37 Tex. Admin. Code § 259.619 - Life Safety
(a) Provisions shall be
made for the rapid removal of occupants by such reliable means as the remote
control of doors or by keying all locks to keys readily available to jail staff
who are continually on duty and have undergone emergency drills. There shall be
not less than two exits on each floor as remote as practicable from one
another. Travel distance between any point on the floor of the facility to an
exit shall not exceed 150 feet. Travel distance between any room door and an
exit may be increased by 50 feet in fully sprinklered facilities not to exceed
200 feet of total travel distance.
(b) Access to exits shall be marked by
readily visible signs at all locations where the exit is not readily visible
from outer cell doors.
(c) Interior
stairways serving as emergency exits for new facilities and new additions shall
be separated by a two-hour fire rated enclosure and self-closing fire
doors.
(d) Hazardous area
protection shall be provided as required by §
263.21 of this title (relating to
Life Safety).
(e) Self alarming
smoke detectors or smoke detectors which are part of an automatic fire
detection and alarm system shall be provided for each inmate living and day
room area in sufficient numbers to provide prompt warning to occupants and
staff. The alarm systems should be tested in accordance with the manufacturer's
recommendation, but shall be tested at least on calendar quarterly intervals
and test results made a matter of record to include date and results of test,
and signature of the person testing the equipment.
(f) Plans and drills for emergencies shall be
provided as required by §§
263.40-263.42 of this title (relating to
Life Safety).
(g) A manually
operated or automatic smoke removal system shall be provided. (Exception:
Single story minimum security facility buildings which provide direct exiting
to the exterior of the building from the inmate living and day room areas and
whose exit doors are incapable of being locked are not required to provide a
smoke removal system.)
(h) Fire
extinguishers of adequate number and type to meet NFPA 10 shall be provided at
appropriate locations. Fire department connections in proximity to the building
as approved in writing by local fire official shall be provided. A standpipe
and hose system with a one-inch non-collapsible or one and one-half inch
collapsible hose utilizing a minimum of two inches domestic water system shall
be provided.
(i) All life safety
equipment shall be out of reach of inmates, or otherwise secured from
unauthorized tampering. At least one self-contained breathing apparatus shall
be available and maintained in or near each facility control station. All jail
staff shall be trained and quarterly drills conducted in the use of this
equipment. A minimum of one unit shall be provided for each building or a
multi-building facility. All life safety equipment shall be inspected,
maintained, and tested by persons qualified to do so (whether under vendor
contract, by state or private agency or otherwise) in order that such equipment
shall be safe, secure, and fully operative at all times.
(j) Records and reports shall be maintained
as required by §
263.70 and § 263.71 of this
title (relating to Life Safety).