34 Pa. Code § 39.177 - Guarding live parts
(a)
Enclosure. Switchboards operating at over 300 volts to ground
and located near passageways shall be guarded from these by suitable inclosures
or barriers and shall be made inaccessible to other than authorized persons,
unless under constant attendance during operation.
(b)
Mats. For the protection
of the operator, if parts over 300 volts to ground are not otherwise guarded or
isolated by elevation, suitable insulating floors, mats, or platforms providing
good footing shall be so placed that the operator does not readily touch the
live parts, unless standing on such floors, mats, or platforms.
(c)
Parts over 750 volts on face of
board. No switchboard shall have exposed on its face within six feet
from floor line any current-carrying part over 750 volts, except as noted in
subsection (e) and except direct current railway boards up to 1,500 volts,
which, if above nominal 750 volts, shall be so constructed that the operator
does not inadvertently come in contact with parts having a hazardous difference
of potential. Dead face panels and remote control should be utilized to achieve
this result if isolation by elevation is impracticable or
undesirable.
(d)
Exposed
live parts on face or back. When working space adjacent to live parts
are not provided in accordance with §
39.104 (relating to working space
about electrical equipment), suitable guards shall be arranged to protect the
operator from accidental contact with parts over 750 volts. Suitable insulating
guardrails, sufficiently spaced from the face or back of the board, or suitable
guards perpendicular to the face or the back of the board, and extending out
beyond the live parts should be used, if practicable.
(e)
Plug-type switchboard.
Plug-type switchboards shall, except while connections are being changed, have
no current-carrying part exposed on face of boards and, if practicable, they
and their plug connectors shall be so arranged where the operating voltage
exceeds 150 as to have current-carrying parts guarded so long as they are
alive, even while connections are being changed.
(f)
Instruments. Metal cases
of instruments, unless isolated by elevation, operating at over 750 volts
should be grounded or enclosed in suitable covers of insulating material or of
grounded metal.
(g)
Exposed
parts over 7,500 volts. No switchboard shall have current-carrying
parts above 7,500 volts exposed unguarded unless these parts are effectively
isolated by elevation, except at times when occasionally left exposed by
removal of covers or entrance into enclosures, such as switch and instrument
transformer cells or compartments, which are ordinarily unoccupied by persons.
For such parts, if exposed while alive for any purpose, including busses and
disconnectors in compartments, working space shall be provided complying with
the requirements under §
39.160(d)
(relating to guarding live parts of switches and automatic cut-outs not
installed on switchboards).
Notes
This section cited in 34 Pa. Code § 39.171 (relating to accessibility and convenient attendance).