Or. Admin. Code § 437-002-2312 - Deenergizing Lines and Equipment for Employee Protection
(1) Application. This rule applies to the
deenergizing of transmission and distribution lines and equipment for the
purpose of protecting employees. See
437-002-2303 Hazardous Energy
Control, Division 2/RR, for requirements on the control of hazardous energy
sources used in the generation of electric energy. Conductors and parts of
electric equipment that have been deenergized under procedures other than those
required by 437-002-2303, as applicable,
must be treated as energized.
(2)
General.
(a) If a system operator is in
charge of the lines or equipment and their means of disconnection, the employer
must designate one employee in the crew to be in charge of the clearance and
must comply with all of the requirements of paragraph (3) of this rule in the
order specified.
(b) If no system
operator is in charge of the lines or equipment and their means of
disconnection, the employer must designate one employee in the crew to be in
charge of the clearance and to perform the functions that the system operator
would otherwise perform under this rule. All of the requirements of paragraph
(3) of this rule apply, in the order specified, except as provided in paragraph
(2)(b) of this rule.
(c) If only
one crew will be working on the lines or equipment and if the means of
disconnection is accessible and visible to, and under the sole control of, the
employee in charge of the clearance, paragraphs (3)(b), (3)(d), and (3)(f) of
this rule do not apply. Additionally, the employer does not need to use the
tags required by the remaining provisions of paragraph (3) of this rule.
(d) If two or more crews will be
working on the same lines or equipment, then:
(A) The crews must coordinate their
activities under this rule with a single employee in charge of the clearance
for all of the crews and follow the requirements of this rule as if all of the
employees formed a single crew, or
(B) Each crew must independently comply with
this rule and, if there is no system operator in charge of the lines or
equipment, must have separate tags and coordinate deenergizing and reenergizing
the lines and equipment with the other crews.
(e) The employer must render any
disconnecting means that are accessible to individuals outside the employer's
control (for example, the general public) inoperable while the disconnecting
means are open for the purpose of protecting employees.
(3) Deenergizing lines and equipment
(a) The employee that the employer designates
pursuant to paragraph (2) of this rule as being in charge of the clearance must
make a request of the system operator to deenergize the particular section of
line or equipment. The designated employee becomes the employee in charge (as
this term is used in paragraph (3) of this rule) and is responsible for the
clearance.
(b) The circuit or
equipment must be considered as energized until notification from the system
operator to the contrary is received.
(c) The system operator must obtain the name
of the person requesting clearance and be assured that the person is qualified
to receive such clearance.
(d) The
person requesting the clearance must state exactly what circuit or equipment
they want de-energized and the reason.
(e) The system operator must repeat the
request for clearance and be certain that the request is fully understood.
(f) The employer must ensure that
all switches, disconnectors, jumpers, taps, and other means through which known
sources of electric energy may be supplied to the particular lines and
equipment to be deenergized are open. The employer must render such means
inoperable, unless its design does not so permit, and then ensure that such
means are tagged to indicate that employees are at work.
(g) The employer must ensure that
automatically and remotely controlled switches that could cause the opened
disconnecting means to close are also tagged at the points of control. The
employer must render the automatic or remote control feature inoperable, unless
its design does not so permit.
(h)
The employer need not use the tags mentioned in paragraphs (3)(f) and (3)(g) of
this rule on a network protector for work on the primary feeder for the network
protector's associated network transformer when the employer can demonstrate
all of the following conditions:
(A) Every
network protector is maintained so that it will immediately trip open if closed
when a primary conductor is deenergized;
(B) Employees cannot manually place any
network protector in a closed position without the use of tools, and any manual
override position is blocked, locked, or otherwise disabled; and
(C) The employer has procedures for manually
overriding any network protector that incorporate provisions for determining,
before anyone places a network protector in a closed position, that: The line
connected to the network protector is not deenergized for the protection of any
employee working on the line; and (if the line connected to the network
protector is not deenergized for the protection of any employee working on the
line) the primary conductors for the network protector are energized.
(i) Tags must prohibit
operation of the disconnecting means and must indicate that employees are at
work.
(j) After the applicable
requirements in paragraphs (3)(a) through (3)(i) of this section have been
followed and the system operator gives a clearance to the employee in charge,
the employer must ensure that the lines and equipment are deenergized by
testing the lines and equipment to be worked with a device designed to detect
voltage.
(k) The employer must
ensure the installation of protective grounds as required by
437-002-2313 Grounding for the
protection of employees, Division 2/RR.
(l) After the applicable requirements of
paragraphs (3)(a) through (3)(k) of this rule have been followed, the lines and
equipment involved may be considered deenergized.
(m) To transfer the clearance, the employee
in charge (or the employee's supervisor if the employee in charge must leave
the worksite due to illness or other emergency) must inform the system operator
and employees in the crew; and the new employee in charge must be responsible
for the clearance.
(n) To release
a clearance, the employee in charge must:
(A)
Notify each employee under that clearance of the pending release of the
clearance;
(B) Ensure that all
employees under that clearance are clear of the lines and equipment;
(C) Ensure that all protective grounds
protecting employees under that clearance have been removed; and
(D) Report this information to the system
operator and then release the clearance.
(o) Only the employee in charge who requested
the clearance may release the clearance, unless the employer transfers
responsibility under paragraph (3)(m) of this rule.
(p) No one may remove tags without the
release of the associated clearance as specified under paragraphs (3)(n) and
(3)(o) of this rule.
(q) The
employer must ensure that no one initiates action to reenergize the lines or
equipment at a point of disconnection until all protective grounds have been
removed, all crews working on the lines or equipment release their clearances,
all employees are clear of the lines and equipment, and all protective tags are
removed from that point of disconnection.