Wis. Admin. Code Department of Agriculture, Trade and Consumer Protection ATCP 93.445 - Seldom-used and temporarily out of service tank systems
(1) OPERATIONAL
REQUIREMENTS. Owners or operators of aboveground seldom-used and temporarily
out of service tanks shall comply with the applicable requirements of s.
ATCP 93.545(1).
(2) PLACING A TANK BACK INTO SERVICE.
(a) The respective API 653 or STI SP001
inspection cycle shall be current for a tank before it is placed back into
service.
(b) All leak detection,
overfill, vent and fire valve devices shall be verified as functional before
being placed back into service.
(c)
1. Tank systems out of service for more than
365 days shall pass a tightness test of the tank ullage portion in accordance
with s.
ATCP 93.515(10), to assure that tank
connections are liquid- and vapor-tight before the tanks are placed back into
service.
2. Field-erected tank
systems out of service for more than 365 days shall be evaluated for
suitability for service in accordance with API 653, to assure that the tank and
tank connections are liquid- and vapor-tight before the tanks are placed back
into service.
3. Underground
product piping out of service for more than 365 days shall pass a tightness
test in accordance with s.
ATCP 93.515(4).
(3) NON-COMPLYING TANK SYSTEMS. Tank systems
that do not comply with this section or in-use tank system requirements are
abandoned tanks and shall be closed in accordance with s.
ATCP 93.460 within 60 calendar days of
non-compliance.