34 Pa. Code § 50.93 - Special stage regulations
Stages used for theatrical, musical and like performances which are equipped with a rigging loft or fly gallery shall comply with the following:
(1)
Stage enclosure
walls. Every stage shall be enclosed on all sides with solid walls of
not less than 2-hour fire resistance rating extending continuously from
foundation to at least 4 feet above the roof.
(2)
Stage floor construction.
The entire stage, except the portion used for the working of scenery,
traps and other mechanical apparatus for the presentation of a scene, and the
roof over the stage may not be less than 3-hour fire resistance rated
construction. Openings through the stage floor shall be equipped with tight
fitting, solid wood trap doors not less than 3 inches in thickness or other
materials of equal physical and fire resistance rated properties.
(3)
Stage rigging loft. The
rigging loft, fly galleries and pin rails shall be constructed of
noncombustible materials.
(4)
Footlights and stage electrical equipment. Footlights and
border lights shall be installed in troughs constructed of noncombustible
materials. The switchboard shall be so located as to be readily accessible at
all times, and the storage or placing of stage equipment against it is
prohibited.
(5)
Exterior
stage doors. Required exit discharge door openings to the outer air
shall be protected with approved self-closing fire doors.
(6)
Proscenium wall. There
may be no openings in the wall separating the stage from the auditorium except
the main proscenium opening; two doorways at the stage level, one on each side
thereof; and, where necessary, not more than two doorways to the musician's pit
from the space below the stage floor. Each doorway may not exceed 21 square
feet in area and shall be protected with 1 1/2-hour B label fire door
assemblies. The distance between the top of the proscenium opening and the
ceiling of the stage shall be not less than 5 feet.
(7)
Proscenium curtain. The
proscenium opening shall be provided with an approved curtain of noncombustible
or fire-retardant material so designed and installed that it will protect
against passage of flame and smoke for 5 minutes. The curtain shall be operated
by an automatic heat activated device to descend instantly and safely and to
completely close the proscenium opening at a rate of temperature rise of 15 to
20 F per minute (0.14 C to 0.19 C per second); and by an auxiliary operating
device to permit immediate manual closing of the proscenium opening.
(8)
Scenery. Combustible
materials used in sets and scenery shall be rendered flame resistant.
(9)
Stage ventilation. Metal
or other approved noncombustible ventilators, equipped with movable shutters or
sash shall be provided over the stage, constructed to open automatically and
instantly by approved heat activated devices, with an aggregate clear opening
of not less than 1/8 the area of the stage.
(10)
Dressing and appurtenant
rooms.
(i)
Construction.
Dressing rooms, scene docks, property rooms, work shops and store
rooms and compartments appurtenant to the stage shall be fireresistive
construction and shall be separated from the stage and other parts of the
building by walls of not less than 2-hour fireresistance rating. The rooms
shall not be placed immediately over or under the operating stage
area.
(ii)
Opening
protectives. Openings other than to trunk rooms and the necessary
doorways at stage level shall not connect the rooms with the stage, and the
openings shall be protected with 1-hour self-closing B label fire
doors.
(iii)
Dressing room
and stage exits. Each tier of dressing rooms shall be provided with at
least two means of egress, one of which shall lead directly to an exit
corridor, outer court or street. Exit stairways from dressing and storage rooms
may be unenclosed in the stage area behind the proscenium wall. At least one
approved exit shall be provided from each side of the stage and from each side
of the space under the stage, and from each fly gallery and from the gridiron
to a street, outer court or passageway to a street. A steel ladder shall be
provided from the gridiron to a scuttle in the stage roof.