52 Pa. Code § 59.18 - Meter, regulator and service line location
(a)
General requirements for meter
and regulator location.
(1) Unless
otherwise allowed or required in this section, meters and regulators must be
located outside and aboveground.
(2) Except in the case of an emergency, a
utility shall provide written notice to a utility customer by first class mail
or by personal delivery at least 30 days prior to relocating and subsequently
installing a meter or regulator outside the customer's building. The notice
must request that if the customer is not the owner of the building, the
customer shall forward the written notice to the owner of the building. If the
utility knows the current address of the owner of the building, notice shall
also be mailed or delivered to that address.
(3) The written notice must inform the
customer and building owner of the equipment that the utility proposes to
relocate, the planned new location and how to contact the utility to provide
supplemental information that the utility may not have, such as the building's
historic status. The written notice must include contact information for the
Commission's Bureau of Consumer Services.
(4) When necessary to install meters at
multiple locations on a premises, a utility shall provide a tag or other means
to indicate there are multiple meter locations.
(5) When selecting a meter or service
regulator location, a utility shall consider potential damage by outside
forces.
(6) The meter location must
accommodate access for meter reading, inspection, repairs, testing, changing
and operation of the gas shut-off valve.
(7) When feasible and practical to do so, the
meter location must accommodate the installation of the service line in a
straight line perpendicular to the main.
(8) Meters and service regulators may not be
installed in the following locations:
(i)
Beneath or in front of windows or other building openings that may directly
obstruct emergency fire exits.
(ii)
Under interior stairways.
(iii)
Under exterior stairways, unless an alternate means of egress exists and the
meter and service regulator are installed in a well-vented location under
stairs constructed of noncombustible material.
(iv) A crawl space.
(v) Near building air intakes under local or
State building codes.
(vi) In
contact with soil or other potentially corrosive materials.
(9) Unless caused by a customer's
or building owner's violation of applicable gas safety or tariff rules, a
utility shall pay the costs of relocating a meter or regulator when the
relocation is performed to meet utility or Commission safety
requirements.
(10) Unless caused by
a customer's or building owner's violation of applicable gas safety or tariff
rules, a utility shall pay the cost of extending customer-owned facilities to
the new meter or regulator location when the relocation is performed to meet
utility or Commission safety requirements.
(11) A customer or building owner requesting
that a meter or regulator be moved shall pay the costs associated with
relocation when the meter and regulator are currently situated in a suitable
location under State and Federal regulations.
(12) Utilities shall address meter, regulator
and service line location regulations in their tariffs.
(b)
Outside meter or service
regulator locations. Outside meters or service regulators shall be
installed in one of the following locations:
(1) When feasible and practical to do so,
above ground in a protected location adjacent to the building served, or as
close as possible to the point where a production or transmission line is
tapped.
(2) In a buried vault or
meter box.
(i) The vault or meter box must be
located on a customer's or building owner's property, either adjacent to the
building served or near the gas main.
(ii) Vaults may be located in a public
right-of-way, subject to the consent of local jurisdictions as may be
required.
(c)
General requirements for vaults or meter boxes.
(1) A utility shall consider proper design
and location criteria for a meter box, including:
(i) Ventilation.
(ii) Vehicular traffic.
(iii) Soil accumulation.
(iv) Surface water runoff.
(v) High water table.
(vi) Proximity to building air intakes or
openings.
(vii) Proximity to an
excessive heat source as defined in
49 CFR
192.353(c) (relating to
customer meters and regulators: location).
(2) Piping installed through vault walls
shall be properly coated to protect from corrosion.
(3) Vaults containing gas piping may not be
connected by means of a drain connection to any other underground
structure.
(4) When a meter box is
located outside a paved surface, a utility shall consider fill, topsoil or sod
being placed over the vault and, when feasible and practical to do so, choose
an alternate location.
(d)
Inside meter locations.
(1) Inside meter locations shall be
considered only when:
(i) The service line
pressure is less than 10 psig.
(ii)
A meter is located in a building that meets one of the following criteria:
(A) A building is listed in the National
Register of Historic Places or the customer or building owner notifies the
utility that the building is eligible to be listed in the National Register of
Historic Places and the eligibility can be readily confirmed by the
utility.
(B) A building is located
within a historic district that is listed in the National Register of Historic
Places or the customer or building owner notifies the utility that the historic
district is eligible to be listed in the National Register of Historic Places
and the eligibility can be readily confirmed by the utility.
(C) A building has been designated as
historic under the act of June 13, 1961 (P. L. 282, No. 167) (53 P. S. §
§
8001-8006), known as the
Pennsylvania Historic District Act, the Pennsylvania Municipalities Planning
Code (53 P. S. §
§
10101-11202) or a municipal home
rule charter.
(D) A building is
located within a locally designated historic district or is eligible for the
listing, or a building is individually designated under a local ordinance as a
historic landmark or is eligible for the listing.
(iii) Protection from ambient temperatures is
necessary to avoid meter freeze-ups.
(iv) A utility determines that a meter is
subject to a high risk of vandalism based on the utility's prior
experience.
(v) A utility
determines that an outside meter location is neither feasible nor
practical.
(2) Except for
low pressure systems with service line pressure less than 10 psig, regulators
must be located outside when a meter is located inside.
(3) Installed inside meters must be attached
to an operable outside shut off valve.
(4) Meters installed within a building must
be located in a ventilated place not less than 3 feet (914 millimeters) from a
source of ignition or source of heat which may damage the meter.
(e)
Other meter or service
regulator locations. A utility may consider a specially constructed
cabinet recessed in the building wall, sealed from inside the building and
vented to and accessible from outside the building.
(f)
General requirements for new
service lines. When feasible and practical to do so:
(1) A building may not have more than one
service line.
(2) A service line
must terminate at the inlet valve of the meter set in the building in which the
service line enters.
(3) The
service line must be installed in a straight line perpendicular to the
main.
(g)
Application of regulation.
(1) Beginning September 13, 2014, utilities
shall comply with this section for new meter, regulator and service line
installations in new locations.
(2)
Beginning September 13, 2014, utilities shall comply with this section when
replacing existing meters, regulators and service line facilities.
(3) By September 13, 2034, utilities shall
complete replacement of existing facilities in compliance with this section or
incorporate the requirements of this section in a distribution integrity
management plan, whichever occurs first.
Notes
The provisions of this § 59.18 amended under the Public Utility Code, 66 Pa.C.S. § 501.