Or. Admin. Code § 340-150-0470 - Other Methods of Release Detection
(1) An owner and permittee may use a release
detection method for an UST or underground piping not otherwise specified in
OAR 340-150-0410 through
340-150-0465 if:
(a) The device is able to detect a 0.2 gallon
per hour leak rate with a probability of detection of at least 95 percent and a
probability of false alarm of no more than 5 percent for all portions of the
UST or underground piping that routinely contains a regulated
substance;
(b) The method is an
approved leak detection method or equipment as listed by a national
organization (e.g., the National Work Group on Leak Detection).
(2) An owner and permittee must
monitor the UST and underground suction piping for a release at least every 30
days and record the results for each month.
(3) An owner and permittee must monitor
pressurized underground piping for a release daily and record the results daily
for each month.
(4) An owner and
permittee must:
(a) Report to the department
any release detection test results indicating the possibility of a release
(i.e., test failure or alarm) within 24 hours as a suspected release (OAR
340-150-0500) and immediately
begin investigation in accordance with
340-150-0510; and
(b) Immediately investigate all
larger-than-normal or reoccurring variations in monitoring results and, if the
variation cannot be accounted for, report such variations to the department as
a suspected release without waiting to obtain a second confirmation of
data.
(5) An owner and
permittee must retain at a minimum the most current 12 consecutive months of
release detection records.