(1) Overhead Power
and Communication Lines. Type of Construction.
(a) Longitudinal installations of overhead
lines within highway rights-of-way are limited to single pole type of
construction unless approved by the State Transportation Engineer as an
exception to these rules and regulations based on extreme hardship conditions.
new facilities or existing facilities being rebuilt in their entirety shall be
designed to provide maximum spacing of poles within the bounds of sound
engineering principles and economic considerations, Alignment shall be as near
uniform as practical to avoid anchors, stub poles and other ground mounted
appurtenances.
(b) On and along
conventional highways in rural areas, poles and related ground mounted
appurtenances shall be located at or as near as practical to the rights-of-way
line. As a minimum the poles shall be located outside the clear zone for the
highway section involved without full access control.
(c) Joint use construction, as indicated by
Rule 222 of Part 2 of the National Electrical Safety Code, shall be considered
at all feasible locations where more than one utility or type of facility is to
be located overhead.
(d) The
minimum vertical clearance for overhead power and communication lines above the
traffic lanes of the highway and the lateral and vertical clearance from
bridges shall conform to currently applicable National Electrical Safety
Code.
(e) Stub poles or guy wires
to ground anchors shall not be placed between a pole and the traveled way where
they encroach upon the clear zone.
(f) Where irregular shaped portions of the
right-of-way extend beyond the normal right-of-way limits, variances in the
location from the right-of-way will be allowed as necessary to maintain a
reasonably uniform alignment for longitudinal installations.
(g) Longitudinal installations will not be
permitted in the highway median.
(h) On crossing a highway, facilities shall
not be located in a highway median within the clear zone from both directions
of travel.
(i) Crossing of the
highway shall be as near normal as practical under prevailing
circumstances.
(j) On or along
conventional highways in urban areas, poles and related ground-mounted
appurtenances shall be located at or as near as practical to the right-of-way
line. Where there are curb and gutter sections, poles shall be located as far
as practical behind the face of outer curbs, and where sidewalks are provided
to the back of sidewalk if at all practical.
It is realized that these sections of highway with closely
abutting improvements and usually a minimum width of right-of-way are special
cases which must be resolved in a manner consistent with the prevailing
limitations and conditions. Considerations must be given to designs employing
self-supporting, armless, single pole construction, with vertical alignment of
wires or cables, or other techniques permitted by applicable governmental or
industry codes. Exceptions to these clearances may be considered where poles
and related ground-mounted appurtenances are placed behind guard rails,
retaining walls or deep drainage ditches, at the toe or top of steep slopes, or
at other similarly protected locations without full access control.
(2) Underground Power,
Communication, Water and Sanitary Sewer Facilities.
(a) On conventional highways in rural areas
longitudinal installations shall be at or as near as practical to the
right-of-way line so as to minimize interference with highway drainage, the
structural integrity of the traveled way, shoulders, embankment and safe
operation of the highway. Alignment of facilities shall be as uniform as
possible under prevailing circumstances in order that points of access for
installation and maintenance may be kept to a minimum. No new installations
will be permitted within the normal highway median area, except in extreme
hardship cases where there is no other feasible location.
(b) On or along conventional highways in
urban areas underground utility facilities shall be located at or as practical
to the highway right-of-way line. Where there are curb and gutter sections,
underground utilities shall be located outside the travel lanes whenever
practical. No new installations will be permitted within the normal highway
median area, except in extreme hardship cases where there is no other feasible
location. It is realized that these sections of the highway must be considered
as special cases in considering longitudinal encroachment of underground
facilities, and problems must be resolved on a case by case basis consistent
with prevailing limitations and conditions and design considerations to elevate
to every extent possible interference with safety and operations of the highway
facilities. Relocation of utility facilities and/or alterations to accommodate
reconstruction of the highway will be reviewed and considered on a case by case
based on the conditions that exist at the time.
(c) Crossings shall be located as near normal
to the highway alignment as practical. Crossing shall have a minimum of 36
inches of cover under the low point of the highway for uncased installations
and 30 inches for encased installations.
(d) Conditions which are generally unsuitable
or undesirable for underground crossings should be avoided. These include
locations such as in deep cuts; near footings of bridges and retaining walls;
across intersections at grade or ramp terminals, at cross drains where flow of
water, drift or stream bedload may be obstructed; within basins of an underpass
drained by a pump; and in wet or rocky terrain where it will be difficult to
attain minimum cover.
(e)
Longitudinal underground installations under sidewalks or grass plots of curb
and gutter urban sections and installations located within 8-fect of the
right-of-way line or rural highways (except as specified below) shall have a
minimum cover of 24-inches. Longitudinal underground installations other than
plowed cable which are located between the ditches of the highway template or
within 5-feet of the ditch line shall have a minimum cover of 36-inches.
