W. Va. Code R. § 64-47-10 - [Effective 7/1/2025] Grease Traps
10.1. There
shall be grease traps for all restaurants and similar establishments where a
large quantity of grease and fats in liquid wastes will occur.
10.2. The location of the external grease
trap shall be within 30 feet from the fixtures served. If meeting this distance
requirement is not possible and thus, external grease traps are not possible
due to existing conditions or physical limitations, the Commissioner may allow
internal grease traps.
10.3. Only
those plumbing fixtures into which the grease and fats are discharging shall
connect to the grease trap.
10.4.
The external grease trap shall be a minimum 150 gallons capacity. Larger grease
traps may be a requirement depending upon the loading.
10.5. The external grease trap shall be in an
easily accessible place outside the building served.
10.6. Grease traps with manhole covers shall
be designed to withstand expected loads and prevent access by
children.
10.7. The manhole cover
shall be secured by a bolt or locking mechanism and be constructed of round
cast iron or similar construction with sufficient weight to prevent
unauthorized access.
10.8. The
Commissioner may specify either method of limiting access to the manhole, if
the method conforms to subsection 10.7 of this section and prevents
unauthorized access.
10.9. A hotel
or restaurant shall ensure that a grease trap manhole is closed and secured or
locked, if applicable, at all times, except when accessed for pumping or
maintenance.