A. General Requirements.
1. Reference materials for electrical
classifications are available at the UOSH office.
2. All electrical work, installation, and
wire capacities shall be in accordance with the pertinent provisions of the
National Electrical Code, 1990 Edition unless otherwise provided by regulations
of this part.
B.
Classification of Areas.
1. Drilling Wells.
Areas surrounding wells in the process of drilling or being serviced by
drilling rigs shall be classified as follows:
a. Well Head Area.
(1) When the derrick is not enclosed or is
equipped with a wind-break (open top and V door) and the substructure is open
to ventilation, the areas shall be classified as shown in Fig. I-1.
(2) When the derrick floor and substructure
are enclosed, the areas shall be classified as shown in Fig. I-2.
b. Mud Tank.
(1) The area around a mud tank located
outdoors with unrestricted ventilation shall be classified to the extent shown
in Figure I-3.
(2) The area around
a mud tank located in an enclosure shall be classed Class I, Div. II to the
extent of the enclosure as shown in Fig. I-4.
c. Mud Ditch.
When an open ditch or trench is used to connect between mud
tanks, or between shale shaker and mud tanks; or open, active mud pits located
outdoors with unrestricted ventilation, the area shall be classified as shown
for mud tanks in Fig. I-3.
d. Mud Pump
The area surrounding a mud pump shall be unclassified unless
it is located in an area that is classified because of some other
facility.
e. Shale Shaker.
(1) The area surrounding a shale shaker with
unrestricted ventilation shall be classified as shown in Fig. I-5.
(2) When the shale shaker is located in an
enclosure, the area shall be classified as Class I, Division II to the extent
of the enclosure.
f.
Desander - desilter
(1) A desander - desilter
located in an open area or in an adequately ventilated enclosure shall be
classified as shown in Fig. I-6.
(2) A desander - desilter located in an
inadequately ventilated enclosure shall be classified as Class I, Division II
to the extent of the enclosure.
g. Degasser.
The area surrounding a degasser which is a closed system, is
unclassified except for the vent from the degasser, which shall be classified
as shown in Fig. I-7.
h.
Open Sump
The area surrounding an open sump which contains volatile,
flammable liquid shall be classified the same as for a mud tank as shown in
Fig. I-3.
i. Diverter line
vent.
The area around the diverter line shall be classified as
shown in Fig. I-7 for gas vent.
2. Producing Oil and Gas Wells.
Areas adjacent to producing oil and gas wells shall be
classified as follows:
a. Flowing
well.
(1) Area around a flowing well located
in an open area is unclassified where a cellar or below grade sump is not
present.
(2) Area around a flowing
well located in an open area with a cellar or below grade sump shall be Class I
Division I below grade and Class I Division II above grade to the extent shown
in Fig. I-8.
b.
Artificially lifted wells.
(1) Beam pumping
well.
(a) Where a cellar or below grade sump
is not present, the area around a pumping well shall be Class I Division II to
the extent shown in Fig. I-9.
(b)
Area around a beam pumping well where a cellar or below grade sump is present
shall be classified Class I Division I below grade and Class I Division II
above grade to the extent shown in Fig. I-10.
(2) Well equipped with submersible, electric
motor-driven pump.
(a) Area around a well in
an open area being produced with a submersible electric motor-driven pump is
unclassified if a cellar or below grade sump is not present.
(b) Where a cellar below grade sump is
present at a well produced with a submersible, electric motor- driven pump,
Class I Division I and Division II areas shall be classified as shown in Fig.
I-8.
(3) Well produced
with hydraulic subsurface pump.
(a) Area
around a well being lifted with a hydraulic subsurface pump is not classified
when there is no cellar or below grade sump.
(b) Where a cellar is present at a well being
lifted with hydraulic subsurface pump, Class I Division I and Division II area
shall be classified as shown in Fig. I-8.
(4) Gas liftwell.
(a) The area around a gas lift well located
in an open area is unclassified when there is no cellar or below grade
sump.
(b) Areas around a gas lift
well that has a cellar or below grade sump shall be classified as Class I,
Division I or Division II as shown in Fig. I-8.
C. Grounding and
Bonding.
