37 Tex. Admin. Code § 259.240 - Walls

Walls should be constructed to resist vandalism and facilitate ease of maintenance. Exterior and interior walls within inmate housing and activity areas shall be constructed as follows:

(1) Exterior walls:
(A) a minimum 8" concrete block vertically reinforced by #3 bars 8" on center and all cells filled with 2500 psi grout, or
(B) a minimum of 4" thick concrete plank reinforced with #4 bars 8" on center each way, or
(C) a minimum 3/16" thick steel plate.
(2) Interior walls:
(A) a minimum 6" concrete block vertically reinforced by #3 bars 8" on center and all cells filled with 2500 psi grout, or
(B) a minimum 4" thick concrete plank reinforced with #4 bars 8" on center each way, or
(C) a minimum 3/16" thick steel plate. Innovative design concepts are encouraged and comparable materials and methods approved by the Commission may be utilized for exterior and interior wall construction.