Or. Admin. Code § 340-071-0520 - Large Systems
Unless DEQ authorizes otherwise, large systems must comply with the following requirements.
(1) Large
system absorption facilities must be designed with distribution to the cells by
means of pumps or siphons.
(2) The
absorption area must be divided into relatively equal units. Each unit may
receive no more than 1300 gallons of effluent per day.
(3) The replacement (repair) absorption area
must be divided into relatively equal units, with a replacement absorption area
unit located adjacent to an initial absorption area unit.
(4) Effluent distribution must alternate
between the absorption area units.
(5) Each system must have at least two pumps
or siphons.
(6) The applicant must
provide a written assessment of the impact of the proposed system on the
quality of public waters and public health, prepared by a registered geologist,
a certified engineering geologist qualified as a hydrogeologist, or a
subordinate under the direction of either, except as specifically exempted in
ORS 672.535.
(7) The owners of all new and existing large
systems must register those systems with DEQ as Underground Injection Control
(UIC) systems under OAR chapter 340, division 044. Large systems receiving
domestic waste are regulated under this division. Drainfields receiving
nondomestic waste are also regulated under the UIC rules.
Notes
Statutory/Other Authority: ORS 454.625 & 468.020
Statutes/Other Implemented: ORS 454.615 & 468B.080