Utah Admin. Code R710-4-5 - Amendments and Additions
(1) Water Supply
Analysis
(a) For proposed construction in
both sprinklered and nonsprinklered occupancies, the architect or engineer
shall provide a water supply analysis as required in NFPA, Standard 13, Chapter
22.
(b) The architect or engineer
shall provide the water supply analysis during the preliminary design phase of
the proposed construction. The AHJ shall not approve the plan review without
the water supply analysis being provided or previously submitted water supply
information within the last 12 months that is approved by the AHJ.
(c) The water analysis shall be
representative of the supply that may be available at the time of a fire as
required in NFPA, Standard 13, 23.2.1.1 and A23.2.1.1.
(2) Fire Alarm Systems
(a) Required Installations
(i) All state-owned buildings, college and
university buildings, other than institutional, with an occupant load of 300 or
more, all schools with an occupant load of 50 or more, shall have an approved
fire alarm system with the following features:
(A) Automatic detection devices that detect
smoke shall be installed throughout all corridors and spaces open to the
corridor at the maximum prescribed spacing of thirty feet on center and no more
than fifteen feet from the walls or smoke detectors shall be installed as
required in NFPA, Standard 72, Section 17.7.
(B) Where structures are not protected or
partially protected with an automatic fire sprinkler system, approved automatic
detectors shall be installed in accordance with the complete coverage
requirements of NFPA, Standard 72.
(C) Manual fire alarm boxes shall be provided
as required. In public and private elementary and secondary schools, manual
fire alarm boxes shall be provided in the boiler room, kitchen, and main
administrative office of each building, and any other areas as determined by
the AHJ.
(b)
Main Panel
(i) An approved key plan drawing
and operating instructions shall be posted at the main fire alarm panel which
displays the location of all alarm zones and if applicable, device addresses.
(ii) The main panel shall be
located in a normally attended area such as the main office or lobby. Location
of the Main Panel other than as stated above, shall require the review and
authorization of the SFM. Where location as required above is not possible, an
electronically supervised remote annunciator from the main panel shall be
located in a supervised area of the building. The remote annunciator shall
visually indicate system power status, alarms for each zone, and give both a
visual and audible indication of trouble conditions in the system. All
indicators on both the main panel and remote annunciator shall be adequately
labeled.
(c) System
Wiring Class
(i) Fire alarm system wiring
shall be designated and installed as follows:
(A) The initiating device circuits shall be
designated and installed Class A as defined in NFPA, Standard 72.
(B) The notification appliance circuits shall
be designated and installed Class A as defined in NFPA, Standard 72.
(C) Signaling line circuits shall be
designated and installed Class A loop as defined in NFPA, Standard 72.
(d) Fan Shut
Down
(A) Fan shut down shall be as required
in IMC, Chapter 6, Section 606.
(B) Duct detectors required by the IMC, shall
be interconnected, and compatible with the fire alarm system.
(3) Time Out and
Seclusion Rooms
(a) Time Out and Seclusion
Rooms are allowed in occupancies protected by an automatic fire alarm system.
(b) A vision panel shall be
provided in the room door for observation purposes.
(c) Time Out and Seclusion Room doors may not
be fitted with a lock unless it is a self-releasing latch that releases
automatically if not physically held in the locked position by an individual on
the outside of the door.
(d) Time
Out and Seclusion Rooms shall be located where a responsible adult can maintain
visual monitoring of the person and room.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.