Wash. Admin. Code § 296-45-345 - Grounding for the protection of employees
(1) Application. This section applies to the
grounding of transmission and distribution lines and equipment for the purpose
of protecting employees. Subsection (4) of this section also applies to the
protective grounding of other equipment as required elsewhere in this
section.
(2) General. For the
employee to work lines or equipment as deenergized, the lines or equipment must
be deenergized under the provisions of WAC
296-45-335
and must be grounded as specified in subsections (3) through (9) of this
section. However, if the employer can demonstrate that installation of a ground
is impracticable or that the conditions resulting from the installation of a
ground would present greater hazards than working without grounds, the lines
and equipment may be treated as deenergized provided all of the following
conditions are met:
(a) The lines and
equipment have been deenergized under the provisions of WAC
296-45-335.
(b) There is no possibility of contact with
another energized source.
(c) The
hazard of induced voltage is not present.
(3) Equipotential zone. Temporary protective
grounds and bonding jumpers must be placed at such locations and arranged in
such a manner as to prevent each employee from being exposed to hazardous
differences in electrical potential.
| Note: | This may require bonding equipment together. |
(4)
Protective grounding equipment.
(a) Protective
grounding equipment must be capable of conducting the maximum fault current
that could flow at the point of grounding for the time necessary to clear the
fault. This equipment must have an ampacity greater than or equal to that of
No. 2 AWG copper.
(b) Grounding
jumpers must have approved ferrules and grounding clamps that provide
mechanical support for jumper cables independent of the electrical connection.
| Note: | Guidelines for protective grounding equipment are contained in American Society for Testing and Materials Standard Specifications for Temporary Grounding Systems to be Used on Deenergized Electric Power Lines and Equipment, ASTM F855-2015. |
(c)
Protective grounds must have an impedance low enough to cause immediate
operation of protective devices in case of accidental energizing of the lines
or equipment.
(5)
Testing. Before any ground is installed, lines and equipment must be tested and
found absent of nominal voltage, unless a previously installed ground is
present.
(a) Inspection before use: Grounding
equipment must be given a visual inspection and all mechanical connections must
be checked for tightness before each use.
(b) Ground surface cleaning: The surface to
which the ground is to be attached must be clean before the grounding clamp is
installed; otherwise, a self-cleaning clamp must be used.
(6) Order of connection. The employer must
ensure that, when an employee attaches a ground to a line or to equipment, the
employee attaches the ground-end connection first and then attaches the other
end by means of a live-line tool. For lines or equipment operating at 600 volts
or less, the employer may permit the employee to use insulating equipment other
than a live-line tool if the employer ensures that the line or equipment is not
energized at the time the ground is connected or if the employer can
demonstrate that each employee is protected from hazards that may develop if
the line or equipment is energized.
(7) Order of removal. When a ground is to be
removed, the grounding device must be removed from the line or equipment using
a live-line tool before the ground-end connection is removed.
(8) Additional precautions. When work is
performed on a cable at a location remote from the cable terminal, the cable
cannot be grounded at the cable terminal if there is a possibility of hazardous
transfer of potential should a fault occur.
(9) Removal of grounds for test. Grounds may
be removed temporarily during tests. During the test procedure, the employer
must ensure that each employee uses insulating equipment and is isolated from
any hazards involved, and the employer must institute any additional measures
as may be necessary to protect each exposed employee in case the previously
grounded lines and equipment become energized.
(10) Conductor separation: In cases where the
conductor separation at any pole or structure is so great as to make it
impractical to apply shorts on all conductors, and where only one conductor is
to be worked on, only that conductor which is to be worked on needs to be
grounded.
(11) Ground personnel: In
cases where ground rods or pole grounds are utilized for personal protective
grounding, personnel working on the ground should maintain sufficient distance
from such equipment or utilize other approved procedures designed to prevent
"touch-and step potential" hazards.
| Note: | See Appendix B of this chapter for protection from step and touch potentials. |
Notes
Statutory Authority: RCW 49.17.010, [49.17].040, [49.17].050 and [49.17].060. 98-07-009, § 296-45-345, filed 3/6/98, effective 5/6/98.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.