26 Tex. Admin. Code § 511.162 - General Construction Requirements
(a) Location. Any
proposed limited services rural hospital (LSRH) shall be easily accessible to
the community and to service vehicles such as delivery trucks, ambulances, and
fire protection apparatus. No building may be converted for use as an LSRH
which, because of its location, physical condition, state of repair, or
arrangement of facilities, would be hazardous to the health and safety of the
patients.
(1) Hazardous locations.
(A) Underground and above ground hazards. New
LSRHs or additions to existing LSRHs shall not be constructed within 150 feet
of easement boundaries or setbacks of hazardous underground locations including
liquid butane or propane, liquid petroleum or natural gas transmission lines,
high pressure lines, and not within the easement of high voltage electrical
lines.
(B) Fire hazards. New LSRHs
and additions to existing LSRHs shall not be built within 300 feet of above
ground or underground storage tanks containing liquid petroleum or other
flammable liquids used in connection with a bulk plant, marine terminal,
aircraft refueling, bottling plant of a liquefied petroleum gas installation,
or near other hazardous or hazard producing plants.
(2) Undesirable locations.
(A) Nuisance producing sites. New LSRHs shall
not be located near nuisance producing industrial sites, feed lots, sanitary
landfills, or manufacturing plants producing excessive noise or air
pollution.
(B) Cemeteries. New
LSRHs shall not be located near a cemetery in a manner that allows direct view
of the cemetery from patient windows.
(C) Flood plains.
(i) Previously licensed eligible general or
special hospital. An existing building or a portion of an existing building
located in a designated 100-year flood plain that was previously licensed as a
general or special hospital but has been vacated or used for purposes other
than a hospital, will not be licensed as an LSRH.
(ii) Existing LSRH. Access and required
functional LSRH components shall be constructed above the designated flood
plain in a new addition to an existing LSRH located in a designated 100-year
flood plain.
(D)
Airports. Construction of new LSRHs shall be avoided in close proximity to
airports. When LSRHs are proposed to be located near airports, recommendations
of the Texas Aviation Authority and the Federal Aviation Authority shall apply.
An LSRH may not be constructed within a rectangular area formed by lines
perpendicular to and two miles (10,560 feet) from each end of any runway and by
lines parallel to and one-half mile (2,640 feet) from each side of any
runway.
(b)
Environmental considerations. Development of an LSRH site and LSRH construction
shall be governed by state and local regulations and requirements with respect
to the effect of noise and traffic on the community and the environmental
impact on air and water.
(c) LSRH
site.
(1) Paved roads and walkways. Paved
roads shall be provided within the lot lines to provide access from public
roads to the main entrance, emergency entrance, entrances serving community
activities, and to service entrances, including loading and unloading docks for
delivery trucks.
(A) Emergency entrance. An
LSRH shall have its emergency entrance well-marked to facilitate entry from the
public roads or streets serving the site.
(B) Access to emergency department. Access to
the emergency entrance shall not conflict with other vehicular traffic or
pedestrian traffic and shall be located so as not to be compromised by
floods.
(C) Pedestrian traffic.
Finished surface walkways shall be provided for pedestrians.
(2) Parking. Off-street parking
shall be available for visitors, employees, and staff. Parking structures
directly accessible from an LSRH shall be separated with two-hour fire rated
noncombustible construction. When used as required means of egress for LSRH
occupants, parking structures shall comply with National Fire Protection
Association (NFPA) 88A, Standard for Parking Structures, 2011 edition. This
requirement does not apply to freestanding parking structures.
(A) Number of parking places. In the absence
of a formal parking study, one parking space shall be provided for each day
shift employee plus one space for each patient station. This ratio may be
reduced in an area convenient to a public transportation system or to public
parking facilities on the basis of a formal parking study. Parking facilities
shall be increased accordingly when the size of existing facilities is
increased.
(B) Additional parking.
Additional parking shall be required to accommodate medical staff, outpatient
and other services when such services are provided.
(C) Emergency and delivery parking. Separate
parking facilities shall be provided for ambulances and delivery
vehicles.
(d)
Building design and construction requirements. Every building and every portion
thereof shall be designed and constructed to sustain all dead and live loads in
accordance with accepted engineering practices and standards and the local
governing building codes. Where there is no local governing building code, the
LSRH shall be constructed in accordance with the International Building Code,
2003 edition.
(1) General architectural
requirements. All new construction, including conversion of an existing
building to an LSRH, and establishing a separately licensed LSRH in a building
with an existing licensed LSRH, shall comply with Chapter 18 of the NFPA 101,
Life Safety Code, 2012 edition (NFPA 101), Subchapter F of this chapter
(relating to Fire Prevention and Safety), and this subchapter. An LSRH shall
submit construction documents to the Texas Health and Human Services Commission
(HHSC) in accordance with §
511.167 of this subchapter
(relating to Preparation, Submittal, Review, and Approval of Plans, and
Retention of Records).
(A) Physical
environment. A physical environment that protects the health and safety of
patients, personnel, and the public shall be provided in each LSRH. The
physical premises of the LSRH and those areas of the LSRH's physical structure
that are used by the patients (including all stairwells, corridors, and
passageways) shall meet the local building and fire safety codes, Subchapter F
of this chapter, and this subchapter.
(B) Construction type. An LSRH may occupy an
entire building or a portion of a building, provided the LSRH portion of the
building is separated from the rest of the building in accordance with
subparagraph (C) of this paragraph and the entire building or the LSRH portion
of the building complies with this subchapter's requirements (type of
construction permitted for hospitals by NFPA 101 §18.1.6.2), and the
entire building is protected with a fire sprinkler system conforming with
requirements of NFPA 13, Standard for the Installation of Sprinkler Systems,
2010 edition.
(C) Separate
buildings. Portions of a building divided horizontally with two-hour fire rated
walls that are continuous (without offsets) from the foundation to above the
roof shall be considered as a separate building. Communicating openings in the
two-hour wall shall be limited to public spaces such as lobbies and corridors.
All such openings shall be protected with self-closing one and one-half hour,
Class B fire door assemblies.
(D)
Design for the accessibility. Special considerations benefiting staff,
visitors, and patients with disabilities shall be provided. An LSRH shall
comply with the Americans with Disabilities Act (ADA) of 1990,
Public Law
101-336 , 42 United States Code, Chapter 126, and
Title 36 Code of Federal Regulations, Part 1191, Appendix A (relating to
Accessibility Guidelines for Buildings and Facilities) or 16 TAC Chapter 68
(relating to Elimination of Architectural Barriers), Texas Accessibility
Standards (TAS), April 1, 1994 edition, issued by the Texas Department of
Licensing and Regulation, under Texas Government Code Chapter 469 (relating to
Elimination of Architectural Barriers).
(E) Patient safety. In developing
construction documents for submission to HHSC in accordance with §
511.167 of this subchapter, the
owner shall comply with the requirements of Texas Health and Safety Code
Chapter 256 (relating to Safe Patient Handling and Movement Practices). Texas
Health and Safety Code §
256.002(b)(8)
requires an LSRH's governing body to consider the feasibility of incorporating
patient handling equipment or the physical space and construction design needed
to incorporate that equipment at a later date.
(F) Other regulations. The more stringent
standard, code or requirement shall apply when a difference in requirements for
construction exists.
(G) Exceeding
minimum requirements. Nothing in this subchapter shall be construed to prohibit
a better type of building construction, more exits, or otherwise safer
conditions than the minimum requirements specified in this
subchapter.
(H) Equivalency.
Nothing in this subchapter is intended to prevent the use of systems, methods,
or devices of equivalent or superior quality, strength, fire resistance,
effectiveness, durability, and safety to those prescribed by this subchapter,
providing technical documentation that demonstrates equivalency is submitted to
HHSC for approval.
(I) Freestanding
buildings (not for patient use). Separate freestanding buildings for nonpatient
use such as the heating plant, boiler plant, laundry, repair workshops, or
general storage may be of unprotected noncombustible construction, protected
noncombustible construction, or fire-resistive construction and be designed in
accordance with other occupancy classifications requirements listed in NFPA
101.
