Or. Admin. Code § 860-023-0015 - Testing Gas and Electric Meters
(1) All meters shall be tested before
installation, or within 30 days thereafter. No meter will be placed in service
or be allowed to remain in service which has an error in registration in excess
of two percent under conditions of normal operation. These requirements may be
waived by written agreement if the energy utility provides an approved random
sampling technique for testing new meters.
(2) New meters, repaired meters, and meters
that have been removed from service shall be correct to within two percent fast
or slow before being installed or reinstalled.
(3) Each energy utility shall adopt schedules
for periodic tests and repairs of meters. The length of time meters shall be
allowed to remain in service before receiving periodic tests and repairs is to
be determined from periodic analysis of the accuracy of meters tested. The
schedules adopted shall be subject to the Commission's approval.
(4) Whenever any meter is tested, the energy
utility shall prepare a test record, including the information needed for
identifying the meter, the reason for making the test, the reading of the
meter, the result of the test, and all data taken at the time of the test in
sufficiently complete form to permit the convenient checking of methods
employed. The energy utility shall retain the current and immediately prior
test records for all meters tested.
(5) Each energy utility shall, unless
specifically excluded by the Commission, provide such laboratory meter-testing
equipment and other equipment and facilities as needed to make the tests
required of it by these rules or other orders of the Commission. The apparatus
and equipment so provided shall be subject to the Commission's
approval.