Or. Admin. Code § 437-004-2900 - Grounding and Bonding
(1) The
path from circuits, equipment, structures, and conduit enclosures to ground
must be permanent and continuous with enough capacity to conduct safely the
currents that might be imposed on it. The path must also have impedance low
enough to limit the potential above ground and to result in the operation of
the over current devices in the circuit.
(2) Driven rod electrodes must, where
practicable, have a resistance to ground not to exceed 25 ohms. Where the
resistance is not as low as 25 ohms, use two or more electrodes connected in
parallel.
(3) Check grounding
circuits to ensure that the circuit between the ground and the grounded power
conductor has a resistance low enough to permit enough current to flow to cause
the fuse or breaker to interrupt the circuit.
(4) Conductors used for bonding and grounding
stationary and moveable equipment must be able to carry the anticipated
current.
(5) Outside conductors,
600 volts, nominal or less. Paragraphs (a), (b), (c), and (d) below apply to
branch circuit, feeder, and service conductors rated 600 volts, nominal, or
less and run outdoors as open conductors. Paragraph (e) below applies to lamps
installed under these conductors.
(a)
Conductors on poles must provide a horizontal climbing space not less than the
following:
(A) Power conductors below
communication conductors - 30 inches.
(B) Power conductors alone or above
communication conductors: 300 volts or less - 24 inches; more than 300 volts -
30 inches.
(b) Clearance
from ground to open conductors must conform to the following minimum
clearances:
(A) 10 feet above finished grade,
sidewalks, or from any platform or projection from which they might be
reached.
(B) 12 feet over areas
subject to vehicle traffic other than truck traffic.
(C) 15 feet over areas other than those in
paragraph (5)(b)(D) below, where there may be truck traffic.
(D) 18 feet over public streets, alleys,
roads, and driveways.
(c) Conductors must have a clearance of at
least 3 feet from windows, doors, porches, fire escapes, or similar locations.
Conductors run above the top level of a window do not have to be 3 feet
away.
(d) Conductors must have a
clearance of not less than 8 feet from the highest point of roofs over which
they pass, except that:
(A) Where the voltage
between conductors is 300 volts or less and the roof has a slope of not less
than 4 inches in 12, the clearance from roofs must be at least 3 feet;
or
(B) Where the voltage between
conductors is 300 volts or less and the conductors do not pass over more than 4
feet of the overhang portion of the roof and they terminate at a
through-the-roof raceway or approved support, the clearance from roofs must be
at least 18 inches.
(e)
Lamps for outdoor lighting must be below all live conductors, transformers, or
other electric equipment, unless the equipment has a disconnecting means that
is lockable in the open position or unless there are adequate clearances or
other safeguards for lamp replacement.
Notes
Stat. Auth.: ORS 654.025(2) & ORS 656.726(3)
Stats. Implemented: ORS 654.001 - ORS 654.295