16 Tex. Admin. Code § 14.2619 - Installation of Piping
(a) Fuel lines
shall be supported at least every 21 to 27 inches.
(b) Joint compound or tape acceptable for use
with LNG shall be applied to all male pipe threads prior to assembly.
(c) Piping and fittings shall be clean and
free from cutting or threading burrs and scaling. The ends of all piping shall
be reamed.
(d) Bends in piping or
tubing are prohibited if the bend weakens the pipe or tubing. Bends shall be
made by bending tools designated for this purpose.
(e) Joints or connections shall be located
only in an accessible location.