Or. Admin. Code § 437-002-0122 - Dipping and Coating
(1)
Scope.
(a) This rule applies to all
operations where an object is partially or fully immersed in a liquid, or the
vapors of a liquid. Such operations include, but are not limited to, cleaning,
coating, altering the surface of an object, or changing the character of an
object. Examples of covered operations are paint dipping, electroplating,
pickling, quenching, tanning, degreasing, stripping, cleaning, roll coating,
flow coating, and curtain coating. This rule also applies to draining or drying
an object that has been dipped or coated.
(b) This rule does not apply to tanks that
contain only water or a molten material.
(2) Definitions. Adjacent area: Any area
within 20 feet (6.1 m) of a vapor area that is not separated from the vapor
area by tight partitions. Approved: The equipment is listed or approved by a
nationally recognized testing laboratory. Autoignition temperature: The minimum
temperature required to cause self-sustained combustion, independent of any
other source of heat.Dip tank: A container holding a liquid other than water
and is used for dipping or coating. An object may be immersed (or partially
immersed) in a dip tank or it may be suspended in a vapor coming from the tank.
Flammable liquid: A liquid having a flashpoint at or below 199.4 degrees F (93
degrees C). Flashpoint: The minimum temperature at which a liquid gives off a
vapor in sufficient concentration to ignite if tested in accordance with the
test methods in Appendix B to OAR 437-002-1920.1200 - Physical Hazard Criteria.
Lower flammable limit (LFL): The lowest concentration of a material that will
propagate a flame. The LFL is usually expressed as a percent by volume of the
material in air (or other oxidant). Vapor area: Any space containing a dip
tank, including its drain boards, associated drying or conveying equipment, and
any surrounding area where the vapor concentration exceeds 25% of the LFL of
the liquid in the tank.
(3) Any
container used as a dip tank must be strong enough to withstand any expected
load.
(4) Ventilation.
(a) Ensure airborne concentrations of
materials in any vapor area do not exceed 25% of its LFL.
(b) A tank cover or material that floats on
the surface of the liquid in a dip tank to replace or supplement ventilation is
acceptable, as long as the airborne concentrations do not exceed 25% of the LFL
or any limit established by Division 2, Subdivision Z.
(c) When mechanical ventilation is used, it
must conform to design standards based on national consensus standards that
meet the following:
(A) The standard specifies
the safety requirements for the particular equipment;
(B) The standard is recognized in the United
States as providing specifications that result in an adequate level of
safety;
(C) The standard was
developed by a standards development organization under a method providing for
input and consideration of views of industry groups, experts, users, govern-
mental authorities, and others having broad experience and expertise in issues
related to the design and construction of the particular equipment.
(d) Nonmandatory appendix A of
this section contains examples of consensus standards that meet the
requirements of paragraph (4)(c) of this section.
(e) When mechanical ventilation is used, each
dip tank must have an independent exhaust system unless the combination of
substances being removed will not cause a fire, explosion, or chemical
reaction.
(f) When mechanical
ventilation is used, it must draw the flow of air into a hood or exhaust duct.
(A) Ensure each room with exhaust hoods has
make-up airflow that is at least 90% of the volume of air exhausted.
(B) Ensure that make-up air does not damage
exhaust hoods.
(C) When air is
recirculated, it must meet the requirements of OAR
437-002-0081, "Oregon
Ventilation Regulations."
(g) Inspect hoods and ventilation ductwork
for corrosion or damage at least quarterly and prior to operation after a
prolonged shutdown.
(h) Ensure the
ventilation airflow is adequate at least quarterly and prior to operation after
a prolonged shutdown.
(5) Periodically inspect all dipping and
coating equipment, including covers, drains, overflow piping, and electrical
and fire-extinguishing systems, and promptly correct any
deficiencies.
(6) Thoroughly clean
dip tanks of solvents and vapors before permitting welding, burning, or
open-flame work.
(7) Provide
mechanical ventilation or respirators (selected and used as specified in
1910.134, Respiratory Protection) to protect employees in the vapor area from
exposure to toxic substances released during welding, burning, or open-flame
work.
(8) Medical, first aid, and
hygiene facilities.
(a) All employees working
with or around dip tanks must know the first-aid procedures appropriate to the
dipping and coating hazards to which they are exposed.
(b) When employees work with liquids that may
burn, irritate, or otherwise harm their skin:
(A) Obtain a physician's approval before an
employee with a sore, burn, or other skin lesion that requires medical
attention can return to work in a vapor area.
