34 Pa. Code § 39.254 - Guards for live parts
(a) Motors
operating at over 150 volts to ground, unless isolated by elevation at least 8
feet above the floor line, should, if practicable, be provided with permanent
inclosures or other suitable guards so arranged as to prevent persons or
conducting objects from inadvertently coming or being brought into contact with
live parts or interfering with the operation of the motors.
(b) Suitable insulating mats or platforms of
substantial construction and providing good footing shall be so placed on
floors and, if necessary, on frames of machines having exposed live parts above
150 volts to ground that the operators or other persons in the vicinity cannot
readily touch such parts unless standing on the mats, platforms, or insulating
floors. The suitable guarding of live parts by inclosures of barriers effective
during attendance or necessary adjustments of live parts will obviate the
necessity for insulating mats, and, if such mats are impracticable from the
nature of the location or process carried on, guards shall be used. If
connectors are used in motor leads, these should be provided with insulating
covering equal to that on the conductors.
(c) If necessary, steps and handrails shall
be installed on or about large machines to afford safe access to live parts
which shall be examined or adjusted during operation.
(d) If two or more machines, either of which
operates at over 150 volts to ground, are mechanically coupled together, and
the operator can touch the frames of more than one at a time, the frames of all
such machines shall be permanently grounded, unless they are bonded together
electrically and surrounded by insulating mats or platforms on which it is
necessary persons stand in order to touch the machine frames. If operating at
above 300 volts to ground, their frames shall always be grounded, and frames
shall also be grounded wherever, from the nature of the location or of
processes carried on, the use or maintenance of insulating mats or platforms is
impracticable. Reference should also be made to §
39.197(c)
(relating to grounding).
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.