1. Portable and/or Cord and
Plug-connected Equipment.
a. The
noncurrent-carrying metal parts of portable and/or plug-connected equipment
shall be grounded.
b. Portable
tools and appliances protected by an approved system of double insulation, or
its equivalent, need not be grounded. Where such an approved system is
employed, the equipment shall be distinctively marked.
2. Fixed Equipment. Exposed
noncurrent-carrying metal parts of fixed electrical equipment, including
motors, generators, frames and tracks of electrically operated cranes,
electrically driven machinery, etc., shall be grounded.
3. Effective Grounding. The path from
circuits, electrical equipment, structures and conduit or enclosure to ground
shall have a maximum resistance to ground of 25 ohms. Where the resistance
exceeds 25 ohms, one or more driven rod electrodes shall be connected to the
ground side of the system to lower the resistance to 25 ohms maximum.
4. Extension Cords/Cables. Extension
cords/cables used with portable electric tools and appliances shall be of three
wire type.
5. Bonding.
a. Conductors used for bonding and grounding
stationary and moveable equipment shall be of ample size to carry the
anticipated current.
b. When
attaching bonding and grounding clamps or clips, secure and positive
metal-to-metal contact shall be made.
6. Temporary Wiring. All temporary wiring
shall be shall be grounded.
D. Overcurrent Protection.
1. Overcurrent protection shall be provided
by fuses or circuit breakers for each feed and branch circuit, and shall be
based on the current-carrying capacity of the conductors supplied and the power
load being used.
2. No overcurrent
device shall be placed in any permanently grounded conductor, except where the
overcurrent device simultaneously opens all conductors of the circuit or for
motor running protection.
3. When
fuses are installed or removed with one or both terminals energized, special
tools insulated for the voltage shall be used.
E. Switches, Circuit Breakers, and
Disconnecting Means.
1. Each disconnecting
means for motors and appliances, and each service feeder or branch circuit at
the point where it originates, shall be legibly marked to indicate its purpose
unless located and arranged so the purpose is evident.
2. Disconnecting means shall be located or
shielded so that employees will not be injured.
F. Lockouts and/or Tagging.
Where there is danger of machinery being started or
electrical circuits being energized while repairs or maintenance work is being
done, the electrical circuits shall be locked open and/or tagged. Where there
is danger of machinery being started or of steam or air creating a hazard to
workers while repairs or maintenance work is being done, the employees shall
disconnect the lines or lock and tag the main valve closed or blank the line on
all steam driven machinery, air driven machinery, pressurized lines or lines
connected to such equipment if they would create a hazard to workers.
G. Electrical Equipment
Installation and Maintenance.
1. General
Requirements
a. Where different voltages,
frequencies, or types of current (A.C. or D.C.) are to be supplied by portable
cords, receptacles shall be of such design that attachment plugs used on such
circuits are not interchangeable.
b. Attachment plugs or other connectors
supplying equipment at more than 300 volts shall be of the skirted type or
otherwise so designed that arcs will be confined.
c. Cable/cords passing through work areas
shall be covered or elevated to protect it from damage which would create a
hazard to employees.
d. Worn or
frayed electric cables/cords shall not be used.
e. Extension cords/cables shall not be
fastened with staples, hung from nails, or suspended by wire.
2. Facilities and Equipment.
a. Light plant generator shall have an
adequate overload safety device.
b.
All light cords and plug-ins shall be kept in good condition.
c. Rig lights shall be of an approved type
for the area in which they are located.
d. Lamps and reflectors shall be cleaned
frequently.
e. The rays of light
shall be directed toward the objects to be illuminated, and away from the eyes
of the worker.
3. Wiring
and Electrical Equipment Permissible in Class I, Division II areas.
a. Wiring shall employ: Rigid threaded
conduits, lead covered armoured cable, Type SO, SOW, STW, STO, GGW, W, Diesel
Locomotive, or equivalent cable with approved connectors (vapor
proof).
b. Electrical equipment
including fixtures, plugs, receptacles, fittings and enclosures for switches
and controllers shall be sealed and gasketted or totally enclosed gasketted
with threaded hubs (vapor proof).
c. Motors: All A.C. motors shall be totally
enclosed, fan-cooled type (TEFC) or equivalent. D.C. motors located in Class I,
Division II areas will be purged (cooled) with air from a safe
source.