(J) Energy conservation. In
new construction and in major alterations and additions to existing buildings
and in new buildings, electrical and mechanical components shall be selected
for efficient utilization of energy. LSRH construction shall be in accordance
with the provisions of Texas Health and Safety Code Chapter 388 (relating to
Texas Building Energy Performance Standards).
(K) Heliports. Heliports located on LSRH
buildings or land used or intended to be used for landing and takeoff of
helicopters shall comply with National Fire Protection Association 418,
Standard for Heliports, 2011 edition.
(2) General detail and finish requirements.
Details and finishes in new construction projects, including additions and
alterations, shall be in compliance with this paragraph, with NFPA 101, Chapter
18, with local building codes, and with any specific detail and finish
requirements for the particular unit as contained in §
511.163 of this subchapter
(relating to Spatial Requirements).
(A)
General detail requirements.
(i) Fire safety.
Fire safety features, including compartmentation, means of egress, automatic
extinguishing systems, inspections, smoking regulations, and other details
relating to fire prevention and fire protection shall comply with §
511.161 of this subchapter
(relating to Requirements for Buildings in Which Existing Licensed Hospitals
Are Located), and NFPA 101, Chapter 18 requirements for hospitals. The Fire
Safety Evaluation System for Health Care Occupancies contained in the NFPA
101A, Alternative Approaches to Life Safety, 2010 edition, Chapter 3, shall not
be used in new building construction, renovations, or additions to existing
LSRHs.
(ii) Access to exits.
Corridors providing access to all patient, diagnostic, treatment, and patient
therapy rooms and exits shall be at least eight feet in clear and unobstructed
width, not less than seven feet six inches in height, and constructed in
accordance with requirements listed in NFPA 101 §18.3.6.
(iii) Corridors in other occupancies. Public
corridors in administrative and service areas that are designed to requirements
other than LSRH requirements and are the required means of egress from the LSRH
shall be not less than five feet in width.
(iv) Encroachment into the means of egress.
Items such as drinking fountains, telephone booths or stations, and vending
machines shall be so located as to not project into and restrict exit corridor
traffic or reduce the exit corridor width below the required minimum. Portable
equipment shall not be stored so as to project into and restrict exit corridor
traffic or reduce the exit corridor width below the required minimum.
(v) Doors in means of egress. All door leaves
in the means of egress shall be not less than 44 inches wide or as otherwise
permitted for hospitals by NFPA 101 §18.2.3.6.
(vi) Sliding doors. Horizontal sliding doors
serving an occupant load of fewer than 10 shall be permitted. The area served
by the door has no high hazard contents. The door is readily operable from
either side without special knowledge or effort. The force required to operate
the door in the direction of door travel is not more than 30 pounds per foot to
set the door in motion and is not more than 15 pounds per foot to close the
door or open in the minimum required width. The door assembly complies with any
required fire protection rating, and, where rated, is self-closing or automatic
closing. The sliding doors opening to the egress corridor doors shall have a
latch or other mechanism that ensures that the doors will not rebound into a
partially open position if forcefully closed. The sliding doors may have
breakaway provisions and shall be installed to resist passage of smoke. The
latching sliding panel shall have a minimum clear opening of 41.5 inches in the
fully open position. The fixed panels may have recessed tracks.
(vii) Control doors. Designs that include
cross-corridor control doors should be avoided. When unavoidable,
cross-corridor control doors shall consist of two 44-inch wide leaves that
swing in a direction opposite from the other, or of the double acting type.
Each door leaf shall be provided with a view window.
(viii) Emergency access. Rooms containing
bathtubs, showers, and water closets, intended for patient use shall be
provided with at least one door having hardware that will permit access from
the outside in any emergency. Door leaf width of such doors shall not be less
than 36 inches.
(ix) Obstruction of
corridors. All doors that swing towards the corridor must be recessed. Corridor
doors to rooms not subject to occupancy (any room that you can walk into and
close the door behind you is considered occupiable) may swing into the
corridor, provided that such doors comply with the requirements of NFPA 101
§7.2.1.4.4.
(x) Stair landing.
Doors shall not open immediately onto a stair without a landing. The landing
shall be 44 inches deep or have a depth at least equal to the door width,
whichever is greater.
(xi) Doors to
rooms subject to occupancy. All doors to rooms subject to occupancy shall be of
the swing type except that horizontal sliding doors complying with the
requirements of NFPA 101 §18.2.2.2.9 are permitted. Door leaves to rooms
subject to occupancy shall not be less than 36 inches wide.
(xii) Operable windows and exterior doors.
Windows that can be opened without tools or keys and outer doors without
automatic closing devices shall be provided with insect screens.
(xiii) Glazing. Glass doors, lights,
sidelights, borrowed lights, and windows located within 12 inches of a door
jamb or with a bottom-frame height of less than 18 inches and a top-frame
height of more than 36 inches above the finished floor that may be broken
accidentally by pedestrian traffic shall be glazed with safety glass or plastic
glazing material that will resist breaking and will not create dangerous
cutting edges when broken. Similar materials shall be used for wall openings in
activity areas such as recreation and exercise rooms, unless otherwise required
for fire safety. Safety glass, tempered, or plastic glazing materials shall be
used for shower doors and bath enclosures, interior windows and doors. Plastic
and similar materials used for glazing shall comply with the flame spread
ratings of NFPA 101 §18.3.3.
(xiv) Fire doors. All fire doors shall be
listed by an independent testing laboratory and shall meet the construction
requirements for fire doors in NFPA 80, Standard for Fire Doors and Fire
Windows, 2010 edition. Reference to a labeled door shall be construed to
include labeled frame and hardware.
(xv) Grab bars. Grab bars shall be provided
at patient toilets, showers and tubs. The bars shall be one and one-half inches
in diameter, shall have either one and one-fourth or one and one-half inches
clearance to walls, and shall have sufficient strength and anchorage to sustain
a concentrated vertical or horizontal load of 250 pounds. Grab bars are not
permitted at bathing and toilet fixtures in mental health and chemical
dependency units unless designed and installed to eliminate the possibility of
patients harming themselves. Grab bars intended for use by the disabled shall
also comply with Americans with Disabilities Act of 1990 (ADA)
requirements.
(xvi) Soap dishes.
Soap dishes shall be provided at all showers and bathtubs.
(xvii) Hand washing facilities. Location and
arrangement of fittings for hand washing facilities shall permit their proper
use and operation. Hand washing fixtures with hands-free operable controls
shall be provided within each workroom, examination, and treatment room.
Hands-free includes blade-type handles, and foot, knee, or sensor operated
controls. Particular care shall be given to the clearances required for
blade-type operating handles. Lavatories and hand washing facilities shall be
securely anchored to withstand an applied vertical load of not less than 250
pounds on the front of the fixture. In addition to the specific areas noted,
hand washing facilities shall be provided and conveniently located for staff
use throughout the LSRH where patient care contact occurs and services are
provided.
(xviii) Soap dispensers.
A liquid or foam soap dispenser shall be located at each hand washing
facility.
(xix) Alcohol-based hand
rubs. Alcohol-based hand rubs (ABHRs) are considered flammable. When used,
ABHRs shall meet the following requirements.
(I) The dispensers may be installed in a
corridor so long as the corridor width is six feet or greater. The dispensers
shall be installed at least four feet apart.
(II) The maximum individual dispenser fluid
capacity is 1.2 liters for dispensers in rooms, corridors, and areas open to
corridors, and 2.0 liters for dispensers in suites of rooms.
(III) The dispensers shall not be installed
over or directly adjacent to electrical outlets and switches.
(IV) Dispensers installed directly over
carpeted surfaces shall be permitted only in sprinklered smoke
compartments.
(V) Each smoke
compartment may contain a maximum aggregate of 10 gallons of ABHR solution in
dispensers and a maximum of five gallons in storage.
(xx) Hand drying. Provisions for hand drying
shall be included at all hand washing facilities except scrub sinks. There
shall be hot air dryers or individual paper or cloth units enclosed in such a
way as to provide protection against dust or soil and ensure single-unit
dispensing.
(xxi) Mirrors. Mirrors
shall not be installed at hand washing fixtures where asepsis control and
sanitation requirements would be lessened by hair combing. Mirrors may be
installed in patient toilet rooms, lockers, and public toilet rooms.
