28 Tex. Admin. Code § 34.826 - Preparing and Conducting Public Pyrotechnic Displays and Flame Effects
(a) Storage. Public display fireworks may be
stored temporarily for a period not to exceed 30 days prior to display date in
a locked area, in regular 1.3G shipping cartons, not accessible by the general
public, and in a location approved by the local fire prevention
officer.
(b) Sobriety. Licensed
operators or assistants shall not be under the influence of or consume
alcoholic beverages or controlled substances during the public
display.
(c) Public display
criteria. Public displays shall be conducted in accordance with the provisions
of the National Fire Protection Association (NFPA) 1123, Code for Fireworks
Display, 1995 Edition, except as modified by paragraphs (1) through (3) of this
subsection. The Appendix to NFPA 1123 is not considered a part of the
requirements of NFPA 1123 and should be used for informational purposes only.
(1) Equivalent material. High density
polyethylene (HDPE) pipe shall be a permissible equivalent material for mortars
if of sufficient strength and durability to fire aerial shells
safely.
(2) Equivalent distance.
The separation distance of NFPA 1123 paragraph 2-3.3.3 between mortars, buried
in the ground or in a trough, shall not apply to a mortar where the mortar is 6
inches (150 mm) in diameter or less, constructed of high density polyethylene
(HDPE), and shells are fired using electrical ignition.
(3) Equivalent distance. The separation
distance of NFPA 1123, paragraph 2-3.3.3.2 between a mortar and the wall of a
trough shall not apply to a mortar where the mortar is 6 inches (150 mm) in
diameter or less and constructed of high density polyethylene (HDPE), shells
are fired using electrical ignition and the adjacent trough wall is braced with
sufficient strength and durability to safely fire the shells. The trough wall
bracing and support shall meet or exceed the following:
(A) two exterior horizontal braces, one along
the bottom of the trough, and a top brace at a distance above the bottom brace
that is at least one half the length of the shortest mortar in the trough, but
not exceeding its top, where bracing consists of angle iron, with a minimum
dimension of one and one half inch by one and one half inch by three sixteenths
of an inch, or other shaped steel of equivalent strength;
(B) a vertical brace attached between the
bottom and top brace spaced no greater than four feet on center along the
length of the trough, where the bracing consists of angle iron, with a minimum
dimension of one and one half inch by one and one half inch by three sixteenths
of an inch, or other shaped steel of equivalent strength; and
(C) a traverse support between the two walls
of the trough, consisting of not less than three eighths of an inch threaded
rod or equivalent material, located approximately half way up the side walls
and located at least every four feet on center along the length of the
trough.
(d)
Firing mortars. All firing shall be done upon order or signal of the licensed
pyrotechnic operator directing the public display.
(e) Public display safety precautions.
(1) A display must be conducted in accordance
with all local regulations and conditions prescribed by the fire prevention
officer at the time of the site inspection.
(2) During the display, at least one approved
Class A type 2 1/2 gallon fire extinguisher or charged garden hose connected to
a water line or equivalent means of fire protection shall be
provided.
(f) Proximate
audience display criteria. Public displays before a proximate audience shall be
conducted in accordance with the provisions of the National Fire Protection
Association (NFPA) 1126, Standards for the Use of Pyrotechnics Before a
Proximate Audience, 1996 Edition. Public displays conducted in accordance with
this section shall include pyrotechnic devices, including 1.3G, 1.4G, and 1.4S,
as defined in NFPA 1126, and individuals conducting such displays shall be
regulated by the provisions of this subchapter as pyrotechnic
operators.
(g) Testing. Testing of
fireworks and components of fireworks intended for public displays shall be
performed in an area set aside for that purpose and located a safe distance
from any plant building or other structure. Such testing shall be permitted by
a licensed manufacturer, or licensed distributor, conducted under the direct
on-site supervision of a licensed pyrotechnic operator, and no public display
permit is required.
(h) Flame
effects criteria. The use of flame effects before an assembly of 50 people or
more shall be conducted in accordance with the provisions of the National Fire
Protection Association (NFPA) 160, Standards for Flame Effects Before an
Audience, 2001 Edition.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.