All longitudinal underground installations which cross under
drainage ditches will be located a minimum of 36-inches below the flow line of
the ditch. All other underground installation shall have a minimum cover of
30-inches. A minimum cover of 24-inches is acceptable for any longitudinal
installation where encasement or mechanical protection is provided. Cable
plowed into shoulders shall have a minimum cover of 30-inches. (See Page
918.012)
REQUIRED MINIMUM COVER FOR LONGITUDINAL UNDERGROUND
INSTALLATIONS
Click to
view Image
(f)
Pedestals, fire hydrants, markers or other above ground utility appurtenances
installed as a part of underground utility facilities shall be located at or as
near the highway right-of-way line as practical. In all cases they must be
outside the clear zone.
(g) Manholes
will not be permitted in the median, pavement or shoulder of the highway in
rural areas, nor will they be permitted in the median, pavement or shoulder in
urban areas except where this practice is shown to be impractical or creates an
undue hardship.
(h) Provisions shall
be made in the overall installation of underground facilities to provide
shut-off valves or sectionalizing devices in order that segments of the
facility may be taken out of service promptly in case of damage or
failure.
(i) Water mains and water
service lines in excess of two inches in diameter and sanitary sewer mains
crossings normal to and under the traveled way of existing highways shall be
encased when installed by boring or pushing under the traveled way. Length of
encasements shall be consistent with paragraph (3), subparagraph (g) of these
rules and regulations. Water mains, water service lines, or sewer mains
installed and/or relocated during construction or reconstruction of the highway
may be installed without an encasement when trenched construction consistent
with the Department of Transportation's standard specification for pipe
structures is utilized.
(j) Sanitary
sewer force mains shall be constructed of durable mechanical joint or lock
joint material when located on highway bridge structures.
(3) Pipelines or Transmission Lines Carrying
Flammable, Corrosive, Expansive, Energized or Unstable Transmittants.
(a) This section applies to interstate and
intrastate carriers whose facilities are operated as pipelines or transmission
lines as defined by applicable ANSI Standard Code (Example: Definition of
pipeline or transmission line as set in Section 805.62 of ANSI Standard Code
for Pressure Piping, Gas Transmission and Distribution Piping Systems, ANSI
B31.8-1968).
(b) For all crossings,
the angle of crossing shall be based on economic considerations of practical
alternates. The crossing shall be located as near normal to the highway
alignment as practical.
(c)
Conditions which are generally unsuitable or undesirable for crossings shall be
avoided. These include locations in deep cuts; near footings of bridges and
retaining walls; across intersections at grade or ramp terminals; at cross
drains where flow of water, drift, or stream bedload may be obstructed; within
basins of an underpass drained by a pump if pipeline carries a liquid or
liquefied gas; and in wet or rocky terrain where it will be difficult to attain
minimum cover.
(d) Longitudinal
installations of pipelines or transmission lines within highway rights-of-way
will be considered only in extreme hardship cases. Each request will be
considered on its own merits subject to the following conditions:
1. Longitudinal installations on conventional
highways in rural areas shall be located as near the right-of way line as
possible and alignment shall be as near uniform as practical. The structural
integrity of the traveled way, shoulders, and embankment; and the safe
operation of the highway shall be maintained in all instances. Highway drainage
shall not be impaired by the installation.
2. Longitudinal installations oil
conventional highways in urban areas shall be located as near as practical to
the right-of-way line. In any event they shall be located so as to be removed
train the traveled way as far as possible. installation in these areas pose
special problems and require special design consideration to provide the most
feasible solution where minimum widths of right-of-way are available.
(e) Vertical and horizontal
clearance between a pipeline and highway structures or other highway or utility
facilities shall be sufficient to permit maintenance of the pipelines and the
other facilities
(f) The following
controls shall apply to the burying of pipelines or transmission lines within
highway rights- of-way:
1. Minimal cover for
longitudinal installations shall be consistent with applicable ANSI Standard
Code or orders issued by appropriate governmental authority.
2. The minimum cover shall be thirty inches
below the low point of the highway cross-section for encased crossings and
thirty-six inches for uncased crossings.
(g) Pipelines or transmission lines may be
installed under State highways without using an encasement pipe under the
following conditions:
1. When trenched
construction is utilized in the adjustment of existing pipelines to accommodate
reconstruction of the highway. Wall thickness of carrier pipe, coating and
wrapping, welds and cathodic protection shall be in accordance with applicable
ANSI Standard Code, industry, or applicable governmental codes.
