Section 1.0 Authority
This rule is adopted pursuant to
18 V.S.A. §
1247.
Section 2.0 Purpose
The purpose of this rule is to set forth the requirements for
the testing and remediation of lead in the drinking water of schools and child
care facilities in Vermont.
Section
3.0 Definitions
3.1 "Action
level" means four parts per billion (ppb) of lead.
3.2 "Building" means any structure, facility,
addition, or wing that may be occupied or used by children or students. This
only includes buildings that are owned, controlled, or operated by the
responsible entity.
3.3 "Child care
provider" has the same meaning as in
33 V.S.A. §
3511.
3.4 "Child care facility" or "facility" has
the same meaning as in
33 V.S.A. §
3511.
3.5 "Commissioner" means the Commissioner of
Health.
3.6 "Department" means the
Department of Health.
3.7 "Drinking
water" has the same meaning as in
10 V.S.A. §
1671.
3.8 "Independent school" has the same meaning
as in
16 V.S.A. §
11.
3.9 "Outlet" means a drinking water fixture
currently or reasonably expected to be used for consumption, teeth brushing, or
cooking purposes, including a drinking fountain, an ice machine, or a faucet as
determined by a school district, supervisory union, independent school, or
child care provider.
3.10
"Non-recurring care" means a program that provides child care designed to meet
the short term, temporary child care needs of parents arising from, but not
limited to tourism, recreation, or shopping.
3.11 "Responsible entity" means a school
district, supervisory union, independent school, or child care provider in the
State.
3.12 "Remediation Plan"
encompasses the complete list of planned remediation actions submitted
electronically on the state results website for all of the responsible entity's
tested outlets that are at or above the action level.
3.13 "School district" has the same meaning
as in
16 V.S.A. §
11.
3.14 "Supervisory union" has the same meaning
as in
16 V.S.A. §
11.
Section 4.0 Testing Requirements
4.1 If the concentration of lead in drinking
water indicates that water from an outlet is at or above the action level, the
responsible entity shall ensure remediation at that outlet is conducted as
described in this rule.
4.2 Initial
Lead Testing in 2019-2021 On or before December 31, 2021, each responsible
entity shall collect and have analyzed for lead according to the methods in
Section 5.0 water samples from outlets in the buildings it owns, controls, or
operates that are currently used or reasonably expected to be used for
consumption, teeth brushing or cooking purposes. This includes outlets expected
to be used on a temporary basis such as during temporary relocations.
4.3 New Outlets
4.3.1 All new outlets should be flushed prior
to use for not less than five minutes, twice a day, for three weeks.
4.3.2 Any outlets newly used or newly
installed for consumption, teeth brushing, or cooking purposes shall be tested
and demonstrate first-draw and flush lead concentrations below the action level
prior to use. This includes outlets expected to be used on a temporary basis.
4.3.3 All new outlets shall be
lead-free and compliant with the federal Safe Drinking Water Act as amended, 9
V.S.A. Ch. 63, Subchapter 1C, and determinations by the Commissioner of Health
pursuant to
9 V.S.A. §
2470 e
(2)(A).
4.4 Outlets
exempted from testing
4.4.1. If
both first draw and flush samples of an outlet test lower than 1 ppb for three
testing cycles consistent with this rule, that outlet is not required to be
tested again, subject to Sections 4.4.2, 4.4.3, and 4.5.
4.4.2 If every outlet in buildings owned or
controlled by a responsible entity tests lower than 1 ppb for three testing
cycles, the entity may choose to either:
4.4.2.1. Continue to test all outlets
pursuant to the testing schedule in Section
8;
or
4.4.2.2 Adopt a testing regime
that includes no fewer than five outlets within the entity, not including any
outlet that utilizes a filter. If a responsible entity has fewer than five
taps, all taps must continue to be tested.
4.4.3 Outlets that utilize a water filter
shall be tested regardless of results below detection of 1 ppb.
4.5 Retesting due to building and chemistry
changes
4.5.1 Outlets shall be retested if
there have been plumbing changes unrelated to remediation efforts, and that
could reasonably be foreseen to result in an increase in lead levels coming
from that outlet prior to use.
4.5.2 Outlets shall be retested when there is
a change to water chemistry that could reasonably be foreseen to result in
increased lead levels coming from that outlet prior to use.
4.6 All analysis shall be
conducted by a certified drinking lab pursuant to
18
V.S.A. §
501 b.
Section 5.0 Sampling Methodology
5.1 Pre-sampling Conditions
5.1.1 Samples shall be collected after the
water sits in the pipes for a minimum of 8 hours. Due to samples needing to be
collected when the facility is in regular use, samples shall not be collected
the day after vacations, weekends or holidays.
5.1.1.2 Samples must be collected during
periods of normal use and occupation.
5.1.1.3 If an outlet or facility does not see
regular use or occupancy prior to sampling, the facility shall flush water from
the respective outlets for five minutes, twice a day for a three- week period
prior to sampling.
5.1.2
Aerators shall be left in place during sampling.
5.1.3 Shut-off valves shall not be opened or
closed prior to sample collection. The outlets may be used in the course of
normal operation but no pre-stagnation flushing or plumbing work shall occur in
the week prior to sampling.
5.1.4
Outlet inventory shall be conducted in a format provided by the Department.
5.1.5 Any additional guidance
provided by the Department shall be followed.
5.2 Sampling
5.2.1 Following guidance provided by the
Department, persons designated by the responsible entity shall collect the
following samples from each outlet identified on the outlet inventory using a
250 mL bottle provided by a certified drinking water lab:
5.2.1.1 First Draw Samples shall be collected
from each outlet after the water sits in the pipes for a minimum of 8 hours;
samples shall be collected when the facility is in regular use, not the day
after vacations, weekends or holidays.
