Or. Admin. Code § 437-007-0410 - Fire Extinguishers
(1)
Portable fire extinguisher use, training and maintenance must be in accordance
with OAR chapter 437, division 2, subdivision L, Fire Protection.
(2) Fire extinguishers or protection systems
must be of a type approved by a nationally recognized testing laboratory (NRTL)
(see OAR 437, division 2/A, § 1910.7, for definition of NRTL).
(3) There must be an approved fire
extinguisher with a minimum rating of 1A:10BC (or equivalent) on each vehicle
and machine, or the area where the vehicles and machines are
operated.
(4) After July 1, 2007,
fire extinguishers provided on each vehicle and machine must be 2A:10BC or
provide equivalent protection.
(5)
Fire extinguishers must be fully charged and maintained in operable
condition.
(6) Portable
extinguishers must be visually inspected monthly.
(7) Portable extinguishers must have an
annual maintenance check.
NOTE: Stored pressure extinguishers do not require an internal examination.
(8) The annual maintenance check date must be
recorded and this record must be retained for one year.
(9) Each motor vehicle used for transporting
explosive materials must be equipped with fire extinguishers as follows:
(a) Vehicle less than 14,000 pounds must have
at least two extinguishers having a combined capacity of 4A:20BC.
(b) Vehicle 14,000 pounds or greater and
tractor/semi-trailer units must have at least two extinguishers having a
combined capacity of 4A:70BC.
Notes
Stat. Auth.: ORS 654.025(2) & ORS 656.726(4)
Stats. Implemented: ORS 654.001 - ORS 654.295
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.