37 Tex. Admin. Code § 351.8 - Physical Plant
(a) Sleeping Units. All
sleeping rooms constructed and/or placed into operation on or after the
effective date of this standard shall be utilized as single occupancy.
(1) Sleeping rooms constructed and/or placed
into operation on or after the effective date of this standard shall have a
minimum ceiling height of seven and one-half feet.
(2) Sleeping rooms constructed and/or placed
into operation on or after the effective date of this standard shall have a
minimum of 60 square feet of floor space.
(3) Residents held in sleeping rooms shall
have access to a toilet above floor level, a washbasin, drinking water, running
water, and a bed above floor level.
(4) There shall be separate sleeping rooms
for male and female residents.
(b) Exits. Facility exits shall be clear of
obstruction and properly marked for evacuation in the event of fire or other
emergency.
(c) Storage. Storage of
cleaning supplies and equipment shall not be accessible to residents.
(d) Safety Plan. Written policies shall
promote the safety of residents, staff, and visitors. The policies shall be
reviewed annually with written documentation submitted by a qualified fire
prevention and safety officer. These shall include, but shall not be limited
to:
(1) maintenance of a current fire drill
log;
(2) proper disposal of
combustible refuse;
(3) a posted
plan for prompt evacuation of the facility;
(4) required quarterly fire drills on all
shifts; and
(5) procedures for use
and control of flammable, toxic, and caustic materials.
(e) Safety Codes. The facility shall conform
to the provisions set forth in the Life Safety Code, National Fire Protection
Association (NFPA), 101 and/or any applicable state and local fire safety
codes. The Life Safety Code may be substituted with local government
ordinances/codes only if said ordinances/codes are specifically written to
include building occupancy for detention and correctional usage.
(1) A formalized facility Life Safety/fire
safety inspection shall be completed prior to the facility becoming
operational.
(2) All subsequent
Life Safety/fire safety shall be conducted at least annually.
(3) All inspection reports shall be reduced
to written documentation which shall include:
(A) an enumeration of the specific codes used
during the inspection;
(B) any
corrective action required;
(C) the
name and title of person conducting the inspection; and
(D) the date(s) of the inspection.
(f) Population. The
population of the facility shall not exceed the rated capacity of the
facility.
(g) Lighting. There shall
be lighting available for the residents.
(h) Lavatory. There shall be a toilet and
washbasin for at least every five residents.
(i) Facility Design. All housing areas shall
provide for the following:
(1) an operable
shower or bath with hot and cold running water for at least every ten
residents;
(2) fully functioning:
(A) heating systems;
(B) ventilation systems; and
(C) cooling systems.
(3) access to a drinking fountain.
(j) New Facilities. All facilities
placed into operation on or after the effective date of this standard shall
provide for the following:
(1) Natural
Lighting. All housing areas shall provide natural light available from a source
within 20 feet of the area.
(2)
Disabled Residents. Rooms or housing units used by disabled residents shall be
designed for their use and provide for their safety and security in accordance
with state and federal law.
(3)
Personal Property. Space shall be provided for secure storage of the resident's
personal property.
(4) Alternate
Power Source. The facility shall have an alternate source of power to operate:
(A) operate lights;
(B) communications systems; and
(C) electric door locks.
(5) Preventive Maintenance.
(A) A written plan shall provide for
emergency repair or replacement of equipment.
(B) Power systems shall be tested at least
every two weeks, the results documented and any deficiencies
corrected.
(C) All emergency
equipment and systems shall be tested at least monthly, the results documented
and any deficiencies corrected.
(6) Ventilation. An alternate means of
ventilation shall be maintained in case regular power is interrupted.
(7) Access for Individuals with Disabilities.
All parts of the facility that are accessible to the public shall be accessible
to and usable by staff and visitors with physical disabilities in accordance
with the Americans with Disabilities Act.
(8) Secure Storage. There shall be a location
for secure storage of restraining devices, and related security equipment. This
equipment shall be readily accessible to authorized persons.
(k) Co-located Facilities. If the
short-term detention facility is located in the same building or is on the
grounds of any type of adult corrections facility, it shall be a separate,
self-contained unit. All applicable federal and state laws pertaining to the
separation of juveniles from adult inmates shall apply.