anchored and
elevated to or above the same elevation as the minimum flood elevation of the
lowest floor of the home.
(b) Air
inlets and exhausts. Appliance air inlets and exhausts shall be located at or
above the same elevation as the minimum flood elevation of the lowest floor of
the home.
(5) Clothes
dryer exhaust system duct. A clothes dryer exhaust duct system shall conform
with and be completed in accordance with the appliance manufacturer
's instructions and rule
4781-6- 02.6
4781-6-
03.6 of the Administrative Code. The vents shall exhaust to the exterior
of the home, beyond any perimeter skirting installed around it, as shown in
figure 5A of this rule.
Click to
view image
(D) Skirting.
(1) Skirting, if used, shall be of
weather-resistant materials.
(2)
Skirting shall not be attached in a manner that can cause water to be trapped
between the siding and trim or forced up into the wall cavities trim to which
it is attached.
(3) All wood
skirting within six inches of the ground shall be pressure treated in
accordance with AWPA "Standard U1 for Use Category 4A, Ground Anchor Contact
Applications" or be naturally resistant to decay and termite
infestations.
(4) Skirting shall
not be attached in a manner that impedes the contraction and expansion
characteristics of the home's exterior covering and siding.
(E) Crawlspace ventilation.
(1) A crawlspace with solid skirting shall be
provided with ventilation openings. The minimum net area of ventilation
openings must not be less than one square foot for every one hundred fifty
square feet of the home's floor area.
The total area of ventilation openings may be reduced to one
square foot for every fifteen hundred square feet of the home's floor area,
where uniform six mil polyethylene vapor retarder or other acceptable vapor
retarder required under rule 4781-6-
02.2
4781-6- 03.2 of the Administrative
Code is placed on the ground surface beneath the entire floor area of the home
with a minimum of four vents per enclosed crawlspace area.
(2) Ventilation openings shall be placed as
high as practicable above the ground and located on at least two opposite sides
to provide cross-ventilation. The vents shall be located within three feet of
the corners of the home and unobstructed.
(3) Ventilation openings shall be covered for
their full height and width with a perforated corrosion and weather resistant
covering that is designed to prevent the entry of rodents. In areas subject to
freezing, the coverings for the ventilation openings shall be of the adjustable
type, permitting them to be in the open or closed position, depending on the
climatic conditions.
(4) Access
opening(s) not less than eighteen inches in width and twenty- four inches in height and not less than three square
feet in area shall be provided and shall be located so that any utility
connections located under the home are accessible.
(5) Condensate drains, water heater drains,
and furnace drains shall be provided when specified by the HVAC manufacturer's
installation instructions and in the absence of manufacturer's installation
instructions, where condensate is discharged from equipment. All condensate
pans and collectors shall have condensate drains. HVAC condensation drains
shall pass to the outside or into another approved drain
which
that
passes to the outside of the home. Drains shall be supported in accordance with
paragraph (D) of rule 4781-6- 02.6
4781-6- 03.6of the Administrative Code.
(6) Dryer vents and combustion air inlets
shall pass through the skirting to the outside of the home. See figure 5A
"Dryer Exhaust system" of the Administrative
Code
this rule.