5.2.1.2 Flush Samples
Following 30 seconds of flushing after first draw samples are
collected.
Section 6.0 Remediation
6.1 If the concentration for lead in drinking
water from an outlet is at or above the action level, the responsible entity
shall ensure remediation of that outlet is conducted as required in this
rule.
6.2 In conducting
remediation, a responsible entity shall strive to achieve the lowest level of
lead possible in drinking water.
6.3 At a minimum, the responsible entity
shall remediate the outlet consistent with the guidance provided by the
Department and the Vermont Department of Environmental Conservation.
6.4 When testing results are at or above the
action level the responsible entity shall:
6.4.1 Prohibit use of an outlet that is at or
above the action level until implementation of a lead remediation plan and
sampling indicates that lead levels from the outlet are below the action level
within one school day; or
6.4.2
Permanently remove, disable, or otherwise ensure it cannot be accessed by any
person for the purposes of consumption, teeth brushing, or cooking purposes.
6.5 Signage
6.5.1 Posting a sign at an outlet that has
tested at or above the action level is not an acceptable means of remediation.
6.5.2 Responsible entities that
have determined that a sink faucet is not reasonably expected to be used for
consumption, teeth brushing, or cooking purposes, but are easily accessible by
the public, shall have signs stating that such sink faucet should not be used
for consumption, teeth brushing, or cooking purposes. Signs must include
visuals for the non-reader.
Section 7.0 Reporting and Communication
7.1 Initial Testing - Prior to December 31,
2021
7.1.1 At least five school days, or
business days for child care providers, prior to sampling and testing,
responsible entities shall notify all staff, parents or guardians of students
directly in writing or by electronic means of the following:
* the scheduled sampling;
* the requirements for testing;
* why testing is required;
* the potential health effects from exposure to lead in
drinking water;
* information provided by the Department, regarding sources
of lead exposure other than drinking water;
* information regarding how the responsible entity shall
provide notice of the sample results; and
* how the responsible entity shall remediate sample results
that are at or above the action level.
7.1.2 Notify all staff and all parents or
guardians of students directly of the test results and the proposed or taken
remedial action in writing or by electronic means within 10 school days, or
business days for child care providers, after receipt of the laboratory report;
7.1.2.1 Center Based Child Care and Preschool
Programs that provide non-recurring care services shall post the results of all
testing and remediation measures where it will be clearly visible to all
parents and guardians of students and children.
7.1.2.2 Center Based Child Care and Preschool
Programs that provide non-recurring services shall note in children's
enrollment forms that the child is enrolled in non-recurring care services.
7.1.2.3 Center Based Child Care
and Preschool Programs that provide recurring care services shall adhere to
7.1.2 for those parents and guardians of students and children.
7.2 Reporting of
Initial Remediation Actions Initial remediation actions shall be reported by
the responsible entity to the Department via the result website within five
business days.
7.3 Reporting of
Remediation Plans
Remediation Plans shall be submitted by the responsible
entity to the Department via the result website within six months of receipt of
laboratory results.
7.4
Reporting Completion of Permanent Remediation
7.4.1 All permanent remediation actions shall
be completed and reported as soon as practicable but not more than 18 months
from the date of receipt of results indicating a lead concentration at or above
4 ppb.
7.4.2 Following remediation,
every outlet that has been remediated must be sampled and the responsible party
be in possession of testing results documenting the lead level is below the
action level prior to the outlet being placed back into use for consumption,
brushing teeth, or cooking purposes.
7.5 Ongoing Testing after December 31, 2021
7.5.1 Responsible entities shall:
7.5.1.1 At least five school days, or
business days for child care providers, prior to sampling and testing,
responsible entities shall notify all staff, parents or guardians of students
directly in writing or by electronic means of the information specified in
Section 7.1.1
7.5.1.2 Notify all
staff and all parents or guardians of students directly of the test results and
the proposed or taken remedial action in writing or by electronic means within
10 school days, or business days for child care providers, after receipt of the
laboratory report;
7.5.1.3 Notify
all staff and all parents or guardians of students, and students in writing or
by electronic means of what remedial actions have been taken. This notification
requirement can be met by referring parents or guardians of students, and
students to the results website.
7.5.1.4 Child care providers that offer care
to children not regularly scheduled to attend shall post the results of all
testing and remediation measures in a way that is easily viewed by parents,
guardians, staff and the public and on any public website if one is maintained.
A child care provider shall note in the child's file whether they regularly
attend or not as determined by the provider.
7.5.2 Certified Drinking Water Laboratories
shall submit all laboratory results in a format determined by the Department:
7.5.2.1 Within 30 days after analysis has
been completed; and
7.5.2.2 Within
two days of notifying the responsible entity.
Section 8.0 Schedule
Testing entities shall sample in accordance with the
following schedule:
8.1 Child Care
Facilities:
* Once every three (3) years, the child care provider shall
complete water testing. Child care facilities located within or operated by
schools shall comply with the schools testing schedule.
8.2 Schools (See Figure 1):
* Group A - By June 30, 2024, every three years
thereafter
* Group B - By December 31, 2024, every three years
thereafter
* Group C - By June 30, 2025, every three years
thereafter
Section
9.0 Retesting and Evidence of Remediation
Under 18 V.S.A. Chapter 24A and
18 V.S.A. §
104, if the Department has reasonable grounds
to believe that there is a potential harm to public health, the Department may
require responsible entities to retest outlets or provide additional evidence
of effective remediation.
Click here to view
image