(B) Only a properly designated person can
provide treatment for any skin abrasion, cut, rash, or open sore.
(C) Keep appropriate first-aid supplies near
dipping or coating operations.
(D)
Provide employees who work with chromic acid periodic examinations, at least
annually, of their exposed body parts, especially their nostrils.
(E) Provide locker space or other storage
space to prevent contamination of employee's street clothes.
(F) Provide at least one basin with hot water
for every 10 employees who work with such liquids.
(G) Follow the emergency eyewash and shower
facilities requirements of OAR
437-002-0161, Medical &
First Aid.
(9) Before cleaning a dip tank:
(a) Drain the tank and open the cleanout
doors; and
(b) Ventilate and clear
any pockets where hazardous vapors may have accumulated.
(10)Use of flammable or combustible liquids.
(a) Use only dip tanks constructed from
non-combustible materials. When drainboards are used, use only drainboards
constructed from non-combustible materials.
(b) Overflow piping.
(A) Provide properly trapped overflow piping
for dip tanks that have a capacity greater than 150 gallons (568 liters) or a
surface area greater than 10 square feet (0.95 square meters).
(B) Overflow piping must discharge to a safe
location.
(C) Overflow piping must
be at least 3 inches (7.6 cm) diameter and must have sufficient capacity to
prevent the tank from overflowing.
(D) The bottom of the overflow connector must
be at least 6 inches (15.2 cm) below the top of the dip tank.
(c) Bottom Drains.
(A) Dip tanks containing more than 500
gallons (1893 L) of liquid must have a bottom drain.
(i) A bottom drain is not required if an
automatic cover that meets the requirements of paragraph (10)(d)(C) is
used.
(ii) A bottom drain is not
required if the viscosity of the liquid at normal atmospheric temperature makes
this impractical.
(B)
Ensure the bottom drain will empty the dip tank in the event of a fire.
(C) Properly trap the bottom
drain.
(D) Ensure the bottom drain
has pipes that will empty the dip tank within 5 minutes.
(E) Bottom drains must discharge to a safe
location.
(F) Bottom drains must be
capable of manual and automatic operation. Manual operation must be from a safe
and accessible location.
(G) When
gravity flow from the bottom drain is impractical, use automatic pumps.
(d) Fire Protection.
(A) Provide portable fire extinguishers that
meet the requirements of OAR
437-002-0187 in every vapor
area.
(B) Provide an automatic fire
extinguishing system:
(i) When the capacity of
the dip tank is at least 150 gallons (568 L) or the liquid surface area is 4
square feet (0.38 square meters) or more; or
(ii) When the capacity of a hardening or
tempering tank is at least 500 gallons (1893 L) or a liquid surface area of 25
square feet (2.37 square meters) or more.
(C) A cover that is closed by an approved
automatic device for the automatic fire-extinguishing system may be used
instead of the fire extinguishing system if the cover:
(i) Can also be activated manually;
(ii) Is noncombustible or tin-clad, with the
enclosing metal applied with locked joints; and
(iii) Is kept closed when the dip tank is not
in use.
(D) In each vapor
area and any adjacent area, ensure that:
(i)
All electrical wiring and equipment conform to OAR 437, Division 2, Subdivision
S (except as specifically permitted in paragraph (15)); and
(ii) There are no flames, spark-producing
devices, or other surfaces that are hot enough to ignite vapors.
(E) Electrically bond and ground
portable containers used to add liquids to dip tanks to prevent static
electrical sparks or arcs.
(F) All
vapor areas must be free of combustible debris and as free as practicable of
combustible stock.
(G) Deposit all
rags or waste impregnated with dipping or coating material in a tightly-closing
metal waste can immediately after use. Use only waste cans that are approved or
acceptable to the local fire authority.
(H) Empty all waste containers at the end of
each shift.
(I) Prohibit smoking in
all vapor areas. Post a readily visible "No Smoking" sign near each dip tank or
designate the entire area as "No Smoking."
(e) If a conveyor system is used with a dip
tank, it must automatically shut down in the event of a fire. If a ventilation
system is used to meet the ventilation requirements of paragraph (4), the
conveyor system must automatically shut down if the ventilation system
fails.
(f) If a liquid is heated in
a dip tank, it must be maintained below the liquid's boiling point, and it must
be maintained at least 1001/4 F (37.81/4 C) below the liquid's autoignition
temperature.
