25 Pa. Code § 109.1304 - Assessment source water monitoring
(a) To enable the Department to determine if
a groundwater system is using a groundwater source with fecal contamination,
the Department may require a groundwater system to conduct monitoring for
E. coli. If directed by the Department to conduct monitoring
under this section, a water supplier shall:
(1) Collect a total of 12 samples from each
groundwater source.
(i) The system may obtain
written approval from the Department to conduct monitoring at one or more
sources within the groundwater system that are representative of multiple
sources used by the system. The Department will consider any factors that
identify sources as representative of multiple sources drawing water from the
same hydrogeologic setting.
(ii)
For sources providing water to the public 12 months out of the year,
groundwater systems shall collect one sample during each month.
(iii) For sources providing water to the
public for less than 12 months out of the year, groundwater systems shall
collect 12 samples evenly distributed over the operational period.
(iv) Samples collected under §
109.1303(a)
(relating to triggered monitoring requirement for groundwater sources) may be
used to satisfy the requirements of this subsection, if approved by the
Department.
(v) If a groundwater
system obtains an E. coli-positive groundwater source sample,
the groundwater system shall perform a corrective action as described under
§
109.1302(c)
(relating to treatment technique requirements).
(vi) The groundwater system may discontinue
assessment source water monitoring if the system demonstrates they provide at
least 4-log treatment of viruses under §
109.1302(b)(1) or
if directed by the Department.
(2) Collect groundwater source samples at a
location prior to any treatment of the groundwater source.
(b) The following apply to an invalidation of
an E. coli sample for groundwater source sampling:
(1) A groundwater system may obtain a
Department invalidation of an E. coli-positive groundwater
source sample collected under this section as follows:
(i) The system provides the Department with
written notice from the laboratory that improper sample analysis
occurred.
(ii) The Department
determines and documents in writing that there is substantial evidence that the
E. coli- positive groundwater source sample is not related to
source water quality.
(2)
If the Department invalidates an E. coli-positive groundwater
source sample, the groundwater system shall collect a replacement source water
sample under subsection (a) within 24 hours of being notified by the Department
of its invalidation decision and have the replacement sample analyzed for
E. coli. The Department may extend the 24-hour time limit on a
case-by-case basis to 72 hours.