16 Tex. Admin. Code § 65.606 - Atmospheric Vents, Gas Vents, Bleed or Relief Lines for Power Boilers, Unfired Steam Boilers and Process Steam Generators with Supplemental Firing (extensions only)
(a) Gas pressure
regulators not incorporating integral vent limiters, and all other gas train
components requiring atmospheric air pressure to balance a diaphragm or other
similar device, shall be provided with a connection for a vent line.
(1) The vent lines in subsection (a) shall
be:
(A) sized in accordance with the component
manufacturer's instructions; and
(B) at least the same size as the vent outlet
of the device.
(2) Where
there is more than one gas pressure regulator at a location, each gas pressure
regulator shall have a separate vent. The vent lines may be manifolded in
accordance with accepted engineering practices to minimize back pressure in the
event of a diaphragm failure (see subsections (c) and (d)).
(3) A gas pressure regulator shall not be
vented into the boiler flue or exhaust system.
(b) Gas pressure relief valves may discharge
into common manifolding only with other gas vent, bleed, or relief lines. When
manifolded, the common vent line shall have a cross-sectional area not less
than the area of the largest vent line plus 50% of the areas of the additional
vent lines.
(c) Atmospheric vent
lines, when manifolded, shall be connected into a common atmospheric vent line,
having a cross-sectional area not less than the area of the largest vent line,
plus 50% of the areas of the additional vent lines.
(d) Atmospheric vent lines shall not be
connected to any common or manifolded gas vent, bleed, or relief
lines.
(e) All vent and relief
lines shall be:
(1) piped to the outdoors at a
safe point of discharge, so there is no possibility of discharged gas being
drawn into the air intake, ventilating system, or openings of any structure or
piece of equipment;
(2) shall
extend sufficiently above any structure, so that gaseous discharge does not
present a fire hazard; and
(3) a
means shall be provided at the terminating point to prevent blockage of the
line by foreign material, moisture, or insects.