Utah Admin. Code R315-319-73 - Structural Integrity Criteria for Existing CCR Surface Impoundments
(a) The requirements of Subsections
R315-319-73(a)(1) through (4) apply to all existing CCR surface impoundments,
except for those existing CCR surface impoundments that are incised CCR units.
If an incised CCR surface impoundment is subsequently modified, e.g., a dike is
constructed, such that the CCR unit no longer meets the definition of an
incised CCR unit, the CCR unit is subject to the requirements of Subsections
R315-319-73(a)(1) through (4).
(1) No later
than, December 17, 2015, the owner or operator of the CCR unit shall place on
or immediately adjacent to the CCR unit a permanent identification marker, at
least six feet high showing the identification number of the CCR unit, if one
has been assigned by the state, the name associated with the CCR unit and the
name of the owner or operator of the CCR unit.
(2) Periodic hazard potential classification
assessments.
(i) The owner or operator of the
CCR unit shall conduct initial and periodic hazard potential classification
assessments of the CCR unit according to the timeframes specified in Subsection
R315-319-73(f). The owner or operator shall document the hazard potential
classification of each CCR unit as either a high hazard potential CCR surface
impoundment, a significant hazard potential CCR surface impoundment, or a low
hazard potential CCR surface impoundment. The owner or operator shall also
document the basis for each hazard potential classification.
(ii) The owner or operator of the CCR unit
shall obtain a certification from a qualified professional engineer stating
that the initial hazard potential classification and each subsequent periodic
classification specified in Subsection R315-319-73(a)(2)(i) was conducted in
accordance with the requirements of Section R315-319-73.
(3) Emergency Action Plan (EAP)
(i) Development of the plan. No later than
April 17, 2017, the owner or operator of a CCR unit determined to be either a
high hazard potential CCR surface impoundment or a significant hazard potential
CCR surface impoundment under Subsection R315-319-73(a)(2) shall prepare and
maintain a written EAP. At a minimum, the EAP shall:
(A) Define the events or circumstances
involving the CCR unit that represent a safety emergency, along with a
description of the procedures that will be followed to detect a safety
emergency in a timely manner;
(B)
Define responsible persons, their respective responsibilities, and notification
procedures in the event of a safety emergency involving the CCR unit;
(C) Provide contact information of emergency
responders;
(D) Include a map which
delineates the downstream area which would be affected in the event of a CCR
unit failure and a physical description of the CCR unit; and
(E) Include provisions for an annual
face-to-face meeting or exercise between representatives of the owner or
operator of the CCR unit and the local emergency responders.
(ii) Amendment of the plan.
(A) The owner or operator of a CCR unit
subject to the requirements of Subsection R315-319-73(a)(3)(i) may amend the
written EAP at any time provided the revised plan is has been submitted to and
has received approval from the Director and placed in the facility's operating
record as required by Subsection R315-319-105(f)(6). The owner or operator
shall amend the written EAP whenever there is a change in conditions that would
substantially affect the EAP in effect.
(B) The written EAP shall be evaluated, at a
minimum, every five years to ensure the information required in Subsection
R315-319-73(a)(3)(i) is accurate. As necessary, the EAP shall be updated and a
revised EAP has been submitted to and has received approval from the Director
and placed in the facility's operating record as required by Subsection
R315-319-105(f)(6).
(iii) Changes in hazard potential
classification.
(A) If the owner or operator
of a CCR unit determines during a periodic hazard potential assessment that the
CCR unit is no longer classified as either a high hazard potential CCR surface
impoundment or a significant hazard potential CCR surface impoundment, then the
owner or operator of the CCR unit is no longer subject to the requirement to
prepare and maintain a written EAP beginning on the date the periodic hazard
potential assessment documentation is has been submitted to and has received
approval from the Director and placed in the facility's operating record as
required by Subsection R315-319-105(f)(5).
(B) If the owner or operator of a CCR unit
classified as a low hazard potential CCR surface impoundment subsequently
determines that the CCR unit is properly re-classified as either a high hazard
potential CCR surface impoundment or a significant hazard potential CCR surface
impoundment, then the owner or operator of the CCR unit shall prepare a written
EAP for the CCR unit as required by Subsection R315-319-73(a)(3)(i) within six
months of completing such periodic hazard potential assessment and submit the
EAP to the Director for approval.
(iv) The owner or operator of the CCR unit
shall obtain a certification from a qualified professional engineer stating
that the written EAP, and any subsequent amendment of the EAP, meets the
requirements of Subsection R315-319-73(a)(3) and submit the certification to
the Director.
(v) Activation of the
EAP. The EAP shall be implemented once events or circumstances involving the
CCR unit that represent a safety emergency are detected, including conditions
identified during periodic structural stability assessments, annual
inspections, and inspections by a qualified person.