(xxii) Ceiling heights. The minimum ceiling
height shall be seven feet six inches with the following exceptions.
(I) Boiler rooms. Boiler rooms shall have
ceiling clearances not less than two feet six inches above the main boiler
header and connecting piping.
(II)
Rooms with ceiling-mounted equipment. Rooms containing ceiling-mounted
equipment shall have the ceiling height clearance increased to accommodate the
equipment or fixtures.
(III)
Overhead clearance. Suspended tracks, rails, pipes, signs, lights, door
closers, exit signs, and other fixtures that protrude into the path of normal
traffic shall not be less than six feet eight inches above the finished
floor.
(xxiii) Areas
producing impact noises. Recreation rooms, exercise rooms, and similar spaces
where impact noises may be generated shall not be located directly over patient
bed area or operating rooms unless special provisions are made to minimize
noise.
(xxiv) Noise reduction.
Noise reduction criteria in accordance with the Table 1 in §
511.169(a) of
this subchapter (relating to Tables) shall apply to partitions, floor, and
ceiling construction in patient areas.
(xxv) Rooms with heat-producing equipment.
Rooms containing heat-producing equipment such as heater rooms, laundries, etc.
shall be insulated and ventilated to prevent any occupied floor surface above
from exceeding a temperature differential of 10 degrees Fahrenheit above the
ambient room temperature.
(xxvi)
Chutes. Linen and refuse chutes shall comply with the requirements of NFPA 82,
Standard on Incinerators, Waste and Linen Handling Systems and Equipment, 2009
edition, and NFPA 101 §18.5.4.
(xxvii) Thresholds and expansion joint
covers. Thresholds and expansion joint covers shall be flush or not more than
one-half inch above the floor surface to facilitate the use of wheelchairs and
carts. Expansion and seismic joints shall be constructed to restrict the
passage of smoke and fire and shall be listed by a nationally recognized
testing laboratory.
(xxviii)
Housekeeping room.
(I) In addition to any
housekeeping rooms required in certain departments, sufficient housekeeping
rooms shall be provided throughout the LSRH as required to maintain a clean and
sanitary environment.
(II) Each
housekeeping room shall contain a floor receptor or service sink and storage
space for housekeeping equipment and supplies.
(B) General finish requirements.
(i) Cubicle curtains and draperies.
(I) Cubicle curtains, draperies, and other
hanging fabrics shall be noncombustible or flame retardant and shall pass both
the small scale and the large-scale tests of NFPA 701, Standard Methods of Fire
Tests for Flame-Resistant Textiles and Films, 2010 edition. Copies of
laboratory test reports for installed materials shall be submitted to HHSC at
the time of the final construction inspection.
(II) Cubicle curtains shall be provided to
assure patient privacy.
(ii) Flame spread, smoke development, and
noxious gases. Flame spread and smoke developed limitations of interior
finishes shall comply with Table 2 of §
511.169(b) of
this subchapter and NFPA 101 §10.2. The use of materials known to produce
large or concentrated amounts of noxious or toxic gases shall not be used in
exit accesses or in patient areas. Copies of laboratory test reports for
installed materials tested in accordance with NFPA 255, Standard Method of Test
of Surface Burning Characteristics of Building Materials, 2000 edition, and
NFPA 258, Standard Research Test Method for Determining Smoke Generation of
Solid Materials, 2001 edition, shall be provided.
(iii) Floor finishes. Flooring shall be easy
to clean and have wear resistance appropriate for the location involved. Floors
that are subject to traffic while wet (such as shower and bath areas, kitchens,
and similar work areas) shall have a nonslip surface. In all areas frequently
subject to wet cleaning methods, floor materials shall not be physically
affected by germicidal and cleaning solutions. The following are acceptable
floor finishes:
(I) painted
concrete;
(II) vinyl and vinyl
composition tiles and sheets;
(III)
monolithic or seamless flooring. Where required, seamless flooring shall be
impervious to water, coved and installed integral with the base, tightly sealed
to the wall, and without voids that can harbor insects or retain dirt
particles. The base shall not be less than six inches in height. Welded joint
flooring is acceptable;
(IV)
ceramic and quarry tile;
(V) wood
floors. Wood floors subject to frequent cleaning methods shall be avoided. When
wood floors are used, the floor shall be tightly sealed, without voids and the
joints shall be impervious to water;
(VI) carpet flooring. Carpeting installed in
patient care areas shall be treated to prevent bacterial and fungal
growth;
(VII) terrazzo;
and
(VIII) poured in place
floors.
(iv) Wall
finishes. Wall finishes shall be smooth, washable, moisture resistant, and
cleanable by standard housekeeping practices. Wall finishes shall comply with
requirements contained in Table 2 of §
511.169(b) of
this subchapter, and NFPA 101 §18.3.3.
(I) Wall finishes shall be water-resistant in
the immediate area of plumbing fixtures.
(II) Wall finishes subject to frequent wet
cleaning methods shall be impervious to water, tightly sealed, and without
voids.
(v) Floor, wall,
and ceiling penetrations. Floor, wall, and ceiling penetrations by pipes,
ducts, and conduits or any direct openings shall be tightly sealed to minimize
entry of dirt particles, rodents, and insects. Joints of structural elements
shall be similarly sealed.
(vi)
Ceiling types. Ceilings that are a part of a rated roof/ceiling assembly or a
floor/ceiling assembly shall be constructed of listed components and installed
in accordance with the listing. The following subclauses describe three types
of ceilings that are required in various areas of the LSRH.
(I) Ordinary ceilings. Ceilings such as
acoustical tiles installed in a metal grid that are dry cleanable with
equipment used in daily housekeeping activities such as dusters and vacuum
cleaners.
(II) Washable ceilings.
Ceilings that are made of washable, smooth, moisture impervious materials such
as painted lay-in gypsum wallboard or vinyl faced acoustic tile in a metal
grid.
(III) Monolithic ceilings.
Ceilings that are monolithic from wall to wall (painted solid gypsum
wallboard), smooth and without fissures, open joints, or crevices and with a
washable and moisture impervious finish.
(vii) Special construction. Special
conditions may require special wall and ceiling construction for security in
areas such as storage of controlled substances and areas where patients are
likely to attempt suicide or escape.
(viii) Flammable anesthetizing locations.
Flammable anesthetic locations in which flammable anesthetic agents are stored
or administered shall comply with Annex E of NFPA 99, Health Facilities Code,
2012 edition.
(ix) Materials
finishes. Materials known to produce noxious gases when burned shall not be
used for mattresses, upholstery, and wall finishes.
(x) Signage. A sign shall be posted at the
entrance to each toilet or restroom to identify the facility for public, staff,
or patient use. A sign is not required for patient room bathrooms.
(3) General mechanical
requirements. This paragraph contains common requirements for mechanical
systems; steam and hot and cold water systems; air conditioning, heating and
ventilating systems; plumbing fixtures; piping systems; and thermal and
acoustical insulation. An LSRH shall comply with the requirements of this
paragraph and any specific mechanical requirements for the particular unit of
the LSRH as described in §
511.163 of this subchapter.
(A) Equipment location. When mechanical
equipment is exposed to weather, it shall be weather protected or protected by
weatherproof construction.
(B)
Vibration isolation. Mechanical equipment shall be mounted on vibration
isolators as required to prevent unacceptable structure-borne vibration. Ducts,
pipes, etc. connected to mechanical equipment that is a source of vibration
shall be isolated from the equipment with vibration isolators.
(C) Performance and acceptance. Before
completion and acceptance of the facility, all mechanical systems shall be
tested, balanced, and operated to demonstrate to the design engineer or their
representative that the installation and performance of these systems conform
to the requirements of the plans and specifications.
(i) Material lists. On completion of the
contract, the owner shall be provided with parts lists and procurement
information with numbers and description for each piece of equipment.
(ii) Instructions. On completion of the
contract, the owner shall be provided with instructions in the operational use
of systems and equipment as required.
(D) Heating, ventilating and air conditioning
(HVAC) systems. All HVAC systems shall comply with and shall be installed in
accordance with the requirements of NFPA 90A, Standard for the Installation of
Air Conditioning and Ventilating Systems, 2012 edition, NFPA 99, Chapter 6, the
requirements contained in this subparagraph, and the specific requirements for
a particular unit in accordance with §
511.163 of this subchapter.