2. New installations under existing State
highways where soil conditions permit the installation of the carrier pipe at a
depth with minimum cover or greater without damage to its protective coating.
Wall thickness of the carrier pipe, welds and cathodic protection shall be in
accordance with applicable ANSI Standard Code, industry, or applicable
governmental codes.
3. The
Department of Transportation will not permit the cutting of pavement of
traveled lanes or excavation of adjacent shoulders for replacement, maintenance
or inspection of uncased pipeline crossings. Excavation of highway
rights-of-way will be limited to an area that will not disturb the highway
embankment.
4. At crossings of
uncased pipelines. where the pipeline has a cover less than four feet to the
highway drainage flow line, the side ditches of the highway shall be paved a
distance of five feet either side of the pipeline centerline with concrete at
elevation of highway ditch or at the toe of slope where there is no ditch in
accordance with the Department's specifications, to alleviate the problem of
erosion or damage to the pipeline during maintenance of the highway.
(h) Encasement or provision of
allied mechanical protection by installation in tunnel or gallery; grouting by
mortar filling borehole annulus; cradling; capping; walling; boxing or
jacketing, as detailed in Appendix #5, shall be required under file following
conditions:
1. For crossings where it is not
possible to obtain minimum cover due to other utilities, soil conditions, water
table, local ordinances, or other reasons.
2. All crossings where soil conditions
preclude the installation of carrier pipe under existing highways by boring or
jacking without damage to the protective coating.
3. Where pipelines are located near footing
of bridge or other highway structures; across Unstable of subsiding ground; or
near other locations where there may be hazards.
4. On conventional highways the encasement of
mechanical protection shall extend a distance of five feet beyond the highway
embankment or back of side ditch. On curbed portions of conventional highways
the encasement or protection provided shall extend to the back of curb or
sidewalk.
5. On freeway highway
projects the encasement or allied :mechanical protection shall extend the
entire width of the rights-of-way including adjacent frontage roads where
topography will permit replacement or maintenance of the pipeline. Exceptions
to the length of encasement will be considered on freeway project: where the
pipeline crossing is located in an area where the median width is in excess of
eighty feet or overall right-of-way width is greater than normally acquired for
the type of highway involved and in areas where topography precludes use of
encasement to repair or replace the carrier pipe.
(i) Every pipeline or transmission line shall
be identified by a permanent marker at the right-of-way lines or as near
thereto as possible.
(j) Encased
crossings shall be vented in order that gases may be exhausted or evacuated
from the encasement pipe. Vents shall be placed at the high end of short
casing,, and at both ends for casings greater than 150 feet in length. Vent
standpipes shall be located at or as near to the right-of-way line as possible
so as not to interfere with maintenance of the highway and in a place where
they will not be obscured by vegetation.
(4) Gas Mains, Gas Distribution Mains and Gas
Service Lines.
(a) For all crossings, the
angle of crossing shall be based on economic considerations of practical
alternatives. The crossing shall be located as near normal to the highway
alignment as practical.
(b)
Conditions which are generally unsuitable or undesirable for crossings shall be
avoided. These include locations in deep cuts; near footings of bridges and
retaining walls, across intersections at grade or ramp terminals; at cross
drains where flow of water, drift, or stream bedload may be obstructed; within
basins of an underpass drained by a pump if a main carries a liquid or
liquefied gas; and in wet or rocky terrain where it will be difficult to attain
minimum cover.
(c) Longitudinal
installations on conventional highways in rural areas shall be located as near
the right-of-way line as possible and alignment shall be as near uniform as
practical. The structural integrity of the traveled way, shoulders, and
embankment; and the safe operation of the highway shall be maintained in all
instances. Highway drainage shall not be impaired by the
installation.
(d) Longitudinal
installations on conventional highways in urban areas shall be located as near
as practical to the right-of-way line. In any event they shall be located so as
to be removed from the traveled was as far as possible. Installations in these
areas pose special problems and require special design consideration to provide
the most feasible solution where minimum widths of right-of-way are
available.
(e) Vertical and
horizontal clearance between a gas main or gas distribution main and highway
structures or other highway or utility facilities shall be sufficient to permit
maintenance of the gas main or gas distribution main and other
facilities.
(f) The following
controls shall apply to the cover over gas mains, gas distribution and gas
service lines within highway rights-of-way:
1.
Minimum cover for longitudinal installations shall be consistent with ANSI
Standard Code USAS B31.8 or orders issued by appropriate governmental
authority.
2. The minimum cover
shall be thirty inches below the low point of the highway cross-section for
encased crossings and thirty-six inches for uncased coverings.