(4) The CCR unit and surrounding areas shall
be designed, constructed, operated, and maintained with vegetated slopes of
dikes except for slopes which are protected with an alternate form(s) of slope
protection.
(b) The
requirements of Subsections R315-319-73(c) through (e) apply to an owner or
operator of an existing CCR surface impoundment that either:
(1) Has a height of five feet or more and a
storage volume of 20 acre-feet or more; or
(2) Has a height of 20 feet or
more.
(c)
(1) No later than October 17, 2016, the owner
or operator of the CCR unit shall compile and submit to the Director a history
of construction, which shall contain, to the extent feasible, the information
specified in Subsections R315-319-73(c)(1)(i) through (xi).
(i) The name and address of the person(s)
owning or operating the CCR unit; the name associated with the CCR unit; and
the identification number of the CCR unit if one has been assigned by the
state.
(ii) The location of the CCR
unit identified on the most recent U.S. Geological Survey (USGS) 71/2 minute or
15 minute topographic quadrangle map, or a topographic map of equivalent scale
if a USGS map is not available.
(iii) A statement of the purpose for which
the CCR unit is being used.
(iv)
The name and size in acres of the watershed within which the CCR unit is
located.
(v) A description of the
physical and engineering properties of the foundation and abutment materials on
which the CCR unit is constructed.
(vi) A statement of the type, size, range,
and physical and engineering properties of the materials used in constructing
each zone or stage of the CCR unit; the method of site preparation and
construction of each zone of the CCR unit; and the approximate dates of
construction of each successive stage of construction of the CCR
unit.
(vii) At a scale that details
engineering structures and appurtenances relevant to the design, construction,
operation, and maintenance of the CCR unit, detailed dimensional drawings of
the CCR unit, including a plan view and cross sections of the length and width
of the CCR unit, showing all zones, foundation improvements, drainage
provisions, spillways, diversion ditches, outlets, instrument locations, and
slope protection, in addition to the normal operating pool surface elevation
and the maximum pool surface elevation following peak discharge from the inflow
design flood, the expected maximum depth of CCR within the CCR surface
impoundment, and any identifiable natural or manmade features that could
adversely affect operation of the CCR unit due to malfunction or
mis-operation.
(viii) A description
of the type, purpose, and location of existing instrumentation.
(ix) Area-capacity curves for the CCR
unit.
(x) A description of each
spillway and diversion design features and capacities and calculations used in
their determination.
(xi) The
construction specifications and provisions for surveillance, maintenance, and
repair of the CCR unit.
(xii) Any
record or knowledge of structural instability of the CCR unit.
(2) Changes to the history of
construction. If there is a significant change to any information compiled
under Subsection R315-319-73(c)(1), the owner or operator of the CCR unit shall
update the relevant information, submit it to the Director, and place it in the
facility's operating record as required by Subsection
R315-319-105(f)(9).
(d)
Periodic structural stability assessments.
(1) The owner or operator of the CCR unit
shall conduct initial and periodic structural stability assessments and
document whether the design, construction, operation, and maintenance of the
CCR unit is consistent with recognized and generally accepted good engineering
practices for the maximum volume of CCR and CCR wastewater which can be
impounded therein. The assessment shall, at a minimum, document whether the CCR
unit has been designed, constructed, operated, and maintained with:
(i) Stable foundations and
abutments;
(ii) Adequate slope
protection to protect against surface erosion, wave action, and adverse effects
of sudden drawdown;
(iii) Dikes
mechanically compacted to a density sufficient to withstand the range of
loading conditions in the CCR unit;
(iv) Vegetated slopes of dikes and
surrounding areas except for slopes which have an alternate form or forms of
slope protection;
(v) A single
spillway or a combination of spillways configured as specified in Subsection
R315-319-73(d)(1)(v)(A). The combined capacity of all spillways shall be
designed, constructed, operated, and maintained to adequately manage flow
during and following the peak discharge from the event specified in Subsection
R315-319-73(d)(1)(v)(B).
(A) All spillways
shall be either:
(I) Of non-erodible
construction and designed to carry sustained flows; or
(II) Earth- or grass-lined and designed to
carry short-term, infrequent flows at non-erosive velocities where sustained
flows are not expected.
(B) The combined capacity of all spillways
shall adequately manage flow during and following the peak discharge from a:
(I) Probable maximum flood (PMF) for a high
hazard potential CCR surface impoundment; or
(II) 1000-year flood for a significant hazard
potential CCR surface impoundment; or
(III) 100-year flood for a low hazard
potential CCR surface impoundment.
