34 Pa. Code § 57.52 - Automatic alarms
(a) An
automatic fire alarm system shall be provided for C-4 occupancies except for
buildings totally protected by an automatic sprinkler system. The automatic
fire alarm system shall comply with §
50.52 (relating to automatic
system), except that buildings with 12 or less apartments may comply with
paragraph (4).
(b) Smoke detectors
shall be located in the corridors, stairs and rooms not located within an
individual apartment. This shall include unfinished basements. Heat detectors
or other detection devices may be approved by the Department for use in special
rooms such as boiler rooms, furnace rooms, incinerator rooms, and the like.
Detection devices required by this paragraph shall be interconnected with
required fire alarm systems.
(c) In
addition to the automatic fire alarm system required in paragraph (2), each
apartment shall have a minimum of one smoke detection device. This device may
be a single-station detection device which is not interconnected with the
automatic fire alarm system. Single-station detection devices shall be listed
as meeting U. L. 217, 1980 Edition.
(d) Smoke detectors listed as meeting U. L.
217, 1980 Edition, as multiple-station smoke detectors shall be provided in the
common areas, such as halls, corridors, stair towers, basements or similar
areas. These detectors shall be interconnected so that all devices sound an
alarm conditioned upon activation of an individual detector. The smoke
detectors may be ceiling or sidewall mounted, with a minimum of a 4-inch
clearance from a ceiling to wall jointure, measured from the jointure to the
top of the detector.
Notes
This section cited in 34 Pa. Code § 49.2 (relating to jurisdiction and effective dates).