(i) General ventilation requirements. All
rooms and areas in the LSRH listed in Table 3 of §
511.169(c) of
this subchapter shall have provision for positive ventilation. Fans serving
exhaust systems shall be located at the discharge end and shall be conveniently
accessible for service. Exhaust systems may be combined, unless otherwise
noted, for efficient use of recovery devices required for energy conservation.
The ventilation rates shown in Table 3 of §
511.169(c) of
this subchapter shall be used only as minimum requirements since they do not
preclude the use of higher rates that may be appropriate. Supply air to the
building and exhaust air from the building shall be regulated to provide a
positive pressure within the building with respect to the exterior.
(I) Cost reduction methods. To reduce utility
costs, facility design may utilize energy conserving procedures including
recovery devices, variable air volume, load shedding, systems shutdown or
reduction of ventilation rates (when specifically permitted) in certain areas
when unoccupied. In no case shall patient care be jeopardized.
(II) Economizer cycle. Mechanical systems
shall be arranged to take advantage of outside air conditions by using an
economizer cycle when appropriate to reduce heating and cooling systems loads.
An LSRH may present to HHSC for consideration an innovative design that
provides for additional energy conservation while meeting the intent of this
section for acceptable patient care.
(III) Outside air intake locations. Outside
air intakes shall be located at least 25 feet from exhaust outlets of
ventilating systems, combustion equipment stacks, medical-surgical vacuum
systems, plumbing vents, or areas that may collect vehicular exhaust or other
noxious fumes. (Prevailing winds and proximity to other structures may require
more stringent requirements). Plumbing and vacuum vents that terminate five
feet above the level of the top of the air intake may be located as close as 10
feet.
(IV) Low air intake location
limit. The bottom of outside air intakes serving central systems shall be
located as high as practical but at least six feet above ground level, or if
installed above the roof, three feet above the roof level.
(V) Contaminated air exhaust outlets. Exhaust
outlets from areas (kitchen hoods, etc.) that exhaust contaminated air shall be
above the roof and be arranged to exhaust upward unless the air has been
treated by an appropriate means where sidewall exhaust will be allowed.
Ethylene oxide sterilizers shall be terminated above the roof and be arranged
to exhaust upward. Each patient room bathroom shall be exhausted continuously
to the exterior in accordance with Table 3 of §
511.169(c) of
this subchapter.
(VI) Directional
air flow. Ventilation systems shall be designed and balanced to provide
directional flow as shown in Table 3 of §
511.169(c) of
this subchapter. For reductions and shutdown of ventilation systems when a room
is unoccupied, the provisions in Note 4 of Table 3 of §
511.169(c) of
this subchapter shall be followed.
(VII) Areas requiring fully ducted systems.
Fully ducted supply, return and exhaust air for HVAC systems shall be provided
for all critical care areas, sensitive care areas, all patient care areas, all
areas requiring a sterile regimen, storage rooms, food preparation areas, and
where required for fire safety purposes. Combination systems, utilizing both
ducts and plenums for movement of air in these areas shall not be
permitted.
(VIII) Ventilation
start-up requirements. Air handling systems shall not be started or operated
without the filters installed in place. This includes the 90 percent and 99.97
percent efficiency filters where required. Ducts shall be cleaned thoroughly
and throughout by a certified air duct cleaning contractor when the air
handling systems have been operating without the required filters in place.
When ducts are determined to be dirty or dusty, HHSC will require a written
report assuring cleanliness of duct and clean air quality.
(IX) Humidifier location. When duct
humidifiers are located upstream of the final filters, they shall be located at
least 15 feet from the filters. Ductwork with duct-mounted humidifiers shall be
provided with a means of removing water accumulation. An adjustable high-limit
humidistat shall be located downstream of the humidifier to reduce the
potential of condensation inside the duct. All duct take-offs should be
sufficiently downstream of the humidifier to ensure complete moisture
absorption. Reservoir-type water spray or evaporative pan humidifiers shall not
be used.
(ii) Filtration
requirements. All central air handling systems serving patient care areas,
including corridors, shall be equipped with filters having efficiencies equal
to, or greater than, those specified in Table 4 of §
511.169(d) of
this subchapter. Filter efficiencies shall be average efficiencies tested in
accordance with American Society of Heating, Refrigerating, and
Air-Conditioning Engineers (ASHRAE), Inc., Standard 52.2, 1999 edition, Method
of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by
Particle Size. All joints between filter segments, and between filter segments
and the enclosing ductwork, shall have gaskets and seals to provide a positive
seal against air leakage. Air handlers serving more than one room shall be
considered as central air handlers.
(I)
Filtration requirements for air handling units serving single rooms requiring
asepsis control. Dedicated air handlers serving only one room where asepsis
control is required, including operating rooms and special procedure rooms
shall be equipped with filters having efficiencies equal to, or greater than,
those specified for patient care areas in Table 4 of §
511.169(d) of
this subchapter.
(II) Filtration
requirements for air handling units serving other single rooms. Dedicated air
handlers serving all other single rooms shall be equipped with nominal filters
installed at the return air system.
(III) Location of multiple filters. Where two
filter beds are required by Table 4 of §
511.169(d) of
this subchapter, filter bed number one shall be located upstream of the air
conditioning equipment, and filter bed number two shall be downstream of the
supply air blowers and cooling and heating coils.
(IV) Location of single filters. Where only
one filter bed is required by Table 4 of §
511.169(d) of
this subchapter, it shall be located upstream of the supply fan. Filter frames
shall be durable and constructed to provide an airtight fit with the enclosing
ductwork.
(V) Pressure monitoring
devices. A manometer or draft gauge shall be installed across each filter bed
having a required efficiency of 75 percent or more including hoods requiring
high efficiency particulate air (HEPA) filters.
(iii) Thermal and acoustical insulation for
air handling systems. Asbestos insulation shall not be used.
(I) Thermal duct insulation. Air ducts and
casings with outside surface temperature below ambient dew point or temperature
above 80 degrees Fahrenheit shall be provided with thermal
insulation.
(II) Insulation in air
plenums and ducts. Linings in air ducts and equipment shall meet the Erosion
Test Method described in Underwriters Laboratories (UL), Inc., Standard Number
181 (relating to Factory-Made Duct Materials and Air Duct Connectors), April 4,
1996 edition.
(III) Insulation
flame spread and smoke developed ratings. Interior and exterior insulation,
including finishes and adhesives on the exterior surfaces of ducts and
equipment, shall have a flame spread rating of 25 or less and a smoke developed
rating of 50 or less as required by NFPA 90A Chapters 4 and 5.
(IV) Linings and acoustical traps. Duct
lining and acoustical traps exposed to air movement shall not be used in ducts
serving critical care areas. This requirement shall not apply to mixing boxes
and acoustical traps that have approved nonabrasive coverings over such
linings.
(V) Frangible insulation.
Insulation of soft and spray-on types shall not be used where it is subject to
air currents or mechanical erosion or where loose particles may create a
maintenance problem.
(VI) Existing
duct linings. Internal linings shall not be used in ducts, terminal boxes, or
other air system components supplying operating rooms, delivery rooms, birthing
rooms, labor rooms, recovery rooms, nurseries, trauma rooms, isolation rooms,
and intensive care units unless terminal filters of at least 90 percent
efficiency are installed downstream of linings.
(iv) Ventilation for anesthetizing locations.
Ventilation for anesthetizing locations, as defined in NFPA 99 §3.3, shall
comply with NFPA 99 §13.4.1.2, and any specific ventilation requirements
for the particular unit in accordance with §
511.163 of this subchapter.
(I) Smoke removal systems for windowless
anesthetizing locations. Smoke removal systems shall be provided in all
windowless anesthetizing locations in accordance with NFPA 99
§6.4.1.2.
(II) Smoke removal
systems for surgical suites. Smoke removal systems shall be provided in all
surgical suites in accordance with NFPA 99 §6.4.1.3.
(III) Smoke exhaust grilles. Exhaust grilles
for smoke evacuation systems shall be ceiling-mounted or wall-mounted within 12
inches of the ceiling.
