34 Pa. Code § 39.85 - General requirements
Rooms or spaces in which electrical supply equipment is installed shall comply with the following requirements:
(1) No room or space in which electrical
supply equipment is installed shall be used for the storage of material or for
manufacturing processes causing hazard to electrical operators, except those
materials or processes attendant upon the production or distribution of a
supply of electrical energy.
(2)
They shall be free from flyings and inflammable gas, except for battery rooms.
Reference should be made to §§
39.121-39.127 (relating to storage
batteries). Indoor stations should be dry and well ventilated.
(3) In outdoor stations or stations in wet
tunnels or subways live parts of equipment shall be enclosed in weatherproof
cases, unless the equipment is suitably designed to withstand the prevailing
atmospheric conditions and the live parts are suitably guarded against
contacts, or isolated by elevation. Ungrounded conductors not in conduit shall
be on suitable insulators, properly guarded or isolated by elevation.