37 Tex. Admin. Code § 12.7 - Testing, Production, and Packaging
(a)
Licensees must comply with all applicable provisions of the Texas Agriculture
Code and the Texas Department of Agriculture's administrative rules, Title 4,
Part 1.
(b) Representative samples
of all processed products must be tested for the levels of tetrahydrocannabinol
and cannabidiol, and for residual solvents, pesticides, fungicides,
fertilizers, mold, and heavy metals, in accordance with applicable provisions
of the Texas Agriculture Code and Texas Department of Agriculture's
administrative rules, Title 4, Part 1, and Code of Federal Regulations, Title
16, Part 1107.
(c) Only pesticides
of minimum risk exempted under the Federal Insecticide, Fungicide, and
Rodenticide Act,
7 USC
§
136, may be used on cannabis. The
pesticide's active ingredients may only be those listed in
40
CFR §
152.25(f)(1). The
pesticide's inert ingredients may only be those that listed in
40
CFR §
152.25(f)(2);
commonly consumed food commodities, animal feed items, and edible fats and oils
as provided in
40
CFR §
180.950(a),(b) and
(c); and chemical substances listed in
40
CFR §
180.950(e). All
pesticide ingredients (both active and inert) must be listed on the pesticide
container's label. The active ingredient(s) must be listed by label display
name and percentage by weight. Each inert ingredient must be listed by label
display name. The product may not bear claims to control or mitigate organisms
that pose a threat to human health, or insects or rodents carrying specific
diseases. The name of the producer or the company for whom the product was
produced and the company's contact information must be displayed prominently on
the product label. The label cannot include any false or misleading statements.
The label must comply with the Texas Department of Agriculture's administrative
rule, 4 TAC §
7.11, relating to Label
Requirements.
(d) All facilities
must be inspected and approved for their use by a local fire code official, or
by the state fire marshal or local designee of the state fire marshal, and must
meet any required fire, safety, and building code requirements specified in:
(1) National Fire Protection Association
(NFPA) standards;
(2) International
Building Code (IBC);
(3)
International Fire Code (IFC);
(4)
Texas Department of Insurance administrative rules, 28 TAC Chapter 34,
concerning State Fire Marshal; and
(5) Other applicable standards including
following all applicable fire, safety, and building codes in processing and the
handling and storage of the solvent or gas.
(e) Licensees must provide certification by a
Texas licensed professional engineer that the extraction system to be used to
produce low-THC cannabis products was commercially manufactured, safe for its
intended use, and built to codes of recognized and generally accepted good
engineering practices, such as:
(1) The
American Society of Mechanical Engineers (ASME);
(2) American National Standards Institute
(ANSI);
(3) Underwriters
Laboratories (UL); or
(4) The
American Society for Testing and Materials (ASTM).
(f) The extraction process must be
continuously staffed during operations by a registered employee trained in the
extraction process, the transfer of LP-gas where applicable, and all emergency
procedures. All staff training records shall be maintained on-site and made
available upon request by the department or local law enforcement or regulatory
official.
(g) The installation,
operation, repair and maintenance of electrical systems, devices, and
components shall conform to the National Electrical Code, NFPA 70 as adopted by
the Texas Department of Licensing and Regulation. All electrical components
within the extraction room shall be interlocked with the hazardous exhaust
system and when provided, the gas detection system. When the hazardous exhaust
system is not operational, or the gas detection system is activated, light
switches and electrical outlets shall be disabled while leaving lights on that
are necessary for evacuation. The electrical systems shall include:
(1) Extraction room lighting;
(2) Extraction room ventilation
system;
(3) Solvent gas detection
system;
(4) Emergency alarm
systems;
(5) Automatic fire
extinguishing systems;
(6) Vent
failure alarm system; and
(7)
Emergency power backup system.
(h) For extraction processes utilizing
gaseous hydrocarbon-based solvents, a continuous gas detection system shall be
provided. The gas detection threshold shall be no greater than 10% of the
LEL/LFL limit of the materials.
