34 Pa. Code § 57.81 - Hazardous areas
(a) Boiler or
furnace rooms, repair or maintenance rooms, trash rooms, and rooms or spaces
used for the storage of combustible materials in quantities deemed hazardous by
the Department shall be separated from other areas of the building by 1-hour
partitions, floors and ceilings. Openings shall be protected by C label door
assemblies. Combustion and ventilation air for boiler, incinerator or heater
rooms shall be taken directly from and discharged directly to the outside
air.
(b) American Gas Association
approved gas fired forced air furnaces and space heaters; U. L. approved
electrical resistive coil heating furnaces and U. L. approved oil fired forced
air furnaces and space heaters need not be enclosed.