(v) Location of return and exhaust air
devices. The bottoms of wall-mounted return and exhaust air openings shall be
at least four inches above the floor. Return air openings located less than six
inches above the floor shall be provided with nominal filters. All exhaust air
openings and return air openings located higher than six inches but less than
seven feet above the floor shall be protected with grilles or screens having
openings through which a one-half inch sphere will not pass.
(vi) Ray protection. Ducts that penetrate
construction intended for X-ray or other ray protection shall not impair the
effectiveness of the protection.
(vii) Fire damper requirements. Fire dampers
shall be located and installed in all ducts at the point of penetration of a
required two-hour or higher fire rated wall or floor in accordance with the
requirements of NFPA 101 §18.5.2.
(viii) Smoke damper requirements. Smoke
dampers shall be located and installed in accordance with the requirements of
NFPA 101 §18.3.7.3 and NFPA 90A Chapter 5.
(I) Fail-safe installation. Smoke dampers
shall close on activation of the fire alarm system by smoke detectors installed
and located as required by NFPA 72, National Fire Alarm Code, 2010 edition,
Chapter 8; NFPA 90A Chapter 6; and NFPA 101 §18.3.7; the fire sprinkler
system; and on loss of power. Smoke dampers shall not close by fan shutdown
alone unless it is a part of an engineered smoke removal system.
(II) Interconnection of air handling fans and
smoke dampers. Air handling fans and smoke damper controls may be
interconnected so that closing of smoke dampers will not damage the
ducts.
(III) Frangible devices. Use
of frangible devices for shutting smoke dampers is not permitted.
(ix) Acceptable damper assemblies.
Only fire damper and smoke damper assemblies integral with sleeves and listed
for the intended purpose is acceptable.
(x) Duct access doors. Unobstructed access to
duct openings in accordance with NFPA 90A §4.3.4 shall be provided in
ducts within reach and sight of every fire damper, smoke damper, and smoke
detector. Each opening shall be protected by an internally insulated door that
shall be labeled externally to indicate the fire protection device located
within.
(xi) Restarting controls.
Controls for restarting fans may be installed for convenient fire department
use to assist in evacuation of smoke after a fire is controlled, provided
provisions are made to avoid possible damage to the system because of closed
dampers. To accomplish this, smoke dampers shall be equipped with remote
control devices.
(xii) Make-up air.
If air supply requirements in Table 3 of §
511.169(c) of
this subchapter do not provide sufficient air for use by exhaust hoods and
safety cabinets, filtered make-up air shall be ducted to maintain the required
air flow direction in that room. Make-up systems for hoods shall be arranged to
minimize short circuiting of air and to avoid reduction in air velocity at the
point of contaminant capture.
(xiii) Isolation room exhaust. An isolation
room exhaust shall be a dedicated system that exhausts all air continuously to
the exterior in accordance with Table 3 of §
511.169(c) of
this subchapter. Multiple isolation rooms may be interconnected to the same
exhaust system.
(4) General piping systems and plumbing
fixture requirements. All piping systems and plumbing fixtures shall be
designed and installed in accordance with the requirements of the National
Standard Plumbing Code Illustrated published by the National Association of
Plumbing-Heating-Cooling Contractors (PHCC), 2003 edition, and this paragraph.
(A) Piping systems.
(i) Water supply systems. Water service pipe
to point of entrance to the building shall be brass pipe, copper tube (not less
than type M when buried directly), copper pipe, cast iron water pipe,
galvanized steel pipe, or approved plastic pipe. Domestic water distribution
system piping within buildings shall be brass pipe, copper pipe, copper tube,
or galvanized steel pipe. Piping systems shall be designed to supply water at
sufficient pressure to operate all fixtures and equipment during maximum
demand.
(I) Valves. Each water service main,
branch main, riser, and branch to a group of fixtures shall be equipped with
accessible and readily identifiable shutoff valves. Stop valves shall be
provided at each fixture.
(II)
Backflow preventers. Backflow preventers (vacuum breakers) shall be installed
on hose bibbs, laboratory sinks, janitor sinks, bedpan-flushing attachments,
autopsy tables, and on all other fixtures to which hoses or tubing can be
attached.
(III) Flushing valves.
Flush valves installed on plumbing fixtures shall be of a quiet operating type,
equipped with silencers.
(IV)
Capacity of water heating equipment. Water heating equipment shall have
sufficient capacity to supply water for clinical, dietary and laundry use at
the temperatures and amounts specified in Table 5 of §
511.169(e) of
this subchapter.
(V) Water
temperature measurements. Water temperatures shall be measured at hot water
point of use or at the inlet to processing equipment.
(VI) Water storage tanks. Any domestic water
storage tanks shall be fabricated of corrosion-resistant metal or lined with
noncorrosive material. When potable water storage tanks (hot and cold) are
used, the water shall be used and replenished. Water shall not be stored in
tanks for future use unless the water is tested weekly for contaminates and
bacteria.
(VII) Hot water
distribution. Water distribution systems shall be arranged to provide hot water
at each hot water outlet at all times.
(VIII) Purified water supply system. Purified
water distribution system piping shall be task specific and include
Polypropylene (PP), Polyvinylidene fluoride (PVDF) or Polyvinyl Chloride (PVC)
pipe. Final installed purified water system piping assemblies shall be UL
approved and fully comply with applicable American Society for Testing and
Materials (ASTM) Fire Resistant/Smoke Density requirements.
(IX) Dead-end piping. Dead-end piping (risers
with no flow, branches with no fixture) shall not be installed. In any
renovation work, dead-end piping shall be removed. Empty risers, mains and
branches installed for future use are permitted.
(ii) Fire sprinkler systems. Fire sprinkler
systems shall be provided in an LSRH as required by NFPA 101 §18.3.5. All
fire sprinkler systems shall be designed, installed, and maintained in
accordance with the requirements of NFPA 13, and shall be certified as required
by §
511.168(c)(1)(C)
of this subchapter (relating to Construction, Inspections, and Approval of
Project).
(iii) Nonflammable
medical gas and clinical vacuum systems. Nonflammable medical gas and clinical
vacuum system installations shall be designed, installed, and certified in
accordance with the requirements of NFPA 99 §5.1 for Level I systems and
the requirements of this clause.
(I) Outlets.
Nonflammable medical gas and clinical vacuum outlets shall be provided in
accordance with Table 6 of §
511.169(f) of
this subchapter.
(II) Installer
qualifications. All installations of the medical gas piping systems shall be
done only by, or under the direct supervision of, a holder of a master plumber
license or a journeyman plumber license with a medical gas piping installation
endorsement issued by the Texas State Board of Plumbing Examiners.
(III) Installer tests. Prior to closing of
walls, the installer shall perform an initial pressure test, a blowdown test, a
secondary pressure test, a cross-connection test, and a purge of the piping
system as required by NFPA 99.
(IV)
Qualifications for conducting verification tests and inspections. Verification
testing shall be performed and inspected by a party, other than the installer,
installing contractor, or material vendor. Testing shall be conducted by a
registered medical gas system verifier and technically competent and
experienced in the field of medical gas and vacuum pipeline testing and meeting
the requirements of the American Society of Safety Engineers (ASSE) Personnel
Standard 6030, Professional Qualifications Standard for Medical Gas
Systems.
(V) Verification tests. On
completion of the installer inspections and tests and after closing of walls,
verification tests of the medical gas piping systems, the warning system, and
the gas supply source shall be conducted. The verification tests shall include
a cross-connection test, valve test, flow test, piping purge test, piping
purity test, final tie-in test, operational pressure tests, and medical gas
concentration test.
(VI)
Verification test requirements. Verification tests of the medical gas piping
system and the warning system shall be performed on all new piped medical gas
systems, additions, renovations, or repaired portions of an existing system.
All systems that are breached and components that are added, renovated, or
replaced shall be inspected and appropriately tested. The breached portions of
the systems subject to inspection and testing shall be all of the new and
existing components in the immediate zone or area located upstream of the point
or area of intrusion and downstream to the end of the system or a properly
installed isolation valve.
(VII)
Warning system verification tests. Verification tests of piped medical gas
systems shall include tests of the source alarms and monitoring safeguards,
master alarm systems, and the area alarm systems.
