Or. Admin. Code § 437-004-3000 - Identification and Load Ratings

(1) Name plates, rating data, and marks of identification on electrical equipment and electrically operated machines must be present and legible.
(2) Do not change the circuit protection in existing installations to increase the load to more than the load rating of the circuit wiring.
(3) Do not allow tampering, bridging, or using oversize fuses. Require workers to report immediately to management or a qualified electrician, any fuses or breakers that blow repeatedly.
(4) Do not attempt to restart electric motors that kick out repeatedly.