34 Pa. Code § 39.103 - Protective grounding
(a)
Grounding method. Lightning arresters, grounding, and all
grounding of circuits, equipment or wire runways, intended to be a permanent
and effective protective measure, shall be made in accordance with methods
specified in §§
39.61-39.70 (relating to methods of
protective grounding).
(b)
Grounding noncurrent-carrying metal parts. Electrical supply
equipment, if operating at over 150 volts to ground, or if in hazardous
locations, shall have their exposed noncurrent carrying metal parts, such as
frames of generators, motors, and switchboards, and cases of transformers and
oil switches, permanently grounded. References should also be made to
§§
39.115 and
39.159 (relating to grounding
noncurrent-carrying parts; grounding noncurrent-carrying metal parts). When
regulating voltage, generators or converters supplying circuits not exceeding
140 volts to ground are operated at not more than 180 volts, such generators or
converters are considered not to exceed 150 volts to ground. Hazardous
locations include those where dampness, acid fumes, explosives, inflammable
gas, or flyings normally exist.
(c)
Exemptions. Exposed noncurrent-carrying metal parts of
electrical supply equipment operating on grounded direct current circuits or on
series direct-current circuits may be left ungrounded if no inflammable gas is
present, and if suitable insulating floors, platforms, or mats are used, so
that no person may inadvertently come in contact with such ungrounded parts
while he is standing upon any grounded surface, including floors not of
insulating material; and further if suitable permanent insulating barrier
guards are used so that a person may not, while touching the ungrounded parts
at the same time inadvertently touch other machine frames or metallic fixtures
not bonded to the parts in question. This provision shall not apply to the
motor frame of a direct connected, motor driven, high tension, series generator
sets in existing installations, when the generators have their frames insulated
from ground, for operating reasons, and the motor frames are grounded, if it is
impracticable to provide insulating barrier guards in the space available.
Reference should also be made to §
39.115 (relating to
noncurrent-carrying parts).
(d) If
exposed noncurrent-carrying metal parts are not grounded they shall be suitably
insulated from the ground and from neighboring grounded surfaces.