34 Pa. Code § 39.246 - Guarding current-carrying parts
(a) Switchboards and panelboards having
exposed current-carrying parts operating at over 150 volts to ground and not
isolated by elevation at least eight feet above the floor shall when
practicable be suitably enclosed in locked cabinets, screens, or rooms, or
other enclosures to make them inaccessible to others than the authorized
operator. Conducting floors about such boards shall be provided with a suitable
insulating platform or mat so placed that no person may inadvertently touch
live parts unless standing on the insulating platform or mat. Reference should
also be made to §§
39.199 and
39.238(a)
(relating to guarding or isolating live parts; guarding live parts of switches
and automatic cut-outs). If the circuit voltage exceeds 300 to ground this
arrangement shall always be made.
(b) If switchboards or panelboards at voltage
below 150 to ground are accessible to other than properly qualified operators,
they should, if practicable, be enclosed in cabinets or screens as an effective
precaution against accidental short circuits at times when no operation of the
board necessitates the opening of the cabinet or screen. Reference should also
be made to §
39.244 (relating to spacing and
barriers against short circuit).
(c) Plug-type switchboards on
constant-current systems, or if above 150 volts to ground, shall have no
current-carrying parts exposed on face of boards, and plug connectors shall
have current-carrying parts guarded as long as they are alive.
(d) Switchboards having no current-carrying
parts exposed to at the face, that is, the working space, should be used in
theaters and similar places where rapid handling is necessary, and the
attention shall be given to signals or to other processes.
(e) Theater switchboards at any voltage, if
having current-carrying parts exposed at the face, should, if practicable, be
elevated, or guarded by suitable railings, to prevent contact with live parts
by passersby.
Notes
This section cited in 34 Pa. Code § 39.241 (relating to accessibility and convenient attendance).
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.