Or. Admin. Code § 437-004-2950 - Switches and Circuit Breakers
(1) There must be at least 3 feet of clear
space in front of switch centers or panels. Passageways to switch centers or
panels must be unobstructed.
(2)
There must be enclosures or screens around live parts of electrical
switchboards and panelboards.
(3)
Each disconnecting means for motors and appliances, and each service feeder or
branch circuit at the point where it originates, must have legible markings to
indicate their purpose unless the purpose is evident.
(4) Locate or shield disconnecting means to
avoid injury to employees. Do not use open knife switches.
(5) Securely mount boxes for disconnecting
means and keep their covers in place.
(6) Boxes and disconnecting means in damp or
wet locations must be waterproof.
(7) There must be sufficient light for all
indoor working spaces around service equipment, switchboards, panelboards, and
motor control centers.
(8) The
minimum headroom of working spaces around service equipment, switchboards,
panelboards, or motor control centers must be 6 feet 3 inches.
Notes
Stat. Auth.: ORS 654.025(2) & ORS 656.726(3)
Stats. Implemented: ORS 654.001 - ORS 654.295