(vi) Hydraulic structures underlying the base
of the CCR unit or passing through the dike of the CCR unit that maintain
structural integrity and are free of significant deterioration, deformation,
distortion, bedding deficiencies, sedimentation, and debris which may
negatively affect the operation of the hydraulic structure; and
(vii) For CCR units with downstream slopes
which can be inundated by the pool of an adjacent water body, such as a river,
stream or lake, downstream slopes that maintain structural stability during low
pool of the adjacent water body or sudden drawdown of the adjacent water
body.
(2) The periodic
assessment described in Subsection R315-319-73(d)(1) shall identify any
structural stability deficiencies associated with the CCR unit in addition to
recommending corrective measures. If a deficiency or a release is identified
during the periodic assessment, the owner or operator unit shall remedy the
deficiency or release as soon as feasible and prepare documentation detailing
the corrective measures taken and submit the documentation to the
Director.
(3) The owner or operator
of the CCR unit shall obtain a certification from a qualified professional
engineer stating that the initial assessment and each subsequent periodic
assessment was conducted in accordance with the requirements of Section
R315-319-73 and submit the certification to the Director.
(e) Periodic safety factor assessments.
(1) The owner or operator shall conduct and
submit to the Director an initial and periodic safety factor assessments for
each CCR unit and document whether the calculated factors of safety for each
CCR unit achieve the minimum safety factors specified in Subsections
R315-319-73(e)(1)(i) through (iv) for the critical cross section of the
embankment. The critical cross section is the cross section anticipated to be
the most susceptible of all cross sections to structural failure based on
appropriate engineering considerations, including loading conditions. The
safety factor assessments shall be supported by appropriate engineering
calculations.
(i) The calculated static factor
of safety under the long-term, maximum storage pool loading condition shall
equal or exceed 1.50.
(ii) The
calculated static factor of safety under the maximum surcharge pool loading
condition shall equal or exceed 1.40.
(iii) The calculated seismic factor of safety
shall equal or exceed 1.00.
(iv)
For dikes constructed of soils that have susceptibility to liquefaction, the
calculated liquefaction factor of safety shall equal or exceed 1.20.
(2) The owner or operator of the
CCR unit shall obtain a certification from a qualified professional engineer
stating that the initial assessment and each subsequent periodic assessment
specified in Subsection R315-319-73(e)(1) meets the requirements of Section
R315-319-73.
(f)
Timeframes for periodic assessments
(1)
Initial assessments. Except as provided by Subsection R315-319-73(f)(2), the
owner or operator of the CCR unit shall complete the initial assessments
required by Subsections R315-319-73(a)(2), (d), and (e) no later than October
17, 2016. The owner or operator has completed an initial assessment when the
owner or operator has and submit to the Director and placed the assessment
required by Subsections R315-319-73(a)(2), (d), and (e) in the facility's
operating record as required by Subsections R315-319-105(f)(5), (10), and
(12).
(2) Use of a previously
completed assessment(s) in lieu of the initial assessment(s). The owner or
operator of the CCR unit may elect to use a previously completed assessment to
serve as the initial assessment required by Subsections R315-319-73(a)(2), (d),
and (e) provided that the previously completed assessment(s):
(i) Was completed no earlier than 42 months
prior to October 17, 2016; and
(ii)
Meets the applicable requirements of Subsections R315-319-73(a)(2), (d), and
(e).
(3) Frequency for
conducting periodic assessments. The owner or operator of the CCR unit shall
conduct and complete and submit to the Director the assessments required by
Subsections R315-319-73(a)(2), (d), and (e) every five years. The date of
completing the initial assessment is the basis for establishing the deadline to
complete the first subsequent assessment. If the owner or operator elects to
use a previously completed assessment(s) in lieu of the initial assessment as
provided by Subsection R315-319-73(f)(2), the date of the report for the
previously completed assessment is the basis for establishing the deadline to
complete the first subsequent assessment. The owner or operator may complete
any required assessment prior to the required deadline provided the owner or
operator submits the assessment to the Director and places the completed
assessment(s) into the facility's operating record within a reasonable amount
of time. In all cases, the deadline for completing subsequent assessments is
based on the date of completing the previous assessment. For purposes of
Subsection R315-319-73(f)(3), the owner or operator has completed an assessment
when the relevant assessment(s) required by Subsections R315-319-73(a)(2), (d),
and (e) has been submitted and approved by the Director and has been placed in
the facility's operating record as required by Subsections R315-319-105(f)(5),
(10), and (12).
(4) Closure of the
CCR unit. An owner or operator of a CCR unit who either fails to complete a
timely safety factor assessment or fails to demonstrate minimum safety factors
as required by Subsection R315-319-73(e) is subject to the requirements of
Subsection R315-319-101(b)(2).
(g) The owner or operator of the CCR unit
shall comply with the recordkeeping requirements specified in Subsection
R315-319-105(f), the notification requirements specified in Subsection
R315-319-106(f), and the internet requirements specified in Subsection
R315-319-107(f).
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.