(VIII) Source equipment verification tests.
Source equipment verification tests shall include medical gas supply sources
(bulk and manifold) and the compressed air source systems (compressors, dryers,
filters, and regulators).
(IX) LSRH
responsibility. Before new piped medical gas systems, additions, renovations,
or repaired portions of an existing system are put into use, the LSRH is
responsible for ensuring the gas delivered at the outlet is the gas shown on
the outlet label and the proper connecting fittings are checked against their
labels.
(X) Written certification.
On successful completion of all verification tests, written certification for
affected piped medical gas systems and piped medical vacuum systems including
the supply sources and warning systems shall be provided by a party technically
competent and experienced in the field of medical gas pipeline testing stating
the provisions of NFPA 99 have been adhered to and systems integrity has been
achieved. The written certification shall be submitted directly to the LSRH and
the installer. The LSRH shall forward a copy to HHSC.
(XI) Documentation of medical gas and
clinical vacuum outlets. The same party certifying the piped medical gas
systems shall submit to HHSC documentation of the installed, modified, extended
or repaired medical gas piping system. The number and type of medical gas
outlets (oxygen, vacuum, medical air, nitrogen, nitrous oxide, etc.) shall be
documented and arranged tabularly by room numbers and room types.
(iv) Medical gas storage
facilities. Main storage of medical gases may be outside or inside the LSRH in
accordance with NFPA 99 §5.1. Provision shall be made for additional
separate storage of reserve gas cylinders necessary to complete at least one
day's procedures.
(v) Multiple gas
outlets on one medical gas outlet. Y-connections, "twinning," or other similar
devices shall not be used on any medical gas outlet.
(vi) Waste anesthetic gas disposal (WAGD)
systems. Each space routinely used for administering inhalation anesthesia
shall be provided with a WAGD system as required by NFPA 99
§5.1.3.7.
(vii) Steam and hot
water systems.
(I) Boilers. Boilers shall have
the capacity, based on the net ratings as published in the I-B-R Ratings Book
for Boilers, Baseboard Radiation and Finned Tube (commercial) by the Hydronics
Institute Division of Gas Appliance Manufacturers Association, to supply the
normal requirements of all systems and equipment. The number and arrangement of
boilers shall be such that, when one boiler breaks down or routine maintenance
requires that one boiler be temporarily taken out of service, the capacity of
the remaining boiler or boilers shall be sufficient to provide hot water
service for clinical, dietary, and patient use, steam for sterilization and
dietary purposes, and heating for operating, emergency, recovery, treatment,
and general patient care rooms. However, reserve capacity for space heating of
noncritical care areas (e.g., general patient care rooms and administrative
areas) is not required in geographical areas where a design dry bulb
temperature equals 25 degrees Fahrenheit or higher as based on the 99 percent
design value shown in the Handbook of Fundamentals, 2005 edition, published by
ASHRAE, Inc.
(II) Boiler
accessories. Boiler feed pumps, heating circulating pumps, condensate return
pumps, and fuel oil pumps shall be connected and installed to provide normal
and standby service.
(III) Valves.
Supply and return mains and risers of cooling, heating, and process steam
systems shall be valved to isolate the various sections of each system. Each
piece of equipment shall be valved at the supply and return ends except that
vacuum condensate returns need not be valved at each piece of
equipment.
(IV) Hot water
distribution systems. Hot water distribution systems for patient care areas
shall be under constant recirculation to provide continuous hot water at each
hot water outlet. Nonrecirculated fixtures branch piping shall not exceed 25
feet in length. Water temperature is measured at the point of use or inlet to
the equipment. Tankless water system may be used at point of use.
(V) Domestic hot water system. The domestic
hot water system shall make provisions to limit the amount of Legionella
bacteria and opportunistic waterborne pathogens.
(viii) Drainage systems.
(I) Above ground piping. Soil stacks, drains,
vents, waste lines, and leaders installed above ground within buildings shall
be drain-waste-vent (DWV) weight or heavier and shall be copper pipe, copper
tube, cast iron pipe, or galvanized iron pipe.
(II) Underground piping. All underground
building drains shall be cast iron soil pipe, hard temper copper tube (DWV or
heavier), acrylonitrile-butodiene-styrene (ABS) plastic pipe (DWV Schedule 40
or heavier), polyvinyl chloride (PVC) plastic pipe (DWV Schedule 40 or
heavier), or extra strength vitrified clay pipe (VCP) with compression joints
or couplings with at least 12 inches of earth cover.
(III) Drains for chemical wastes. Separate
drainage systems for chemical wastes (acids and other corrosive materials)
shall be provided. Materials acceptable for chemical waste drainage systems
shall include chemically resistant glass pipe, high silicone content cast iron
pipe, VCP, plastic pipe, or plastic lined pipe.
(ix) Thermal insulation for piping systems
and equipment. Insulation shall be provided for the following:
(I) boilers, smoke breeching, and
stacks;
(II) steam supply and
condensate return piping;
(III) hot
water piping and all hot water heaters, generators, converters, and storage
tanks;
(IV) chilled water,
refrigerant, other process piping, equipment operating with fluid temperatures
below ambient dew point, and water supply and drainage piping on which
condensation may occur. Insulation on cold surfaces shall include an exterior
vapor barrier; and
(V) other
piping, ducts, and equipment as necessary to maintain the efficiency of the
system.
(x) Pipe and
equipment insulation rating. Flame spread shall not exceed 25 and smoke
development rating shall not exceed 150 for pipe insulation as determined by an
independent testing laboratory in accordance with NFPA 255, Standard Method of
Test of Surface Burning Characteristics of Building Materials, 2000 edition.
Smoke development rating for pipe insulation located in environmental air areas
shall not exceed 50.
(xi) Asbestos
insulation. Asbestos insulation shall not be used.
(B) Plumbing fixtures. Plumbing fixtures
shall be made of nonabsorptive acid-resistant materials and shall comply with
the recommendations of the National Standard Plumbing Code and this paragraph.
(i) Sink and lavatory controls. All fixtures
used by medical and nursing staff and all lavatories used by patients and food
handlers shall be trimmed with valves that can be operated without the use of
hands. Blade handles used for this purpose shall not be less than four inches
in length. Single lever or wrist blade devices may be used.
(ii) Clinical sink traps. Clinical sinks
shall have an integral trap in which the upper portion of a visible trap seal
provides a water surface.
(iii)
Sinks for disposal of plaster of paris. Sinks used for the disposal of plaster
of paris shall have a plaster trap.
(iv) Back-flow or siphoning. All plumbing
fixtures and equipment shall be designed and installed to prevent the back-flow
or back-siphonage of any material into the water supply. The over-the-rim type
water inlet shall be used wherever possible. Vacuum-breaking devices shall be
properly installed when an over-the-rim type water inlet cannot be
utilized.
(v) Drinking fountain.
Each drinking fountain shall be designed so that the water issues at an angle
from the vertical, the end of the water orifice is above the rim of the bowl,
and a guard is located over the orifice to protect it from lip
contamination.
(vi) Sterilizing
equipment. All sterilizing equipment shall be designed and installed to prevent
not only the contamination of the water supply but also the entrance of
contaminating materials into the sterilizing units.
(vii) Hose attachment. No hose shall be
affixed to any faucet if the end of the hose can become submerged in
contaminated liquid unless the faucet is equipped with an approved, properly
installed vacuum breaker.
(viii)
Bedpan washers and sterilizers. Bedpan washers and sterilizers shall be
designed and installed so that both hot and cold water inlets shall be
protected against back-siphonage at maximum water level.
(ix) Flood level rim clearance. The water
supply spout for lavatories and sinks required in patient care areas shall be
mounted so that its discharge point is a minimum of five inches above the rim
of the fixture.
(x) Scrub sink
controls. Scrub sinks and lavatories used for scrubbing in procedure rooms
shall be trimmed with foot, knee, or ultrasonic controls. Single lever wrist
blades are not acceptable at scrub sinks.
(xi) Floor drains or floor sinks. Where floor
drains or floor sinks are installed, they shall be of a type that can be easily
cleaned by removal of the cover. Removable stainless steel mesh shall be
provided in addition to grilled drain cover to prevent entry of large particles
of waste that might cause stoppages.
