34 Pa. Code § 35.75 - Sprinklers
(a)
Quantity required. Booths 3 feet or more in width (measured
along the floor or bottom of face), or having a face area of more than 16
square feet, shall be equipped with one or more approved automatic sprinklers.
At least one automatic sprinkler shall be installed in booths between 3 feet
and 8 feet in width, and one automatic sprinkler for each additional width of 8
feet or fraction thereof.
(b)
Location in booths. Sprinklers shall be so located at the top
of the booth that they do not readily become coated with paint or other
materials, and in such position that they afford protection to some of the area
outside and immediately adjacent to the face of the booth. No sprinklers shall
be located less than 4 inches from the edge or the top of any booth. Each room
booth shall be equipped with one approved automatic sprinkler for each 160
square foot unit of floor area or fraction thereof.
(c)
Maintenance. The
accumulated deposits of sprayed materials shall be cleaned from the sprinkler
heads at frequent intervals with sufficient care to avoid injury to the
sprinkler head.