(A)
Container valves and accessories, filling and discharge connections
:
(1) Each filling
connection shall be provided with combination back-pressure check valve and
excess flow valve; one double or two single back-pressure check valves; or a
positive shut-off valve in conjunction with either an internal back-pressure
check valve or an internal excess flow valve.
;
(2) All vapor and liquid connections, except
safety-relief valves and those specifically exempt in rule
901:5-3-06 of the
Administrative Code shall be equipped with approved excess flow valves; or in
lieu thereof, may be fitted with approved quick-closing internal valves which,
except during operating periods, shall remain closed
.
;
(3) Each storage container shall be provided
with a pressure gage graduated from zero to four hundred psig. Gages shall be
designated for use in ammonia service.
;
(4) All
containers shall be equipped with an approved vapor return valve.
; and
(5) All containers shall be equipped with a
fixed maximum liquid level gage.
(B) Safety relief devices
:
Every container shall be provided with one or more safety
relief valves of spring-loaded or equivalent type and shall comply with the
following:
(1) The discharge from
safety relief valves shall be directed away from the container upward and
unobstructed to the open air. Vent pipes shall not be restrictive or smaller in
size than the safety relief valve outlet connection. All safety relief valve
discharges shall have suitable rain caps that will allow free discharge of the
vapor and prevent the entrance of water. Suitable provision shall be made for
draining condensate which may accumulate; and
(2) If
desired, vent pipes from two or more safety relief devices located on the same
unit, or similar lines from two or more different units, may be run into a
common header, provided the cross-sectional area of such header is at least
equal to the sum of the cross-sectional areas of the individual vent
pipes.
(C) Installation
of storage containers
:
(1) Containers shall be provided with
substantial reinforced concrete footings and foundations or structural steel
supports mounted on reinforced concrete foundations. In either case, the
reinforced concrete foundations or footings shall extend below the established
frost line and shall be of sufficient width and thickness to support the total
weight of the containers and contents adequately. The foundation shall maintain
the lowest point of the tank at not less than eighteen inches above the ground.
Floating type foundations shall also be acceptable providing the foundations
are designed to adequately support the tank, contents and pumping
equipment.
;
(2)
Horizontal aboveground containers shall be mounted on foundations in such a
manner as to permit expansion and contraction. Every container shall be
supported so as to prevent the concentration of excessive loads on the
supporting portion of the shell. The bearing afforded by the saddles shall
extend over at least one third of the circumference of the shell. Suitable
means for preventing corrosion shall be provided on that portion of the
container in contact with the foundations or saddles.
;
(3) Distance between containers shall be at
least five feet, end to end or side to side.
; and
(4) Only two supports shall be used per
container.
(D) Marking
of containers
:
(1) Aboveground uninsulated containers shall
have a reflective surface maintained in good condition. White is recommended
for painted surfaces, but other light reflecting colors are acceptable.
; and
(2) Each container or group of containers
shall be marked on at least two sides with the words "Anhydrous Ammonia" in
sharply contrasting colors with letters not less than
four
three
inches high.
(E) Marking
of appurtenances
:
(1) All container openings, except safety
relief valves, liquid level gaging devices, and pressure gages shall be
identified by legend or color code as specified in paragraphs (C)(1) and (2) of
rule
901:5-3-04 of the
Administrative Code
.
; and
(2)
Instructions for loading and unloading procedures shall be required at all
installations.
(F)
Protection of container appurtenances
:
(1) Valves and other appurtenances shall be
protected against physical damage. Main container shut-off valves shall be kept
closed and locked when the installation is unattended. If the facility is
protected against tampering by fencing or other suitable means, valve locks are
not required.
;
and
(2) Storage containers
need not be grounded.
(G) Identification
:
(1) A sign shall be
displayed in a conspicuous place stating the name, address, and phone number of
the nearest representative, agent, or owner of the storage system, an emergency
phone number and the phone number of the nearest fire department.
(2) A plant registration number
assigned by the Ohio department of agriculture shall be prominently displayed
with the information required in paragraph (G)(1).
(H) Electrical equipment and wiring
:
(1) Electrical
equipment and wiring for use in ammonia installations shall be general purpose
or weather resistant as appropriate.
; and
(2)
Where concentrations of ammonia in air in excess of sixteen per cent by volume
are likely to be encountered, electrical equipment and wiring shall be a type
specified by and be installed in accordance with "National Electrical Code,"
"NFPA 70 (ANSI-C1)," for "Class I, Group D" locations.