34 Pa. Code § 3a.36 - Clearances
(a) The following
clearances apply for boilers installed after January 1, 1960:
(1) The minimum clearance around each boiler
must be 30 inches with at least 6 feet clearance from the floor to overhead
obstructions.
(2) The minimum
clearance around each unfired pressure vessel must be 18 inches. The minimum
clearance in front of a manhole cover must be 30 inches.
(3) A clearance of at least 12 inches must be
provided between the floor and lower head or the underside of the shell of an
unfired pressure vessel. The clearance distance must be the measurement from a
vessel appendage to the next object.
(b) The following requirements apply to a
single installation or assembly of storage water heaters or instantaneous water
heaters, which operate as a unit:
(1) The
unit may be arranged with a minimum clearance of 6 inches between components if
an 18-inch clearance shall be maintained around the assembly. The clearance in
front of a manhole opening is a minimum of 30 inches.
(2) An assembly may not exceed 9 million BTU
input.
(3) Casings must be readily
removable for inspection purposes, if casings are provided.
(c) A new building containing multiple boiler
installations must meet the following minimum overhead clearance requirements:
(1) Between the boiler platform and the
ceiling: 7 feet.
(2) Between the
top of the boiler proper and the ceiling for all installations: 3 1/2
feet.
(3) Between the highest point
of any valve or fitting and the ceiling: 6 inches.
(d) Subsections (a) and (b) do not apply to
pressure vessels of factory assembled package units that are governed by §
3a.111 (relating to field
inspections) if there is adequate clearance for operation and inspection.
Subsection (a) applies to the entire factory assembled unit.
(e) The minimum clearance around a wall-hung
boiler must be 30 inches except for the wall mount side.
(f) The clearance between modules in a
modular system may be reduced to the manufacturer's recommendations if the
entire modular boiler system meets the 30-inch clearance requirement of
subsection (a)(1).
(g) This section
does not apply to a miniature boiler if the boiler can be safely inspected as
installed.
(h) Tripping hazards are
not permitted.