(xii) Under-counter piping. Under-counter
piping and above floor drains shall be arranged (raised) so as not to interfere
with cleaning of floor below the equipment.
(xiii) Ice machines. All ice-making machines
used for human consumption shall be of the self-dispensing type. Copper tubing
shall be provided for supply connections to ice machines.
(xiv) Food disposal units. A food disposal
unit shall only be permitted in the dietary department in accordance with
§
511.163(d) of
this subchapter.
(5) General electrical requirements. This
paragraph contains common electrical requirements. The LSRH shall comply with
the requirements of this paragraph and with any specific electrical
requirements for the particular unit of the LSRH in accordance with §
511.163 of this subchapter.
(A) Electrical installations. All new
electrical material and equipment, including conductors, controls, and
signaling devices, shall be installed in compliance with applicable sections of
NFPA 70, National Electrical Code, 2011 edition, and NFPA 99 and as necessary
to provide a complete electrical system. Electrical systems and components
shall be listed by nationally recognized listing agencies as complying with
available standards and shall be installed in accordance with the listings and
manufacturers' instructions.
(i) All fixtures,
switches, sockets, and other pieces of apparatus shall be maintained in a safe
and working condition.
(ii)
Extension cords and cables shall not be used for permanent wiring.
(iii) All electrical heating devices shall be
equipped with a pilot light to indicate when the device is in service, unless
equipped with a temperature limiting device integral with the heater.
(iv) All equipment, fixtures, and appliances
shall be properly grounded in accordance with NFPA 70.
(v) Under-counter receptacles and conduits
shall be arranged (raised) to not interfere with cleaning of floor below the
equipment.
(B)
Installation testing and certification.
(i)
Installation testing. The electrical installations, including alarm, nurses
calling system and communication systems, shall be tested to demonstrate that
equipment installation and operation is appropriate and functional.
(ii) Grounding system testing. The grounding
system shall be tested as described in NFPA 99 4.3.3, for patient care areas in
new or renovated work. A qualified electrician or their qualified electrical
testing agent shall perform the testing. The electrical contractor shall
provide a letter stating the grounding system has been tested in accordance
with NFPA 99, the testing device use complies with NFPA 99, and whether the
grounding system passed the test. The qualified electrical contractor or their
designated qualified electrical testing agent shall sign the letter, certifying
the system has been tested and the results of the test are indicated.
(C) Electrical safeguards.
Shielded isolation transformers, voltage regulators, filters, surge
suppressors, and other safeguards shall be provided as required where power
line disturbances are likely to affect fire alarm components, data processing,
equipment used for treatment, and automated laboratory diagnostic
equipment.
(D) Services and
switchboards. Electrical service and switchboards serving the required LSRH
components shall be installed above the designated 100-year flood plain. Main
switchboards shall be located in separate rooms, separated from adjacent areas
with one-hour fire rated enclosures containing only electrical switchgear and
distribution panels and shall be accessible to authorized persons only. These
rooms shall be ventilated to provide an environment free of corrosive or
explosive fumes and gases, or any flammable and combustible materials.
Switchboards shall be located convenient for use and readily accessible for
maintenance as required by NFPA 70 Article 384. Overload protective devices
shall operate properly in ambient temperatures.
(E) Panelboards. Panelboards serving normal
lighting and appliance circuits shall be located on the same floor as the
circuits they serve. Panelboards serving critical branch emergency circuits
shall be located on each floor that has major users (operating rooms, emergency
department, etc.) and may also serve the floor above and the floor below.
Panelboards serving life safety branch circuits may serve three floors, the
floor where the panelboard is located and the floors above and below.
(F) Wiring. All conductors for controls,
equipment, lighting and power operating at 100 volts or higher shall be
installed in accordance with the requirements of NFPA 70 Article 517. All
surface mounted wiring operating at less than 100 volts shall be protected from
mechanical injury with metal raceways to a height of seven feet above the
floor. Conduits and cables shall be supported in accordance with NFPA 70
Article 300.
(G) Lighting.
(i) Lighting intensity for staff and patient
needs shall comply with guidelines for health care facilities set forth in the
Illuminating Engineering Society of North America (IESNA) Handbook, 2000
edition, published by the IESNA.
(I)
Consideration should be given to controlling intensity and wavelength to
prevent harm to the patient's eyes (i.e., cataracts due to ultraviolet
light).
(II) Approaches to
buildings and parking lots shall be illuminated. All rooms including
storerooms, electrical and mechanical equipment rooms, and all attics shall
have sufficient artificial lighting so all parts of these spaces are clearly
visible.
(III) Consideration should
be given to the special needs of the elderly. Excessive contrast in lighting
levels that makes effective sight adaptation difficult shall be
minimized.
(ii) Means of
egress and exit sign lighting intensity shall comply with NFPA 101
§§7.8 - 7.10.
(iii)
Electric lamps that may be subject to breakage or that are installed in
fixtures in confined locations when near woodwork, paper, clothing, or other
combustible materials, shall be protected by wire guards, or plastic
shields.
(iv) Ceiling-mounted
surgical and examination light fixtures shall be suspended from rigid support
structures mounted above the ceiling.
(H) Receptacles. Only listed hospital grade
single-grounding or duplex-grounding receptacles shall be used in all patient
care areas. This does not apply to special purpose receptacles.
(i) Installations of multiple-ganged
receptacles shall not be permitted in patient care areas.
(ii) Electrical outlets powered from the
critical branch shall be provided in all patient care, procedure and treatment
locations in accordance with NFPA 99 §4.4.2.2.2.3. At least one receptacle
at each patient treatment or procedure location shall be powered from the
normal power panel.
(iii)
Replacement of malfunctioning receptacles and installation of new receptacles
powered from the critical branch in existing facilities shall be accomplished
with receptacles of the same distinct color as the existing
receptacles.
(iv) In locations
where mobile X-ray or other equipment requiring special electrical
configuration is used, the additional receptacles shall be distinctively marked
for the special use.
(v) Each
receptacle shall be grounded to the reference grounding point by means of a
green insulated copper equipment grounding conductor.
(vi) All critical care area receptacles shall
be identified. The face plate for the receptacle or receptacles shall have a
nonremovable label or be engraved indicating the panel and circuit
number.
(I) Equipment.
(i) Equipment required for safe operation of
the LSRH shall be powered from the equipment system in accordance with the
requirements contained in NFPA 99 §4.4.2.2.3.
(ii) Boiler accessories including feed pumps,
heat-circulating pumps, condensate return pumps, fuel oil pumps, and waste heat
boilers shall be connected and installed to provide both normal and standby
service.
(iii) Laser equipment
shall be installed according to manufacturer recommendations and shall be
registered with the Texas Department of State Health Services Radiation Control
Program.
(J) Ground fault
circuit interrupters (GFCI). GFCI receptacles shall be provided for all general
use receptacles located within three feet of a wash basin or sink. When GFCI
receptacles are used, they shall be connected to not affect other devices
connected to the circuit in the event of a trip. Receptacles connected to the
critical branch that may be used for equipment that should not be interrupted
do not have to be GFCI protected. Receptacles in wet locations, as defined by
NFPA 70 §517.20 and §517.21, shall be GFCI protected regardless of
the branch of the electrical system serving the receptacle.
(K) Grounding requirements. In areas such as
a critical care unit where a patient may be treated with an internal probe or
catheter connected to the heart, the ground system shall comply with applicable
sections of NFPA 99 and NFPA 70.
(L) Nurses calling systems. Three different
types of nurses calling systems are required to be installed in an LSRH: a
nurses regular calling system; a nurses emergency calling system; and a staff
emergency assistance calling system. The LSRH shall comply with the
requirements of this subparagraph in addition to any specific requirements for
nurses calling systems for the particular unit of the LSRH in accordance with
§511.163 and Table 7 of §
511.169(g) of
this subchapter. When required in this subparagraph, when a colored dome light
lamp or particular combination of colored lamps is used for only one type of
call, a distinct visible signal shall be (used or provided). Different flash
rates do not meet this requirement.