(g) Gas mains, gas distributions
mains or gas service lines may be installed within highway rights-of-way and
under the traveled way of highways without encasement under the following
conditions:
1. When trenched construction is
utilized in the adjustment of existing facilities to accommodate reconstruction
of the highway or installation of new mains or service lines within highway
rights-of-way. Wall thickness or carrier pipe, coating and wrapping, welds and
cathodic protection shall be in accordance with ANSI Standard Code for Pressure
Piping Gas Transmission and Distribution Systems ANSI B31.8 or orders of
appropriate governmental authority.
2. Crossing under existing highways where
soil conditions permit the installation of the carrier pipe without damage to
its protection coating. Wall thickness of carrier pipe, coating and wrapping,
welds and cathodic protection shall be in accordance with ANSI Standard Code
for Pressure Piping Gas Transmission and Distribution Systems. ANSI
B31.8
3. At crossings of uncased
pipelines the side ditches of the highway shall be paved a distance of five
feet either side of the pipeline centerline with concrete at elevation of
highway ditch or at the toe of slope where there is no ditch in accordance with
Department of Transportation specifications to alleviate the problem of erosion
or damage to the gas main during maintenance of the highway.
4. When a gas main or gas distribution main
or gas service line is adjusted to accommodate highway construction and an
uncased crossing of the highway is proposed, consideration shall be given to
future replacement or maintenance of the facility at locations where it would
be impractical to borer or jack a replacement pipe under the highway. Provision
for replacement at such locations may include, but is not limited to:
(i) A casing enclosing the carrier
pipe.
(ii) A spare encasement
pipe.
(iii) Enlargement of the
carrier pipe to a size sufficient to be used as a casing.
(iv) A gallery or box culvert for future
installation of carrier pipe.
5. The Department of Transportation will not
permit the cutting of pavement or traveled lanes or excavation of adjacent
shoulders for replacement, maintenance or inspection of uncased gas main
crossings. Excavation of highway rights-of-way will be limited to an area that
will not disturb the highway embankment.
(h) Encasement or provision of allied
mechanical protection by installing gas mains or gas distribution in tunnel or
gallery; grouting by filing borehole annulus; cradling; capping; walling;
boxing or jacketing; as detailed in Appendix #5, shall be required under the
following conditions:
1. Crossings where it is
not possible to obtain minimum cover due to other utilities, soil conditions,
water table, local ordinances, or other reasons.
2. Crossings where soil conditions preclude
the installations of carrier pipe under existing highways by boring or jacking
without damage to the protective coating.
3. Where pipelines are locate near footing of
bridge or other highway structures; across unstable or subsiding ground; or
near other locations where there may be a hazard.
4. On conventional highways the encasement or
mechanical protection shall extend a distance of five feet beyond the highway
embankment or back of side ditch. On curbed portions of conventional highways,
the encasement or protection provided shall extend to the back of curb or
sidewalk. On freeway highway projects the encasement or allied mechanical
protection shall extend the entire width of the rights-of-way including
adjacent frontage roads where topography will permit replacement or maintenance
of the carrier pipe. Exceptions to the length of encasement will be considered
on freeway projects where a gas main or gas distribution main is located in an
area where the median width is in excess of eighty feet or overall
rights-of-way width is greater than normally acquired for the type of highway
involved and in areas where topography precludes use of encasement to repair or
replace the carrier pipe.
(i) Crossings of the highway shall be
identified by a permanent marker placed at the right-of-way lines or as near
thereto as possible. In all cases they shall be located so as not to interfere
with maintenance of the highway.
(j) Encased crossings shall be vented in
order that gases may be exhausted or evacuated from the
encasement pipe. Vents shall be placed at the high end of short casings and at
both ends for casings greater than 150 feet in length. Vent standpipes shall be
located at or as near to the right-of-way line as possible so as not to
interfere with maintenance of the highway and in a place where
they will not be obscured by vegetation.
(5) Roadway Lighting
(a) The Department of Transportation has
developed these rules in an effort to provide a safe, effective and economical
lighting system. This can be obtained by utilizing greater mounting heights
which results in a more uniform illumination with fewer poles, by using
break-away supports and by placing the supports a sufficient distance from the
edge of the travel way. The following are prime considerations:
1. Emphasis on minimizing maximum to minimum
footcandle ratios.
2. Optimizing
average to minimum footcandle ratios.
3. Providing adequate levels of
illumination.
4. Minimizing the
amount of glare.
5. Reducing the
number of poles required.
