Okla. Admin. Code § 252:641-9-2 - Sizing
Pump tanks shall be sized as follows:
(1)
Lift stations. The lift station pump tank shall have a minimum liquid storage capacity of one thousand (1,000) gallons.
(A)
Daily flow over 500 gallons. For systems with average daily flows over five hundred (500) gallons, the liquid capacity of the pump tank shall be at least twice the highest daily flow.
(B)
Daily flow over 2,000 gallons. For systems with an average daily flow over two thousand (2,000) gallons, the liquid capacity of the pump tank may be reduced to one-half (1/2) of the average daily flow, if a backup pump is available on site.
(2)
Flow equalization tanks. The flow equalization pump tank shall have a minimum liquid storage capacity of one thousand (1,000) gallons. If the daily flow is greater than five hundred (500) gallons, the liquid capacity of the pump tank shall be at least twice the highest daily flow.