Wash. Admin. Code § 51-11R-40211 - Table R40212-Insulation and fenestration requirements by component
TABLE R402.1.2 INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa
|
CLIMATE ZONE 5 AND MARINE 4 |
|
|
Fenestration U-factorb |
0.30 |
|
Skylight U-factor |
0.50 |
|
Ceiling U-factor |
0.024 |
|
Above-Grade Wall U-factor |
0.056 |
|
Floor U-factor |
0.029 |
|
Slab on Grade F-factor |
0.54 |
|
Below Grade 2' Depth |
|
|
Wall U-factor |
0.042 |
|
Slab F-factor |
0.59 |
|
Below Grade 3.5' Depth |
|
|
Wall U-factor |
0.040 |
|
Slab F-factor |
0.56 |
|
Below Grade 7' Depth |
|
|
Wall U-factor |
0.035 |
|
Slab F-factor |
0.50 |
a U-factors or F factors shall be obtained from measurement, calculation, or an approved source or as specified in Section R402.1.5.
b A maximumU -factor of 0.32 shall apply to vertical fenestration products installed in buildings located above 4000 feet in elevation above sea level, or in windborne debris regions where protection of openings is required under Section R301.2.1.2 of the International Residential Code.