34 Pa. Code § 39.131 - Current transformers secondary circuits
(a) Secondary circuits of current
transformers including constant current and instrument transformers, except
those supplying relays only, or those having their primary circuits always
disconnected before the secondary circuits are worked on, shall be provided
with means of short circuiting them which may be readily connected while the
primary is energized and which are so arranged as to permit the removal of any
instrument or other device from such circuits without opening the
circuits.
(b) If primaries are
above 7,500 volts, secondary circuits, unless otherwise adequately protected
from injury or contact of persons, shall be permanently grounded
conduit.