(a) The owner or operator of a petroleum
refinery shall do the following:
(1) Develop
and conduct a monitoring program consistent with the provisions of subsection
(d).
(2) Record leaking refinery
components which have a VOC concentration exceeding 10,000 ppm when tested in
accordance with the provisions of §
139.14 (relating to emissions of
VOCs) and place an identifying tag on each refinery component consistent with
the provisions in subsection (d)(3).
(3) Repair and retest the leaking refinery
components as soon as possible. Every reasonable effort shall be made to repair
each leak within 15 days unless a refinery unit shutdown is required to make
the necessary repair.
(4) Identify
leaking refinery components which cannot be repaired until the unit is shutdown
for turnaround.
(b)
Except for safety pressure relief valves and fittings on valves 1 inch or
smaller, no owner or operator of a petroleum refinery shall install or operate
a valve at the end of a pipe or line containing VOCs unless the pipe or line is
sealed with a second valve, a blind flange, a plug or a cap. The sealing device
may be removed only when a sample is being taken or during maintenance
operations.
(c) Pipeline valves and
pressure relief valves in gaseous VOC service shall be marked in some manner
that will be readily obvious to both refinery personnel performing monitoring
and the Department.
(d) Monitoring
shall be done as follows:
(1) The owner or
operator of a petroleum refinery shall conduct a monitoring program consistent
with the following requirements:
(i) Check
yearly, by methods referenced in §
139.14, pump seals and pipeline
valves in liquid service.
(ii)
Check quarterly, by methods referenced in §
139.14, compressor seals, pipeline
valves in gaseous service, and pressure relief valves in gaseous
service.
(iii) Check monthly, by
visual methods, pump seals.
(iv)
Check within 24 hours, by methods referenced in §
139.14, a pump seal from which VOC
liquids are observed to be dripping.
(v) Check, by methods referenced in §
139.14, a relief valve within 24
hours after it has vented to the atmosphere.
(vi) Check within 72 hours after repair, by
methods referenced in §
139.14, a refinery component that
was found leaking.
(2)
Pressure relief devices which are connected to an operating flare header, vapor
recovery devices, inaccessible valves, storage tank valves and valves that are
not externally regulated are exempt from the monitoring requirements in
paragraph (1).
(3) The owner or
operator of a petroleum refinery, upon the detection of a leaking refinery
component, shall affix a weatherproof and readily visible tag, bearing an
identification number and the date upon which the leak is located to the
leaking refinery component. This tag shall remain in place until the leaking
refinery component is repaired.
(e) Record keeping shall comply with the
following:
(1) The owner or operator of a
petroleum refinery shall maintain a leaking refinery components' monitoring log
which shall contain, at a minimum, the following data:
(i) The name of the process unit where the
refinery component is located.
(ii)
The type of refinery component-for example, valve, seal.
(iii) The tag number of refinery
component.
(iv) The dates on which
the leaking refinery component was discovered and repaired.
(v) The date and instrument reading of the
recheck procedure after a leaking refinery component was repaired.
(vi) A record of the calibration of the
monitoring instrument.
(vii) Those
leaks that cannot be repaired until turnaround.
(viii) The total number of refinery
components checked and the total number of refinery components found
leaking.
(2) Copies of
the monitoring log shall be retained by the owner for 2 years after the date on
which the record was made or the report was prepared.
(3) Copies of the monitoring log shall
immediately be made available to the Department, upon verbal or written
request, at any reasonable time.
(f) Reporting shall comply with the
following:
(1) The owner or operator of a
petroleum refinery, upon completion of each yearly and quarterly monitoring
procedure, shall do the following:
(i) Submit
a report to the Department by the last business day of January, April, July and
October that lists leaking refinery components that were located during the
previous calendar quarter but not repaired within 15 days, leaking refinery
components awaiting unit turnaround, the total number of refinery components
inspected and the total number of refinery components found leaking.
(ii) Submit a signed statement with the
report attesting to the fact that, with the exception of those leaking refinery
components listed in subparagraph (i), monitoring and repairs were performed as
stipulated in the monitoring program.
(g) The owner or operator of a petroleum
refinery may submit an alternative plan for the control of leaks from petroleum
refinery equipment to the Department. If the Department finds that the
alternative plan will achieve an emission reduction which is equivalent to or
greater than the reduction which can be achieved under the provisions of this
section and that the alternative plan is as enforceable as this section, then
the Department will allow the implementation of this alternative
plan.
(h) The owner or operator of a
petroleum refinery may submit to the Department a list of refinery components
the inspection of which would involve a significant element of danger. The
Department may exempt the refinery components on this list from the
requirements of this section if the owner or operator can demonstrate to the
satisfaction of the Department that a significant element of danger exists
which cannot be reasonably eliminated and that these exemptions will not result
in a significant reduction in the effectiveness in the control of VOC
emissions.
Notes
The
provisions of this § 129.58 adopted April 27, 1979, effective
8/1/1979, 9 Pa.B. 1447; corrected
May 11, 1979, effective 8/1/1979,
9 Pa.B. 1534; amended August 12, 1983, effective 8/13/1983, 13 Pa.B.
2478.
The provisions of this § 129.58 issued under the
Air Pollution Control Act (35 P.S. §§
4001-4015).
This section cited in 25 Pa. Code §
121.1 (relating to definitions);
25 Pa. Code §
129.51 (relating to general); 25
Pa. Code §
129.54 (relating to seasonal
operation of auxiliary incineration equipment); 25 Pa. Code §
129.91 (relating to control of
major sources of NOx and VOCs); 25 Pa. Code §
129.96 (relating to
applicability); and 25 Pa. Code §
129.111 (relating to
applicability).