Wash. Admin. Code § 296-24-37007 - Ventilation
(1)
Conformance. Ventilating and exhaust systems must be in accordance
with the Standard for Blower and Exhaust Systems for Vapor Removal, NFPA No.
91-1961, where applicable and must also conform to the provisions of this
section.
(2)
General.
You must provide all spraying areas with mechanical ventilation adequate to
remove flammable vapors, mists or powders to a safe location and to confine and
control combustible residues so that life is not endangered. You must keep
mechanical ventilation in operation at all times while spraying operations are
being conducted and for a sufficient time thereafter to allow vapors from
drying coated articles and drying finishing material residue to be
exhausted.
(3)
Independent
exhaust. Each spray booth must have an independent exhaust duct system
discharging to the exterior of the building, except that multiple cabinet spray
booths in which identical spray finishing material is used with a combined
frontal area of not more than 18 square feet may have a common exhaust. If more
than one fan serves one booth, all fans must be interconnected so that one fan
cannot operate without all fans being operated.
(4)
Fan-rotating element. The
fan-rotating element must be nonferrous or nonsparking or the casing must
consist of or be lined with such material. There must be ample clearance
between the fan-rotating element and the fan casing to avoid a fire by
friction, necessary allowance being made for ordinary expansion and loading to
prevent contact between moving parts and the duct or fan housing. Fan blades
must be mounted on a shaft sufficiently heavy to maintain perfect alignment
even when the blades of the fan are heavily loaded, the shaft preferably to
have bearings outside the duct and booth. All bearings must be of the
self-lubricating type, or lubricated from the outside duct.
(5)
Electric motors. You must
not place electric motors driving exhaust fans inside booths or ducts. See also
WAC 296-24-37005.
(6)
Belts. Belts must not enter
the duct or booth unless the belt and pulley within the duct or booth are
thoroughly enclosed.
(7)
Exhaust ducts. Exhaust ducts must be constructed of steel and must
be substantially supported. Exhaust ducts without dampers are preferred;
however, if dampers are installed, you must maintain them so that they will be
in a full open position at all times the ventilating system is in operation.
(a) You must protect exhaust ducts against
mechanical damage and have a clearance from unprotected combustible
construction or other combustible material of not less than 18
inches.
(b) If combustible
construction is provided with the following protection applied to all surfaces
within 18 inches, clearances may be reduced to the distances indicated:
(i) 8- gauge sheet metal on 1/4-inch 12
inches. asbestos mill board.
(ii)
28- gauge sheet metal on 1/8-inch 9 inches. asbestos mill board spaced out 1
inch on noncombustible spacers.
(iii) 22- gauge sheet metal on 1-inch 3
inches. rockwool batts reinforced with wire mesh or the equivalent.
(iv) Where ducts are protected with an
approved automatic sprinkler system, properly maintained, the clearance
required in (7)(a) of this section may be reduced to 6 inches.
(8)
Discharge
clearance. Unless the spray booth exhaust duct terminal is from a
water-wash spray booth, the terminal discharge point must be not less than 6
feet from any combustible exterior wall or roof nor discharge in the direction
of any combustible construction or unprotected opening in any noncombustible
exterior wall within 25 feet.
(9)
Air exhaust. You must not direct air exhaust from spray operations
so that it will contaminate makeup air being introduced into the spraying area
or other ventilating intakes, nor directed so as to create a nuisance. You must
not recirculate air exhausted from spray operations.
(10)
Access doors. When
necessary to facilitate cleaning, you must provide exhaust ducts with an ample
number of access doors.
(11)
Room intakes. Air intake openings to rooms containing spray
finishing operations must be adequate for the efficient operation of exhaust
fans and must be so located as to minimize the creation of dead air
pockets.
(12)
Drying
spaces. You must only dry freshly sprayed articles in spaces provided
with adequate ventilation to prevent the formation of explosive vapors. In the
event adequate and reliable ventilation is not provided you must consider such
drying spaces a spraying area. (See also WAC
296-24-37019.)