Or. Admin. Code § 437-004-3050 - Work Near Overhead Lines
Clearance or Safeguards Required
Note: High voltage is 750 v or higher.
(1) Isolate exposed overhead conductors from
contact by persons or equipment.
(2) Do not store irrigation pipe within 100
feet of overhead high voltage conductors.
(3) Do not allow upending if irrigation pipe
is within 100 feet of overhead conductors.
(4) Do not set up or operate any part of a
water or irrigation system, or any other device that discharges a conductive
liquid, so that the discharge is toward or may come within 10 feet of overhead
high-voltage lines or any other exposed electric conductor.
(5) Do not require or permit an employee to
pass or work near high-voltage lines, unless you effectively guard against
danger from contact.
(6) No work
activity may bring workers or equipment within 10 feet of high-voltage
lines.
(7) Do not operate equipment
or machines near power lines except:
(a) When
electrical distribution and transmission lines are deenergized and visibly
grounded at the point of work or where insulating barriers are in place to
prevent physical contact with the lines;
(b) For lines rated 50 kV. or below, minimum
clearance between the lines and any part of the object must be 10
feet;
(c) For lines rated more than
50 kV. minimum clearance between the lines and any part of the object must be
10 feet plus 0.4 inches for each 1 kV., more than 50 kV., or twice the length
of the line insulator but never less than 10 feet.
(d) In transit, the clearance must be a
minimum of 4 feet for voltages less than 50 kV., 10 feet for voltages more than
50 kV. up to and including 345 kV., and 16 feet for voltages up to and
including 750 kV.
(e) A person must
observe clearances and give timely warning for all work where it is difficult
for the operator to maintain the desired clearance by sight.
(8)
Warning Sign
Required: The employer must post and keep in plain view of the operator
on each derrick, power shovel, drilling rig, hay loader, hay stacker or similar
apparatus, any part of which is capable of vertical, lateral or swinging
motion, a warning sign legible at 12 feet reading "Unlawful to operate this
equipment within 10 feet of high-voltage lines."
(9)
Notification to Power Company and
Responsibility for Safeguards: When any work may be within 10 feet of
any high-voltage line, the person or persons responsible for the work must
promptly notify the power company and is responsible for the completion of
required safety measures before beginning the work.
Notes
Stat. Auth.: ORS 654.025(2) & ORS 656.726(3)
Stats. Implemented: ORS 654.001 - ORS 654.295