34 Pa. Code § 405.12 - Lumber elevators
(a) A
lumber elevator is a platform that is used to raise or lower stacked lumber
under the requirements of this section. An individual may not ride a lumber
elevator.
(b) The shaftway is
enclosed on all sides that are not used for loading or unloading with flush
partitions that are at least 6 feet high. Movable bars or railings are required
to protect all points of loading and unloading, unless gates are provided.
Flaring is at an angle of at least 75° from the horizontal and shall
protect all shearing points in the shaftway excluding each loading and
unloading landing.
(c) Gates are
required to protect all points of loading and unloading when the platform's
vertical travel exceeds 6 feet or when there are two or more landings. The
following types of automatic and semiautomatic gates may be used:
(1) Semiautomatic vertical-rising
gates.
(2) Fully automatic
vertical-rising gates only at terminal landings.
(3) Manually operated swinging or horizontal
gates with locking devices and electric brakes.
(4) Department-approved, power-operated
horizontal gates.
(d) A
locking device shall comply with the following requirements:
(1) An automatic locking device shall be
placed on, or attached to a manually operated gate. The locking device shall
prevent the normal operation of the platform when the gate is open and
unsecured. The locking device shall prevent the opening of the gate when the
car is away from the landing.
(2) A
shield shall be installed on openwork gates and shall be of sufficient size to
prevent access to the lock from the outside of the shaftway.
(e) The shaftway shall have a pit
with a depth of at least 2 feet from the lowest point of the underside of the
platform framing to the pit floor or highest projection when the platform is at
its lowest limit of travel. Toe guards, guide shoes or rollers attached to the
platform and buffers or bumpers may extend into this space.
(f) Substantial guides of either wood or
steel are required for installation on lumber elevators.
(g) Lifting capacity shall equal a live load
of at least 50 pounds per square foot of platform floor area. The gross weight
of the movable platform shall include railings, aprons, wirings, conduits,
outlets and every item that is permanently attached to the platform and its
rated lifting capacity.
(h) The
lifting speed of a lumber elevator may not exceed 15 feet per minute.
(i) A lumber elevator shall be equipped with
operating switches that meet the following requirements:
(1) An operating switch shall be located
where the entire shaftway is visible when gates are not installed.
(2) An operating switch shall be a continuous
pressure switch.
(3) A manually
operated emergency stop switch shall be placed adjacent to the elevator's
operating switches, driving machines, pit entrances, machine controller and
landings. An emergency stop switch shall be a manually reset switch and cannot
be dependent upon springs for proper operation.
(4) An emergency stop switch shall be red. No
other switch may be red.
(5)
Operating switches shall be labeled by function.
(j) Reverse phase protection is required when
alternating current is used.
(k)
Elevator screws shall be directly connecting with worm or beveled gears. Gears
shall be enclosed in a housing.
(l)
A lumber elevator that is not supported or operated by screws, plungers or
similar means shall have approved platform safeties capable of stopping and
holding the platform at any point of its travel and its rated lifting
capacity.
(m) The motor, controller
and brake shall be located in a lighted room outside of the shaftway, unless
the devices are located in the pit. The lumber elevator shall be equipped with
stone or masonry piers or columns capable of absorbing the impact of a
full-loaded platform when the motor and controller are located in the
pit.
(n) A lumber elevator shall be
equipped with normal terminal limit switches located in the shaftway or stop
motion devices on the operating machine and arranged to automatically bring the
platform to rest at either terminal landing.
(o) Final terminal limit switches shall be
installed and connected so the switch will function if a lumber elevator runs
by the normal terminal limit switch. Final terminal limit switches will
automatically shut off the power, apply the brake and prevent the operation of
the lumber elevator in either direction until adjustments are made to return
the lumber elevator to normal operation. Final terminal limit switches shall be
located in the shaftway.
(p) A
slack cable or slack chain device shall be installed on all winding drum or
sprocket power-driven lumber elevator machinery. The device shall automatically
shut off the power, apply the brake and stop the machinery when the platform is
obstructed in its descent.
(q) A
lumber elevator shall be equipped with an approved and enclosed fused main line
switch or an approved and enclosed circuit breaker switch. The switch shall be
located adjacent to the entrance door in the machine room when the motor and
controller are located in a machine room. The switch shall be located outside
of the shaftway and adjacent to the pit access door when the motor and
controller are located in the pit.
(r) A motor or controller shall be equipped
with a second device for disconnection when the motor or controller is not
visible from the disconnection equipment required in subsection (q). The second
disconnection device shall be equipped to accept a padlock that can lock the
device in an "open" and "off" position.
(s) Lighting shall be provided in all machine
spaces and pits within the shaftway and landings. The light switch shall be
mounted at the entryway to a machine space and pit.
(t) A lumber elevator shall be equipped with
a door that allows access to the pit when the motor or controller is located in
the pit. A pit access door is to meet all of the following requirements:
(1) A pit access door shall be located below
the bottom of the platform when the platform is at its lowest limit of
travel.
(2) A pit access door shall
be at least 30 inches by 30 inches in size, self-closing and
self-locking.
(3) A pit access door
shall have a switch to prevent operation of the elevator while the pit access
door is open.
(4) An emergency stop
switch shall be installed on the strike side of each pit access door.
(5) A switch for operating the pit lights
shall be installed on the strike side of all pit access doors.
(6) A sign shall be located on the exterior
strike side of each pit access door with the notation, "CAUTION-Elevator Pit
Access Door-Authorized Personnel Only." The sign lettering shall be a minimum
of 1/4 inch in width and 1 1/2 inches in height. The color of the lettering
shall contrast with the color of the access door.
(7) An owner or owner's agent shall have sole
possession of keys to each pit access door.
(u) A lumber elevator platform shall have a
steel frame designed with a minimum safety factor of six based on the highest
rating of either the rated lifting load or the rated static load, uniformly
distributed.
(v) A platform shall
be equipped with an apron on all its sides. When the travel distance of a
lumber elevator extends above the top of the surrounding floor level, the apron
shall have sufficient depth to enclose the space between the floor level and
the under side of the platform when the platform is at its travel
limit.
(w) As part of the initial
inspection, the elevator shall be loaded to rated lifting capacity and operated
throughout its entire travel. Platform safeties are to be tested with the
maximum rated lifting capacity.