(g) Ensure that a
heating system that is used in a drying operation and could cause ignition:
(A) Is installed in accordance with NFPA
86A-1969, Standard for Ovens and Furnaces (which is incorporated by reference
in 1910.6 of this part); and
(B)
Has adequate mechanical ventilation that operates before and during the drying
operation; and
(C) Shuts down
automatically if any ventilating fan fails to maintain adequate
ventilation.
(11) Hardening or Tempering Tanks.
(a) Ensure that hardening or tempering tanks:
(A) Are located as far as practicable from
furnaces;
(B) Are on noncombustible
flooring;
(C) Have noncombustible
hoods and vents (or equivalent devices) for venting to the outside. For this
purpose, treat vent ducts as flues and keep them away from combustible
materials, particularly roofs.
(b) Equip each tank with an alarm that will
sound if the temperature of the liquid comes within 501/4 F (101/4 C) of its
flashpoint (the alarm set point).
(c) When practicable, provide each tank with
a limit switch to shut down the conveyor supplying work to the tank.
(d) If the temperature of the liquid can
exceed the alarm set point, equip the tank with a circulating cooling
system.
(e) If the tank has a
bottom drain, the bottom drain may be combined with the oil-circulating
system.
(f) Do not use air under
pressure when filling the dip tank or agitating the liquid in the dip
tank.
(12) Flow Coating.
(a) Use a direct low-pressure pumping system
or a 10-gallon (38 L) or smaller gravity tank to supply the paint for flow
coating. In case of fire, an approved heat-actuated device must shut down the
pumping system.
(b) Ensure that the
piping is substantial and rigidly supported.
(13) When roll coating, roll spreading, or
roll impregnating operations use a flammable or combustible liquid that has a
flashpoint below 1401/4 F (601/4 C), prevent sparking of static electricity by:
(a) Bonding and grounding all metallic parts
(including rotating parts) and installing static collectors; or
(b) Maintaining a conductive atmosphere (for
example, one with a high relative humidity) in the vapor
area.
(14) Vapor
degreasing tanks.
(a) Ensure that the
condenser or vapor-level thermostat keeps the vapor level at least 36 inches
(91 cm) or one-half the tank width, whichever is less, below the top of the
vapor degreasing tank.
(b) When
using gas as a fuel to heat the tank liquid, the combustion chamber must be
airtight (except for the flue opening) to prevent solvent vapors from entering
the air-fuel mixture.
(c) The flue
must be made of corrosion-resistant material, and it must extend to the
outside. Install a draft diverter if mechanical exhaust is used on the
flue.
(d) Do not allow the
temperature of the heating element to cause a solvent or mixture to decompose
or to generate an excessive amount of vapor.
(15) Ensure that cyanide tanks have a dike or
other safeguard to prevent cyanide from mixing with an acid if a dip tank
fails.
(16) If a liquid is sprayed
in the air over an open-surface cleaning or degreasing tank, control the
spraying to the extent feasible by:
(a)
Enclosing the spraying operation; and
(b) Using mechanical ventilation to provide
enough inward air velocity to prevent the spray from leaving the vapor
area.
(17) Electrostatic
paint detearing.
(a) Use only approved
electrostatic equipment in paint-detearing operations. Electrodes in such
equipment must be substantial, rigidly supported, permanently located, and
effectively insulated from ground by nonporous, noncombustible, clean, dry
insulators.
(b) Use conveyors to
support any goods being paint deteared.
(c) Do not manually handle goods being
electrostatically deteared.
(d)
Maintain a minimum distance of twice the sparking distance between goods being
electro- statically deteared and the electrodes or conductors of the
electrostatic equipment. This minimum distance must be displayed conspicuously
on a sign located near the equipment.
(e) Ensure that the electrostatic equipment
has automatic controls that immediately disconnect the power supply to the
high-voltage transformer and signal the operator if:
(A) Ventilation or the conveyors fail to
operate;
(B) A ground (or imminent
ground) occurs anywhere in the high-voltage system; or
(C) Goods being electrostatically deteared
come within twice the sparking distance of the electrodes or conductors of the
equipment.
(f) Use
fences, rails, or guards, made of conducting material and adequately grounded,
to separate paint-detearing operations from storage areas and from
personnel.
(g) To protect
paint-detearing operations from fire, use automatic sprinklers or an automatic
fire-extinguishing system conforming to the requirements of OAR 437, Division
2, Subdivision F.
(h) To collect
paint deposits, provide drip plates and screens and clean these plates and
screens in a safe location.
Notes
Stat. Authority: ORS 654.025(2), 656.726(4).
Stats. Implemented: ORS 654.001 - 654.295.