25 Pa. Code § 109.708 - System service and auxiliary power
(a)
System service. No later than the dates specified in
paragraphs (1)-(3), a community water supplier shall submit a certification on
a certification form provided by the Department verifying completion of the
uninterrupted system service plan (USSP) which was completed using the USSP
form provided by the Department to ensure operation of the sources, treatment
and pumping facilities necessary to ensure that safe and potable water is
continuously supplied to users in accordance with subsection (b) or (c), or
both. A continuous supply of safe and potable water is one that meets all
applicable MCLs, MRDLs and treatment techniques specified in §
109.202 (relating to State MCLs,
MRDLs and treatment technique requirements) and is sufficient to maintain
system pressure specified in §
109.607 (relating to pressures)
throughout the distribution system.
(1) By
August 19, 2019, for systems serving 3,300 or fewer persons.
(2) By August 17, 2020, for systems serving
3,301-10,000 persons.
(3) By August
17, 2021, for systems serving greater than 10,000 persons.
(b)
Auxiliary power and alternate
provisions. System service must be provided through one or more of
the following methods:
(1) Connection to at
least two independent power feeds from separate substations.
(i) The power feeds may not be located in the
same conduit or supported from the same utility pole.
(ii) If overhead power feeds are used, the
power feeds may not cross or be located in an area where a single plausible
occurrence (for example, a fallen tree) could disrupt both power
feeds.
(2) Onsite
auxiliary power sources (that is, generators or engines).
(3) A combination of alternate provisions,
such as finished water storage capacity, interconnections with another public
water system, portable generators and other system specific alternate
provisions to meet the requirements of subsection (a).
(c)
Corrective action
schedule. If the USSP and certification form completed in subsection
(a) identify that deficiencies exist which prevent a continuous supply of safe
and potable water as specified in subsection (a), and these deficiencies are
not corrected by the dates specified in subsection (a)(1)-(3), a community
water supplier shall submit to the Department, within 6 months after the dates
specified in subsection (a)(1)-(3), a schedule which includes detailed
corrective actions to address these deficiencies, including corresponding
completion dates. The schedule for completion of each corrective action must be
commensurate with the complexity of the associated corrective action.
(d)
Planned service
interruptions. The public water supplier shall give reasonable notice
to the affected customers prior to a planned service interruption affecting
quantity or quality of the water delivered to the customer. If the interruption
is scheduled to exceed 8 hours and affect 15 or more service connections the
water supplier shall also notify the Department.
Notes
The provisions of this § 109.708 amended under section 4(a) of the Pennsylvania Safe Drinking Water Act (35 P.S. § 721.4(a)); and section 1920-A(b) of The Administrative Code of 1929 (71 P.S. § 510-20(b)).
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.