(i)
Signs shall be posted at the entrance to each production area using or storing
carbon dioxide, indicating the hazard. Signs shall be durable and permanent in
nature and not less than 7 inches wide by 10 inches tall. Signs shall bear the
"skull and crossbones" emblem with the warning "DANGER! POTENTIAL OXYGEN
DEFICIENT ATMOSPHERE". NFPA 704 signage shall be provided at the building main
entry and the rooms where the carbon dioxide is used and stored. The main
entrance to the facility and any door to a room where storage, transfer or use
of hazardous materials is conducted shall be appropriately posted with markings
in accordance with NFPA 704, Standard System for the Identification of the
Hazards of Materials for Emergency Response.
(j) Mechanical ventilation within an
extraction or processing facility shall be in accordance with the applicable
local ordinances or the appropriate NFPA standard as adopted by the State Fire
Marshal's Office if no applicable local ordinance exists, and shall have:
(1) Mechanical ventilation in the room or
area of rate of not less than 1 cubic foot per minute per square
foot;
(2) Exhaust system intake
from a point within 12 inches of the floor; and
(3) Ventilation operating at a negative
pressure in relation to the surrounding area.
(k) Any liquid extraction process using
flammable and combustible liquids in which the liquid is boiled, distilled, or
evaporated must operate in compliance with this section and NFPA 30 as adopted
by the State Fire Marshal's Office.
(l) Any processing equipment using a
flammable or combustible vapor or liquid must meet the requirements of NFPA 30
and NRPA 70. Such equipment shall be located within a hazardous exhaust fume
hood, rated for exhausting flammable vapors. Electrical equipment used within
the hazardous exhaust fume hood shall be rated for use in flammable
atmospheres. Heating of flammable or combustible liquids over an open flame is
prohibited, with the exception that the use of a heating element not rated for
flammable atmospheres may be used where documentation from the manufacturer or
a nationally recognized testing laboratory indicates it is rated for heating of
flammable liquids.
(m) Product
extraction processes may use only potable water in compliance with Code of
Federal Regulations, Title 40, Part 141.
(n) All regulated premises shall be located
at least 1000 feet from any private or public school or day care center that
existed prior to the date of initial license application, measured from the
closest points on the respective property lines.
(o) All final packaging for patient
consumption must be in child-resistant packaging designed or constructed to be
significantly difficult for children under five (5) years of age to open and
not difficult for normal adults to use properly as defined by the most current
version of the Code of Federal Regulations, Title 16, Part 1700 and Title 40,
Part 157.2 and American Society for Testing and Materials (ASTM) D3475-15,
Standard Classification of Child-Resistant Packages, ASTM International, West
Conshohocken, PA, 2015.
(p) All
final packaging labels must include:
(1)
Physician's name;
(2) Patient's
name;
(3) Dispensing organization's
name, state license number, telephone number, and mailing address;
(4) Dosage prescribed and means of
administration;
(5) Date the
dispensing organization packaged the contents;
(6) Batch number, sequential serial number,
and bar code when used, to identify the batch associated with manufacturing and
processing;
(7) Potency of the
low-THC cannabis product contained in the package, including the levels of
tetrahydrocannabinol and cannabidiol;
(8) Statement that the product has been
tested for contaminants with specific indications of all findings, and the date
of testing in accordance with Code of Federal Regulations, Title 16, Part 1107;
and
(9) Statement that the product
is for medical use only and is intended for the exclusive use of the patient to
whom it is prescribed. This statement should be in bold print.
(q) The dispensed product may
contain no more than 0.5% by weight of tetrahydrocannabinols and not less than
10% by weight of cannabidiol.
(r)
The storage, transfer, and use of LP- Gas shall conform to the regulations of
the Texas Railroad Commission, including but not limited to NFPA 58, LP Gas
Code (as amended) and the adopted standards of the State Fire Marshal's
Office.
(s) The storage, use and
handling of liquid carbon dioxide shall be in accordance with Chapter 13 of
NFPA 55.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.