(b) New lighting installations on the State
system of roads will be reviewed by the Department of Transportation on the
basis of the following criteria:
1. Minimum
Mounting Height-45 feet. In the relocation of utility poles on State highway
rights-of-way, every effort shall be taken to relocate these poles to provide
for their use for roadway lighting. This will provide an economical system,
allowing utility poles to be used for street lighting as well as electrical
distribution. It will also reduce the number of the fixed objects most
frequently involved in motor vehicle accidents.
Where electrical distribution or communication lines are in
existence, mounting heights less than 45 feet may be approved in order to
utilize existing poles to the full extent; however, the effectiveness of a
satisfactory lighting job should not be jeopardized just to use existing
poles.
2. Pole setback from
the edge of pavement-20 feet minimum, or at the right-of-way line if located
less than 20 feet from the edge of pavement. In urban areas, poles shall be
located as near to the right-of-way line as possible, but in no case shall they
be less than 2 feet from the face of the curb. Where a utility strip or grass
plot is located between the face of curb and the sidewalk, poles may be allowed
in this area if they can be set at least 2 feet from the face of the curb. All
installation must meet the minimum requirements set by the National Electric
Safety Code.
3. Poles shall not be
set in the median of the roadway, except where a 20 feet minimum setback can be
obtained, or where protected by guardrails already existing because of other
safety considerations.
4. Mast Arm
Length-Provision shall be made for the horizontal distance from the lamp to the
edge of the pavement to be no greater than 5 feet, except as dictated by
approved special lighting design.
5. Maximum maintained average horizontal
footcandle level shall be used as recommended in the latest edition of the
AASHTO Publications "An Information Guide For Roadway
Lighting".
6. Maintenance
factor-as suggested by the manufacturer.
7. Maximum allowable uniformity ratio 3.00:1
based on Average/Minimum Horizontal Footcandle Level.
8. Maximum allowable uniformity ratio -
6.00:1 based on Maximum/Horizontal Footcandle Level.
9. Concrete pole bases preferably should be
flush but shall not extend over 4 inches above ground level.
10. Luminaire pole mountings shall be of an
approved AASHTO breakaway type. in urban or highly developed areas where travel
speeds are low and pedestrian activity high, consideration will be given to the
installation of non-breakaway mountings where there is eminent danger of an
impacted support striking a pedestrian, private property or other traffic.
Poles to be located behind existing guardrail, rock bluffs, embankments or
ditches are not required to be the breakaway type.
11. Poles used in a lighting system required
to be located greater than 20 feet front the edge of the highway due to
physical constraints and not meeting acceptable uniformity ratios should be
designed using offset lighting applications.
12. Luminaires mounted 45 feet above the
pavement on bridges often become inoperable because of excessive vibration from
traffic. Therefore, the mounting height for bridge lighting
may vary, Light standards may be installed 30 or 35 feet above the pavement if
appropriate uniform ratios can be achieved for that portion of the design. If
satisfactory uniform ratios cannot be obtained for the design using the shorter
mountings, mountings of 40 to 45 feet should be considered for the lighting
design. All luminaries mounted on bridges must be approved by the Structures
Division.
13. Transitional lighting
should be provided when the average maintained horizontal footcandle level of
illumination for lighting designs exceeds 1.00 footcandles. The roadway sector
requiring transitional lighting should be illuminated so as to allow the
motorist's eyes to adjust to a different level of illumination and should be
traditionally illuminated for no less than 15 seconds. The level of
illumination for transitional lighting sector should be equal to approximately
one-half of the preceding higher lighted sector. The terminal illumination in
the lowest sector should not be less than 0.25 footcandle nor more than 0.5
footcandle. An expedient formula for calculating the required roadway lengths
for transitional lighting is as follows:
L = (RS) (C) (T)
Where L = Length of Transitional Lighting
RS = Running Speed Along Roadway Section in MPH
C = 1.47 (Converts MPH to Feet per Second)
T = 15 See (Recommended exposure time to allow motorist's
eyes to adjust to different level of illumination).
14. Transitional lighting is best provided by
maintaining the same average spacing and by using lower wattage lamps. This
allows for future extension of the lighting system without having to
relocate mountings.
(c) The Engineering Director of the
Department of Transportation's Maintenance Division will be responsible for
reviewing and approving all requests for roadway lighting on existing
conventional highway projects. Requests for roadway lighting on existing
freeway projects will be reviewed and approved by the Engineering Director of
the Design Division.
(d) It is
recognized that certain locations will not permit installation of lighting
consistent with these rules and regulations in every respect. In such cases the
proposal submitted to the Department of Transportation will be reviewed by the
Engineering Director of the Maintenance or Design Division and forwarded along
with recommendations to the State Transportation Engineer for approval or
disapproval of the installation.