37 Pa. Code § 14.2 - Physical requirements of vaults
(a) Vaults for retail distribution shall be
constructed below grade. Vaults for nonretail distribution may be constructed
either above or below grade.
(b)
The vault shall completely enclose each tank. There may not be openings in the
vault enclosure except those necessary for access to, inspection of, and
filling, emptying and venting of the tank. The walls and floor of the vault
shall be constructed of reinforced concrete at least 6 inches thick. The top of
an above grade vault shall be constructed of noncombustible material
constructed to be weaker than the walls to assure that in the event of an
explosion inside the vault, the thrust of the explosion will be inside the
vault. The top, floor and tank foundation shall be designed to withstand the
anticipated loading. The walls and floor of a vault installed below grade shall
be designed to withstand anticipated soil and hydrostatic loading. The vault
shall be substantially liquid tight and there may be no backfill around the
tank. There shall be sufficient space between the tank and the vault to allow
for inspection of the tank and appurtenances.
(c) Each vault and its tank shall be suitably
anchored to withstand uplifting by groundwater or flooding, including when the
tank is empty.
(d) The vault shall
be designed to be wind and earthquake resistant, in accordance with sound
engineering practice. The vault shall be resistant to damage from the impact of
a motor vehicle, or suitable collision barriers shall be provided.
(e) Each tank shall be in its own vault.
Adjacent vaults may share a common wall if the top of each vault is constructed
to conform to the requirements of subsection (b). The top of each vault shall
be constructed of noncombustible material constructed to be weaker than the
walls to assure that in the event of an explosion inside the vault, the thrust
of the explosion will be directed upward before a significantly high pressure
can develop inside the vault.
(f)
Connections shall be provided to permit venting of each vault to dilute,
disperse and remove vapors prior to personnel entering the vault.
(g) Vaults shall be provided with continuous
ventilation at a rate of not less than 1 cubic foot per minute per square foot
of floor area, but not less than 150 cubic feet per minute. Failure of the
exhaust air flow shall automatically shut down the dispensing system. The
exhaust system shall be designed to provide air movement across all parts of
the vault floor. Supply and exhaust ducts shall extend to within 3 inches, but
not more than 12 inches of the floor. The exhaust system shall be installed in
accordance with NFPA 91, Standard For Exhaust Systems For Air Conveying of
Materials. A means shall be provided to automatically detect flammable vapors
and to automatically shut down the dispensing system upon detection of the
flammable vapors in the exhaust duct at a concentration of 25% of the lower
flammable limit.
(h) Each vault
shall be equipped with a detection system capable of detecting liquids,
including water, and of activating an alarm upon detection.
(i) A means to recover liquid from the vault
shall be provided. If a pump is used to meet this requirement, the pump may not
be permanently installed in the vault. Electric powered portable pumps used to
recover liquid shall be suitable for use in Class I, Division I locations, as
defined in NFPA 70, National Electric Code.
(j) Vent pipes that are provided for normal
tank venting shall extend at least 12 feet above ground level.
(k) Emergency vents shall be vapor tight and
shall be permitted to discharge inside the vault. Long-bolt manhole covers will
not be permitted for this purpose.
(l) Each vault shall be provided with a means
for personnel entry. At each entry point, a warning sign indicating the need
for procedures for safe entry into confined spaces shall be posted. Employees
and other persons who anticipate entering the vault shall be made aware of and
each entry shall conform to applicable Federal regulations regarding confined
space entry. Each entry point shall be secured against unauthorized entry and
vandalism.
(m) Each vault shall be
provided with a suitable means to admit a fire suppression agent. The
connection shall be at least 25 feet from the nearest wall of the vault and
shall be compatible with standard couplings used by fire departments in that
area.
(n) The interior of a vault
shall be designated a Class I, Division I location as defined in NFPA 70,
National Electric Code.
(o) Each
vault shall be equipped with adequate lighting. The lighting shall be explosion
proof and conform with NFPA 70, National Electric Code.
(p) Tanks within vaults shall be approved for
aboveground use and shall have been tested in accordance with UL 142, Standard
for Steel Aboveground Tanks For Flammable Or Combustible Liquids, or an
equivalent test procedure. Individual tanks shall be limited to a maximum
capacity of 12,000 gallons.
(q)
Tanks within above grade vaults shall be at least 25 feet from buildings on the
same property, 25 feet from the nearest side of a public way and 50 feet from a
property line that may be built upon. Tanks within below grade vaults shall be
at least 5 feet from buildings on the same property, 5 feet from the nearest