28 Tex. Admin. Code § 34.821 - Manufacturing Operations
(a) Building site
security.
(1) All fireworks manufacturing
plants shall be completely surrounded by a substantial fence having a minimum
height of six feet. All openings in the fence shall be equipped with suitable
gates which shall be kept securely locked at all times when not in actual use.
The main gate may be left open during the regular hours of operation while in
plain view of authorized responsible employees or guards. Conspicuous signs
indicating "Warning," "No Smoking," and "No Trespassing" shall be
posted.
(2) No person other than
authorized employees or representatives of departments of federal, state, or
political subdivisions of the state governments having jurisdiction shall be
allowed in any fireworks manufacturing plants, except by special permission
from the plant office.
(3) All
manufacturing process buildings shall be separated from inhabited buildings,
public highways, and passenger railways in accordance with Table 1 in §
34.824 of this title (relating to
Distance Tables).
(4) The distance
between process buildings shall be in accordance with provisions of Table 2 in
§
34.824 of this title (relating to
Distance Tables).
(5) Distance
between nonprocess buildings, process buildings, and magazines shall be in
accordance with Table 2 in §
34.824 of this title (relating to
Distance Tables).
(6) Magazines
storing Fireworks 1.3G, black powder, and salutes shall be separated from
inhabited buildings, highways, or other magazines containing black powder or
salutes in accordance with Table 3 in §
34.824 of this title (relating to
Distance Tables).
(7) Permissible
bulk storage of Class I flammable liquids (such as gasoline) and flammable
compressed gases at fireworks manufacturing and/or storage facilities shall:
(A) be located at least 100 feet from
processing, storage buildings, or magazines; or flammable liquid tanks may be
located below ground; and
(B)
provide that dispensing units and ventilation pipes be located at least 100
feet from processing or storage buildings or magazines.
(b) Building construction.
(1) Process buildings, except buildings in
which customers' orders are prepared for shipment, shall embody breakaway
construction. The exterior of process buildings shall be constructed of
materials no more combustible than painted wood.
(2) No building shall have a basement or be
more than one story high. Interior surfaces shall be finished to discourage the
accumulation of dust.
(3) Mixing
and pressing buildings shall have conductive flooring, properly
grounded.
(c) Heat,
light, electrical equipment.
(1) No stoves,
exposed flames, or electrical heaters shall be used in any part of a process or
mixing building. Heating shall be by means of steam, indirect hot air
radiation, hot water, or any other means approved by the state fire marshal.
Unit heaters located inside buildings shall be equipped with motors and
switches suitable for use in Class II, Division 1 locations found in National
Electrical Code, 1984, Article 502.
(2) Where artificial lighting is required in
fireworks processing buildings, it shall be by electricity. Temporary or loose
electrical wiring shall not be used.
(3) All wiring in mixing and pressing
buildings shall be in rigid metal conduit or by Type MI cable. The wiring,
lighting fixtures, and switches shall comply with the requirements for Class
II, Division 1 locations in the National Electrical Code, 1984, Article
502.
(4) Wiring, switches, and
fixtures in storage buildings shall comply with the requirements for Class II,
Division 2 locations in the National Electrical Code, 1984, Article
502.
(5) All presses and other
mechanical devices shall be properly grounded.
(6) A master switch shall be provided at the
point where electric current enters the plant, which will, upon being opened,
immediately cut off all electric current to the plant, except that to emergency
circuits.
(d) Maximum
building occupancy and quantities of explosive or pyrotechnic composition.
(1) Occupants in each process building and
magazine shall be limited to those conducting the operations.
(2) No more than 500 pounds of pyrotechnic
and explosive composition shall be permitted at one time in any mixing building
or any building in which pyrotechnic and explosive compositions are pressed or
otherwise prepared for finishing and assembling.
(e) Fire, explosion prevention.
(1) All buildings shall be kept clean,
orderly, and free from accumulation of dust or rubbish. Powder, or other
explosive or pyrotechnic materials, when spilled, shall be immediately cleaned
up and removed from the building.
(2) Rags, combustible pyrotechnic or
explosive scrap, and paper shall be kept separate from each other and placed in
approved marked containers. All waste and reject hazardous material shall be
removed from all buildings daily and removed from the plant at regular
intervals and destroyed in an appropriate manner.
(3) No smoking or carrying of lighted pipes,
cigarettes, cigars, matches, lighters, or open flame is permitted within the
plant fence; except that smoking may be permitted in office buildings, or
buildings used exclusively as lunchrooms or restrooms and in which the presence
of fireworks or any explosive composition is prohibited. Authorized smoking
locations shall be established, so marked, and contain suitable receptacles for
cigarette and cigar butts and pipe residue. At least one Class A fire
extinguisher shall be located in this area. Persons whose clothing is
contaminated with explosives, pyrotechnic, or other dangerous materials shall
not be permitted in smoking locations.
(4) Matches, cigarette lighters, or other
flame-producing devices shall not be brought into any process building or
magazine.
(5) No person shall enter
any fireworks plant in possession of liquor or narcotics, or be under the
influence of liquor or narcotics, while in a fireworks plant.
(6) Each fireworks plant shall have an
employee designated as safety officer. All employees of a fireworks plant, upon
commencing employment and at least annually thereafter, shall be given formal
instruction by the safety officer, regarding proper methods, procedures, and
safety requirements for handling explosives, pyrotechnics, and
fireworks.
(7) In areas where there
is a danger of ignition of materials by sparks, properly maintained and
nonferrous safety hand tools shall be used.
(8) In no case shall oxidizers such as
nitrates, chlorates, or perchlorates be stored in the same building with
combustible powdered materials such as charcoal, gums, metals, sulfur, or
antimony sulfide.
(f)
Testing. Testing of fireworks and components of fireworks shall be performed in
an area set aside for that purpose and located a safe distance from any plant
building or other structure.
(g)
Fire extinguishers; emergency procedures.
(1)
Fire extinguishers shall be provided in all buildings except those in which
pyrotechnic mixtures are exposed.
(2) Emergency procedures shall be established
for each plant which will include personnel instruction in any emergency that
may be anticipated.
(3) Emergency
procedures shall include instruction in the use of portable fire extinguishers
and instructions on the type of fires on which they may and may not be used.
(A) The employees shall be told that if a
fire is involved with or is in danger of spreading to pyrotechnic mixtures,
they are to leave the building at once and follow prescribed procedures for
alerting other employees.
(B)
Extinguishers shall be used on fires involving ordinary combustible
materials.