(i) A
nurses regular calling system is intended for routine communication between
each patient and the nursing staff. Activation of the system at a patient's
regular calling station will sound a repeating (every 20 seconds or less)
distinct audible signal at the nurse station, indicate type and location of
call on the system monitor, and activate a distinct visible signal in the
corridor at the patient suites door. In multi-corridor nursing units,
additional visible signals shall be installed at corridor intersections. The
audible signal shall be canceled and two-way voice communication between the
patient room and the nursing staff shall be established at the unit's nursing
station when the call is answered by the nursing staff. The visible signal or
signals in the corridor shall be canceled upon termination of the call. Calls
shall activate visible signals in accordance with Table 7 of §
511.169(g) of
this subchapter. An alarm shall activate at the nurse station when the call
cable is unplugged.
(ii) A nurses
emergency calling system shall be installed in all toilets used by patients to
summon nursing staff in an emergency. Activation of the system shall sound a
repeating (every 5 seconds or less) a distinct audible signal at the nurse
station, indicate type and location of call on the system monitor, and activate
a distinct visible signal in the corridor at the patient suites door. In
multi-corridor nursing units, additional visible signals shall be installed at
corridor intersections. The visible and audible signals shall be cancelable
only at the patient calling station. Calls shall activate visible signals in
accordance with Table 7 of §
511.169(g) of
this subchapter. When conveniently located and accessible from both the bathing
and toilet fixtures, one emergency call station may serve one bathroom. A
nurses emergency call system shall be accessible to a collapsed patient lying
on the floor. Inclusion of a pull cord extending to within six inches of the
floor will satisfy this requirement.
(iii) A staff emergency assistance calling
system (code blue) is intended to be used by staff to summon additional help in
an emergency. In open suites, an emergency assistant call system device shall
be located at the head of each patient station and in each individual room. The
emergency assistance calling device can be shared between two patient stations
if conveniently located. Activation of the system will sound a distinct audible
signal at the nursing unit's nurse station or at a staffed control station of a
suite, department or unit, indicate type and location of call on the system
monitor and activate a distinct visible signal in the corridor at the patient
suites door. In multi-corridor nursing units, additional visible signals shall
be installed at corridor intersections. Calls shall activate audible and
visible signals in accordance with Table 7 of §
511.169(g) of
this subchapter. A visible system shall clearly define the alarm location to a
continuously staffed back up area (other than the nurse station or an
administrative center) from which assistance can be summoned. Alternatively,
back up may be provided by automatic annunciation from the staff emergency
assistance calling system through wireless phones or pagers. The system shall
have voice communication capability so that the type of emergency or help
required may be specified between the point of alarm and the unit's nurse
station.
(M) Emergency
electric service. A type I essential electrical system shall be provided in
each LSRH in accordance with requirements of NFPA 99; NFPA 101; and NFPA 110,
Standard for Emergency and Standby Power Systems, 2010 edition.
(i) When the emergency and standby power
systems require a fuel source with tank, the fuel storage capacity tank shall
have enough fuel for a 24-hour period.
(ii) When a vapor liquefied petroleum gas
(LPG) systems (natural gas) system is used, the 24-hour fuel capacity on-site
is not required. The vapor withdrawal LPG system shall require a dedicated fuel
supply.
(iii) When the emergency
generator or generators and electrical transformer or transformers are located
within the same area, they shall be located at least 10 feet apart.
(N) Fire alarm system. A fire
alarm system that complies with NFPA 101 §18.3.4, and with NFPA 72 Chapter
6 requirements shall be provided in each LSRH. The required fire alarm system
components are as follows.
(i) A fire alarm
control panel (FACP) shall be installed at a continuously attended (24 hour)
location. A remote fire alarm annunciator listed for fire alarm service and
installed at a continuously attended location and is capable of indicating both
visual and audible alarm, trouble and supervisory signals in accordance with
the requirements of NFPA 72 may be substituted for the FACP.
(ii) Manual fire alarm pull stations shall be
installed in accordance with NFPA 101 §18.3.4.
(iii) Smoke detectors for door release
service shall be installed on the ceiling at each door opening in the smoke
partition in accordance with NFPA 72 §6.15.6, where the doors are held
open with electromagnetic devices conforming with NFPA 101
§18.2.2.6.
(iv)
Ceiling-mounted smoke detector or detectors shall be installed in room
containing the FACP when this room is not attended continuously by staff as
required by NFPA 72 §4.4.5.
(v) Smoke detectors shall be installed in air
ducts in accordance with NFPA 72 §5.14.4.2 and §5.14.5 and NFPA 90A
§6.4.2.
(vi) Smoke detectors
shall be installed in return air ducts in accordance with requirements of NFPA
72 §5.14.4.2.2 and §5.14.5 and NFPA 90A §6.4.2.2.
(vii) Fire sprinkler system water flow
switches shall be installed in accordance with requirements of NFPA 101
§9.6.2; NFPA 13 §6.9; and NFPA 72 §8.5.3.3.3.4.
(viii) Sprinkler system valve supervisory
switches shall be installed in accordance with the requirements of NFPA 72
§6.8.5.5.
(ix) Audible alarm
indicating devices shall be installed in accordance with the requirements of
NFPA 101 §18.3.4 and NFPA 72 §7.4.
(x) Visual fire alarm indicating devices that
comply with the requirements of paragraph (1)(D) of this subsection and NFPA 72
§7.5 shall be provided.
(xi)
Devices for transmitting alarm for alerting the local fire brigade or municipal
fire department of fire or other emergency shall be provided. The devices shall
be listed for the fire alarm service by a nationally recognized laboratory, and
be installed in accordance with such listing and the requirements of NFPA
72.
(xii) A smoke detection system
for spaces open to a corridor shall be provided when required by NFPA 101
§18.3.6.1.
(xiii) A fire alarm
signal notification that complies with NFPA 101 §9.6.3 shall be provided
to alert occupants of fire or other emergency.
(xiv) Wiring for fire alarm detection
circuits and fire alarm notification circuits shall comply with requirements of
NFPA 70 Article 760.
(xv) A smoke
detection system for elevator recall shall be located in elevator lobbies,
elevator machine rooms and at the top of elevator hoist ways as required by
NFPA 72 §6.15.3.10.
(I) The elevator
recall smoke detection system in new construction shall comply with
requirements of American Society of Mechanical Engineers/American National
Standards Institute (ASME/ANSI) A17.1, Safety Code for Elevators and
Escalators, 2000 edition.
(II) The
elevator recall smoke detection system in existing hospitals shall comply with
requirements of ASME/ANSI A17.3, Safety Code for Existing Elevators and
Escalators, 2002 edition.
(xvi) Smoke detectors for initiating smoke
removal from windowless anesthetizing areas shall be provided in accordance
with NFPA 99 §6.4.1.2.
(xvii)
Smoke detectors for initiating smoke removal from surgical suites shall be
provided in accordance with NFPA 99 §6.4.1.3.
(xviii) A smoke detection system for
initiating smoke removal from atriums shall be located above the highest floor
level of the atrium and at return intakes from the atrium in accordance with
NFPA 92B, Guide for Smoke Management Systems in Malls, Atria, and Large Areas,
2000 edition.
(xix) A smoke
detector or detectors for shutdown of air handling units shall be provided. The
detectors shall be installed in accordance with NFPA 90A §6.4.3.
(O) Telecommunications and
information systems. Telecommunications and information systems central
equipment shall be installed in a separate location designed for the intended
purpose. Special air conditioning and voltage regulation shall be provided as
recommended by the manufacturer.
(P) Lightning protection systems. When
installed, lightning protection systems shall comply with NFPA 780, Standard
for the Installation of Lightning Protection Systems, 2000 edition.
(6) General design requirements.
Services that the LSRH provides to patients under the LSRH license shall be
within the LSRH. The services may be provided throughout the LSRH within
identifiable suites, departments or units within the LSRH however all required
units in this chapter shall be in one identifiable contiguous location. To be
included in the LSRH license, a required patient care unit or support areas
shall be physically connected to the LSRH and become contiguous to the LSRH. In
no case may one leave the LSRH, traverse the other occupancies, and then
reenter the LSRH to access the remaining portion of the LSRH. An LSRH may not
occupy two or more noncontiguous areas of non-LSRH occupancies that contain
intervening space of the non-LSRH occupancies even if on the same floor or
other floors.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.